Page 51

Input 24V DC Module (32 or 16 points) EMC Compliant Emissions Noise immunity

CE Marked

UL and C/UL Listed Physical size Vibration (per IEC 68-2-6) Shock (per IEC 68-2-27)

Giddings & Lewis

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge(4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information. Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204 File No. E126417 NRAQ Programmable Controllers 1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm 10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g) Four shocks per axis (15g/11 msec)

PiC900 Controls Motion Solutions Product Guide

47

Page 52

Input 24V DC Module (16 switch)

Input 24V DC Module (16 switch) The input switch module converts the position status of 16 on/off switches mounted on the faceplate into logic levels that the CPU can use. The on/off position status of each switch is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. 16 LEDs in the upper section of the module indicate the logic state of each switch input. The DIAG LED goes on briefly while the diagnostic tests are running.

INPUT Switch Module (16) INPUT

24 V DC

Name of Module Diagnostic LED

Indicator LEDs

1

9

2

10

3

11

4

12

5

13

6

14

7

15

8

16

Face mounted switches

Door

ON/OFF ON/OFF

48

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 53

Input 24V DC Module (16 switch) Specification Table

Characteristic

Input switch (16) module specifications

Function

Monitors on/off states from up to 16 face mounted switches

Part number

M.1016.9095 (old # 502-03651-00)

Field side connector

25-pin card edge connector, face plate, switches

Protection of logic circuits

Optical isolation between the logic and field sides

Indicator lights, input circuits

An LED indicates the logic state of each switch

Indicator light, module

The DIAG LED goes OFF when the module passes power-on diagnostic tests

Logic side power requirements (typical)

2 mA @ +5 V 11mA per energized input @ +5 V

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

49

Page 54

Input 24V DC Module (16 switch)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm.

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

50

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 55

Input 12V DC Module (32 points)

Input 12V DC Module (32 points) The input 12V DC module converts DC signals from 32 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 12 VDC, but can be any level between 10 and 14 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 32 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running.

INPUT 12V DC Module (32 PT)

INPUT

12 V DC

Name of Module Diagnostic LED

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

Giddings & Lewis

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

51

Page 56

Input 12V DC Module (32 points) Specification Table

Characteristic

Input 12V DC (32 pt) module specifications

Function

Monitors on/off states from up to 32 DC voltage inputs

Part number

M.1016.9085 (old #502-03643-00)

Field side connector

40-pin card edge connector, screw terminals

Input signals

Nominal 12V DC on, 0V DC off

Maximum allowed voltage

14V DC

Maximum current @ 14V DC

8.5 mA

Guaranteed on

10V DC

Minimum current @ 10V DC

5 mA

Guaranteed off

5V DC

Current allowed when off

2 mA

Time delay on

1 ms max.

Time delay off

1 ms max.

Protection of logic circuits

Optical isolation between the logic and field sides, 4000 V peak

Input groups

Four groups of 8 inputs UL 508 spacing

Indicator lights, input circuits

An LED indicates the logic state of each input

Indicator light, module

The DIAG LED goes OFF when the module passes power-on diagnostic tests

Logic side power requirements (typi- 29 mA @ +5V cal) 7 mA per energized input @ +5V Field side power dissipation, worst case

3.8 W

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

52

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 57

Input 12V DC Module (32 points)

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge(4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

53

Page 58

Input 120V AC Module (16 points)

Input 120V AC Module (16 points) The 120V AC input module converts AC signals from 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An “on” signal is nominally 120V AC, but can be any level between 79 and 132 volts. An “off” signal is any level below 20 A C. The wiring configurations may be sink or source. 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running.

INPUT 120V AC Module (16 PT)

INPUT

12 V DC

Name of Module Diagnostic LED

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

54

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 59

Input 120V AC Module (16 points) Specification Table

Characteristic

Input 120V AC (16 pt) Module Specifications

Function

Monitors on/off states from up to 16 AC voltage inputs

Part number

M.1016.8937 (old # 502-03550-02)

Field side connector

25-pin card edge connector, screw terminals

Input signals

Nominal 120V AC on, 0V AC off

UH Max (max. allowed voltage)

132V AC

IH Max (max. current @ 132V AC)

8.7 mA

UL Min

0V

Guaranteed on

79V AC

IH Min (min. current @ UH Min)

4.6 mA

Guaranteed off

20V AC

IT Min (current allowed when off)

1 mA

Frequency

50/60 Hz ± 5%

Time delay on, max.

14 ms

Time delay off, max.

20 ms

Protection of logic circuits

Optical isolation between the logic and field sides, 1780 VAC.

Arrangement of inputs

Four groups of 4 IEC Type 1 inputs per NEMA Standard, ICS 3-1983, Table 3-304-2. UL 508 spacing

Indicator lights, circuits

An LED indicates its logic state of each input

Indicator light, module

The DIAG LED goes off after the module passes its diagnostic tests at power-on.

Logic side power requirements (typical)

1 mA 11 mA per energized input

Field side power dissipation, worst case

18.4 W

Operating temperature range

7°C to 55°C (45°F to 131°F)

Storage temperature range

-40°C to 85°C (-40°F to 185°F)

Humidity

5 to 95%, non-condensing

Giddings & Lewis

@ +5V @ +5V

PiC900 Controls Motion Solutions Product Guide

55

Page 60

Input 120V AC Module (16 points) EMC Compliant Emissions

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

Noise immunity

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15 mm) 57-2000 Hz (acceleration 2 g)

Shock (per IEC 68-2-27)

Four shocks per axis (15g/11 msec)

56

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis