Page 61

Output 24V DC Source Module (32 or 16 points)

Output 24V DC Source Module (32 or 16 points) The output 24V DC module sources voltage for individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in the following configurations. • •

32 point 24V DC output module 16 point 24V DC output module

32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running.

OUTPUT 24V DC Source Module 32 point

OUTPUT 24 V DC

16 point

Name of Module Diagnostic LED “Fuse Blown” LED

OUTPUT 24 V DC

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

Giddings & Lewis

Screw terminal connector

Door

Name of Module Diagnostic LED “Fuse Blown” LED Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

57

Page 62

Output 24V DC Source Module (32 or 16 points) Specification Table

Characteristic Function Part number

Output 24V DC module specifications Sources an external DC supply to 16/32 loads 32 point M.1016.9070 (old # 502-03640-02 16 point M.1016.8933 (old # 502-03549-02) DC source requirements Nominal 24V DC; range 5 to 32V DC Field side connector 32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals Protection of logic circuits Optical isolation between the logic and field side Grouping of outputs Four groups of 8 or 4 solid-state switches. Each group may use its own DC supply, or one supply may be daisychained. UL 508 spacing Fuse per group of 8 switches Fast-acting, UL rated 3 A 250V AC metric fuse, 5 x 20 mm Maximum current per group 2 A of continuous current for the group; 32-point - each switch is rated at .4 A continuous 16 point - each switch is rated at .75 A continuous Indicator lights, output circuits An LED for each output Indicator light, module A DIAG LED turns OFF when the module passes its diagnostic tests at power-on Indicator light, fuses A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse Switch characteristics Solid-state switches Time delay on for resistive loads 30 µsec max Time delay off for resistive 300 µsec max loads Leakage current in off state 0.5 mA max Switch voltage, maximum ON 32 point 1.8V DC @ .4 A 16 point 1.6V DC @ .75 A Surge current, maximum 32 point 2.5 A for 40 msec., every 2 seconds 16 point 5 A for 40 msec, every 2 seconds; fuse blows if this is exceeded Response to scan loss (present) All outputs are reset to the OFF state Logic side power requirements 1 mA @ +5V (typical) 32 point25 mA per energized output@ +5V 16 point23 mA per energized output @ +5V Field side power dissipation, 15.8 W worst case (at 32 VDC) Operating temperature range 7°C to 55°C (45°F to 131°F) Storage temperature range -40°C to 85°C (-40°F to 185°F)

58

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 63

Output 24V DC Source Module (32 or 16 points) Humidity EMC Compliant Emissions

Shock (per IEC 68-2-27)

5 to 95%, non-condensing Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: •Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 •RF electromagnetic fields per IEC 1000-4-3 •Electrical fast transients per IEC 1000-4-4 on incoming power lines File No. E126417 NRAQ Programmable Controllers 1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm 10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g) Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

Noise immunity

UL and C/UL Listed Physical size Vibration (per IEC 68-2-6)

59

Page 64

Output 24V DC Sink Module (3 versions)

Output 24V DC Sink Module (3 versions) The output 24V DC module sinks voltage for 32 individual loads from one or more DC power supplies. Each external supply is nominally 24 volts, but can be between 5 and 32 volts. It is available in three configurations: • • •

32 point, all diode protected 32 point, 16 diode protected/16 unprotected 32 point, all unprotected

32 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running.

OUTPUT 24V DC Source Module (32 pt)

OUTPUT 24 V DC

Name of Module Diagnostic LED “Fuse Blown” LED

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

60

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 65

Output 24V DC Sink Module (3 versions) Specification Table

Characteristic Function Part number

Output 24V DC module (32 pt sink) specifications Sinks an external DC source to 32 loads 16 protected/16 unprotected M.1016.9127 (old # 50203674-02) All diode protected M.1016.9130 (old # 502-03674-22) All unprotected M.1016.9133 (old # 502-03674-42) DC source requirements Nominal 24V DC; range 5 to 32V DC Field side connector 40-pin card edge connector, screw terminals Protection of logic circuits Optical isolation between the logic and field side Grouping of outputs Four groups of 8 solid-state switches. Two groups share a DC supply. Two DC supplies are allowed per module. (One supply may be daisy chained.) UL 508 spacing Fuse per group of 8 switches Fast-acting, UL rated 3A 250V AC metric fuse, 5 x 20 mm Maximum current per group 2 A of continuous current for the group; each switch is rated at .4 A continuous Indicator lights, output cir- An LED for each output cuits Indicator light, module A DIAG LED turns OFF when the module passes its diagnostic tests at power-on Indicator light, fuses A logic side LED lights to indicate a "blown fuse" condition when power is on to a group with missing or open fuse Switch characteristics Solid-state switches Time delay on for resistive 30 µsec max loads Time delay off for resistive 300 µsec max loads Leakage current in off state 0.5 mA max Switch voltage, maximum 1.8V DC @ .4 A ON Surge current, maximum 2.5 A for 40 msec., every 2 seconds Response to scan loss All outputs are reset to the OFF state. (present) Logic side power require- 1 mA @+5V ments 25 mA per energized output @ +5V (typical) Field side power dissipation, 15.8 W worst case (at 32 VDC) Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

