Page 71
Output 120/240V AC Module (32 or 16 points) Specification Table
Characteristic Function Part number
Output 120/240V AC module specifications Switches an external AC source to 32 or 16 loads 32 point M.1016.9076 (old # 502-03641-03) 16 point M.1016.8943 (old # 502-03551-03) AC source requirements Nominal 115 VAC, range 48 to 240V AC Field side connector 32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals Protection of logic circuits Optical isolation between the logic and field side, 2830 V AC Arrangement of outputs Four groups of 8 or 4 solid-state switches. Each group can use its own AC source, or one source can be daisy-chained. UL 508 spacing Fuse per group of 8 Fast-acting, UL rated 3A 250V AC metric fuse, 5 x 20 mm Maximum current per 2 A of continuous current for the group; group 32 point each switch is rated at .75 A continuous 16 point each switch is rated at 2 A continuous Indicator lights, output An LED for each output circuits Indicator light, module A DIAG LED turns OFF when the module passes its diagnostic tests at power-on. Indicator light, fuses A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with a missing or open fuse. Switch characteristics Solid-state switches. Switch voltage, maxi32 point 1V AC @ .75A RMS mum ON 16 point 1.2V AC @ 2A RMS Surge current, maximum 20 A for 2 cycles, every 2 seconds; fuse blows if this is exceeded. Frequency 50 / 60 Hz. ± 5% Time delay on, maximum 1/2 cycle (turns on at zero voltage) Time delay off, maximum 1/2 cycle (turns off at zero voltage) Minimum load current 50 mA Leakage current in OFF 4 mA @ 120 VAC 6 mA @ 240V AC state, max Response to scan loss All outputs are reset to the OFF state (present) Logic side power require- 32 point 1 mA @ +5V ments (typical) 7 mA per energized output @ +5V 16 point 1 mA @ +5V 23 mA per energized output @ +5V
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
67
Page 72
Output 120/240V AC Module (32 or 16 points) Field side power dissipa- 32 point 11.0 W tion, worst case 16 point 12.0 W Operating temperature 7°C to 55°C (45°F to 131°F) range Storage temperature range -40° C to 85°C (-40°F to 185°F) Humidity 5 to 95%, non-condensing EMC Compliant Emissions Operates with emissions below EN55011/ CISPR 11 Class A limits Noise immunity Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information. UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers Physical size 1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm Vibration (per IEC 68-2- 10-57 Hz (constant amplitude .15 mm) 6) 57-2000 Hz (acceleration 2 g) Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
68
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 73
Input/Output TTL Module (24 inputs/8 outputs)
Input/Output TTL Module (24 inputs/8 outputs) The TTL (Transistor-Transistor Logic) module provides 24 optically isolated input points to monitor the status of TTL devices and 8 optically isolated output points to interface with TTL devices (or other 5V DC devices such as photoelectric sensors). The module can also be used as a feedback module to read devices like linear displacement transducers (TEMPOSONICS™, BALLUFF) or absolute encoders. These devices provide high speed, low voltage, low noise parallel digital signals. An external +5V DC is required for operation. The DIAG LED goes on briefly while the diagnostic tests are running.
TTL (24 inputs/8 outputs)
Name of Module Diagnostic LED
TTL
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
Giddings & Lewis
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
69
Page 74
Input/Output TTL Module (24 inputs/8 outputs) Specification Table
Characteristics
TTL module specifications
Function
Monitors on/off states of 24 TTL inputs and controls on/off state of 8 TTL outputs.
Part number
M.1016.9291 (old # 502-03810-03)
Field side connector
40 pin card edge connector, screw terminals
External power supply
+5V ±5% 450 mA
Isolation
2500 VRMS between field side and logic side
Input characteristics
Vin high2.0 V minimum Vin low0.8 V maximum Iin high 1µA maximum Iin low - -0.65 mA maximum Minimum input pulse width1 µsec
Output characteristics
Vol -0.8V maximum @ Io = 10 mA (sinking) Voh -4.0V minimum @ Io = -10 mA (sourcing) Output turn on/off time - 300 nano sec Maximum cable length - 3 meters (approximately 10 feet)
Logic side power requirements (typical)
+5V @ 450 mA
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
70
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 75
Input/Output TTL Module (24 inputs/8 outputs)
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
71
Page 76
Input/Output 24V DC Sink Module (16/8 points)
Input/Output 24V DC Sink Module (16/8 points) The input section of the 24V DC I/O module converts DC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU. An "on" signal is nominally 24 VDC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 16 LEDs indicate the logic state of each input. The output section of the module sinks voltage for eight individual loads from one DC power supply. The external supply is nominally 24 volts, but can be between 5 and 32 volts. Eight LEDs on the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in the active circuit is open or missing. The DIAG LED goes on briefly while the diagnostics tests are running.