61

Page 66

Output 24V DC Sink Module (3 versions) Operating temperature range 7°C to 55°C (45°F to 131°F) Storage temperature range -40°C to 85°C (-40°F to 185°F) Humidity 5 to 95%, non-condensing EMC Compliant Emissions Operates with emissions below EN55011/ CISPR 11 Class A limits Noise immunity Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information. UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers Physical size 1.6" wide x 12" high x 8.4" deep (including latch). 41 mm x 305 mm x 213 mm Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g) Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)

62

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 67

Output Relay Module (8 points)

Output Relay Module (8 points) The relay output module can switch eight relay contacts. Four relays are normally open(NO)/ normally closed(NC) form C type and four are normally open (NO) form A type. Eight LEDs in the upper section of the module indicate the logic state that drives each relay. The DIAG LED goes on briefly while the diagnostic tests are running.

OUTPUT RELAY Module (8 PT)

OUTPUT

RELAY

Name of Module Diagnostic LED Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

63

Page 68

Output Relay Module (8 points) Specification Table

Characteristic

Output relay (8) module specification

Function

Switches eight relay contacts

Part number

M.1016.9089 (old # 502-03644-03)

Field side connector

25 pin card edge connector, screw terminals

Output channels

8

Relay characteristics Contact types

Four form C (NO/NC) Four form A (NO)

Maximum switching voltage

280V AC resistive load; 50V DC resistive load

Minimum switching current

100 mA

Maximum switching current (DC)

0-24V DC @ 3 A 30 VDC 40V DC @ 1.5 A 50 VDC

Maximum switching current (AC)

0-120V AC @ 3 A 280V AC @ 2.5 A

Initial contact resistance

100 m¾

Turn on time (resistive load)

10 msec maximum

Turn off time (resistive load)

10 msec maximum

Expected life, electrical

105 operations minimum

Expected life, mechanical

107 operations minimum

Breakdown voltage between contacts

750 Vrms for 1 minute

Breakdown voltage between contacts and coil

1500 Vrms for 1 minute

@ 2.5 A @ 1.0 A

Maximum switching frequency 20 energize/deenergize cycles/min. (to satisfy expected life ratings) Indicator light, module

DIAG LED turns off after the module passes its diagnostic tests. A logic side LED for each relay turns on when the logic side energizes the relay.

Isolation

Electromechanical relay provides protection between logic and field side

Logic side power requirements (typical)

1 mA @ 5V 5 mA @ +15V 39 mA per energized output @ +15V (Pt 1-4) 24 mA per energized output @ +15V (Pt 5-8)

64

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 69

Output Relay Module (8 points) Operating temperature range Storage temperature range Humidity EMC Compliant Emissions Noise immunity

7°C to 55 C (45°F to 131°F) -40°C to 85°C (-40°F to 185°F) 5 to 95%, non-condensing Refer to the EMC Guidelines for more information. Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines

UL and C/UL Listed Physical size

File No. E126417 NRAQ Programmable Controllers 1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

65

Page 70

Output 120/240V AC Module (32 or 16 points)

Output 120/240V AC Module (32 or 16 points) The 120/240V output module switches voltage for individual loads from one or more AC power sources. Each external AC source is nominally 115 VAC, but can be between 48 and 240 volts. It is available in the following configurations: • •

32 point 120/240V AC output module 16 point 120/240V AC output module

32 or 16 LEDs in the upper section of the module indicate the logic state that drives each output. Another LED labeled FB turns on if the fuse in any active circuit is open or missing. The DIAG LED goes on briefly while the diagnostic tests are running.

OUTPUT 120/240 VAC Module 32 point 16 point

INPUT

12 V DC

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

66

Name of Module Diagnostic LED

Name of Module Diagnostic LED “Fuse Blown” LED

Indicator LEDs

Indicator LEDs

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

Giddings & Lewis