24V DC Input/Output Module (16/8 sink pt)
IN/OUT
24 V DC
Name of Module Diagnostic LED Input LEDs “Fuse Blown” LED Output LEDs
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
72
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 77
Input/Output 24V DC Sink Module (16/8 points) Specification Table
Characteristic
Module specifications
Function
Monitors on/off states from up to 16 DC voltage inputs Sinks an external DC source to eight loads
Part number
M.1016.9350 (old # 502-03843-02)
Field side connector
40-pin card edge connector, screw terminals
Logic side power requirements (typical)
30 mA 7 mA per energized input 25 mA per energized output
Field side power dissipation (worst case at 32V DC)
3.6 W for inputs 4.0 W for outputs
Indicator lights, input/output circuits
An LED for each input/output
Indicator light, module
A DIAG LED turns OFF when the module passes its diagnostic tests at power-on
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to the eight outputs when a fuse is missing or open
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
@ @ @
5V +5 V +5 V
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
73
Page 78
Input/Output 24V DC Sink Module (16/8 points)
Input section(16 pt) Input signals (exceed IEC standards) Nominal 24V DC on, 0V DC off UH Max (max. allowed voltage)
30V DC
IH Max (max. current @ 30 VDC)
7.5 mA
UL Min
Polarity independent
Guaranteed on
14V DC
IH Min (min. current @ UH Min)
2.8 mA
Guaranteed off
5V DC
IT Min (current allowed when off)
.75 mA
Time delay on
.75 mA
Time delay off
1 ms max
Protection of logic circuits
Optical isolation between the logic and field sides 4000 V peak
Input groups
Two groups of 8 IEC Type 1 inputs per NEMA Standard, ICS 3-1983, Table 3-304-2. UL 508 spacing
Output section (8 pt sink) DC source requirements
Nominal 24V DC; range 5 to 32V DC
Protection of logic circuits
Optical isolation between the logic and field side
Grouping of output
One grup of 8 solid-state switches UL 508 spacing
Fuse per group of 8 switches
Fast-acting UL rated 3 A 250V AC metric fuse, 5 x 20 mm
Maxiumum current per group
2 A of continuous current for the group; each switch is rated at .4 A continuous
Switch characteristics
Solid-state switches
Time delay on for resistive loads
30 µsec max
Time delay off for resistive loads
300 µsec max
Leakage current in off state
0.5 mA max
Switch voltage, maxiumum ON
1.8 VDC@ .4A
Surge current, maxiumum
2.5 A for 40 msec., every 2 seconds
Response to scan loss (present)
All outputs are reset to the OFF state
74
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 79
Input/Output 24V DC Source Module (16/8 points)
Input/Output 24V DC Source Module (16/8 points) The input section of the 24V DC I/O module converts DC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU. An “on” signal is nominally 24V DC, but can be any level between 14 and 30 volts. An “off” signal is any level below 5V. The wiring configurations may be sink or source. 16 LEDs on the module indicate the logic state of each input. The output section of the module sources voltage for eight individual loads from one or two DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. Eight LEDs indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostics tests are running.
24V DC input/output module (16/8 source PT) IN/OUT
24 V DC
Name of Module Diagnostic LED Input LEDs “Fuse Blown” LED Output LEDs
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
Giddings & Lewis
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
75
Page 80
Input/Output 24V DC Source Module (16/8 points) Specification Table
Characteristic
Input/Output module specifications
Function
Monitors on/off states from up to 16 DC voltage inputs Sources an external DC source to 8 loads
New Part number
M.1016.9348 (old # 502-03842-02)
Field side connector
40-pin card edge connector, screw terminals
Logic side power requirements (typical)
30 mA @ +5V 7 mA per energized input @ +5V 23 mA per energized output @ +5V for outputs
Field side power dissipation worst case (at 32V DC)
3.6 W for inputs 6.4 W for outputs
Indicator lights, input/output circuits
An LED indicates the logic state of each input/output
Indicator light, module
The DIAG LED goes OFF when the module passes power-on diagnostic tests
Indicator light, fuses
A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse
Operating temperature range
7°C to 55°C (45°F to 131°F)
Storage temperature range
-40°C to 85°C (-40°F to 185°F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
Noise immunity
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27)
Four shocks per axis (15g/11 msec)
76
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis