The text of a manual · part 5 of 15
PiC900 Controls Motion Solutions Product Guide, pages 41 to 50
Pages 41 to 50 of 150
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Giddings & Lewis 502-03550-02
Page 41
Serial Communications Module (2, 4 channel) Specification Table
Characteristics
Communications Module Specifications
Function
Provides 2 or 4 asynchronous serial communication channels to be used with serial interface devices
Part number
2 channel - M.1016.9143 (old # 502-03676-23) 4 channel - M.1016-9140 (old # 502-03676-03)
Dedicated processor
80C186, 8 MHz, 32K x 16 EPROM, 8K x 16 RAM
Ports 1, 2, 3, and 4
RS232 or RS422/485 electrical interface Supports RTS/CTS hardware handshaking Baud rates to 19.2 Kbps
Logic side power requirements (typical)
420 mA @ +5V 450 mA @ +5V 5 mA @ +15V 5 mA @ -15V
(2 ch) (4 ch)
50 mA per terminated RS422/485 channel @ +5V 5 mA per active RS232 channel @ +15V 6 mA per active RS232 channel @ -15V Operating temperature range
7° C to 55° C (45° F to 131° F)
Storage temperature range
-40° C to 85° C (-40° F to 185° F)
Humidity
5 to 95%, non-condensing
EMC Compliant Emissions Noise immunity
Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
37
Page 42
Serial Communications Module (2, 4 channel)
CE Marked
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204
UL and C/UL Listed
File No. E126417 NRAQ Programmable Controllers
Physical size
1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm
Vibration (per IEC 68-2-6)
10-57 Hz (constant amplitude .15mm) 57-2000 Hz (acceleration 2g)
Shock (per IEC 68-2-27)
38
Four shocks per axis (15g/11msec)
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 43
I/O Expansion
I/O Expansion Local I/O Expansion
Local I/O Expansion allows additional PiC900 or PiC90 racks of input/output modules to be connected to a PiC900 master rack within the same cabinet. The diagram below shows three expansion racks connected to a master rack.
Local I/O Expansion
CSM CPU
RSM
I/O Driver
IO
RSM
I O
I/O Driver
RSM I/O
I O
I O
NOTE: When a PiC900 rack is used for expansion, an RSM (or CSM) module is placed in slot 1 and the I/O driver module is placed in slot 2. When a PiC90 rack is used for expansion, the RSM I/O driver module is placed in slot 1/2. Expansion Modules
Expansion is accomplished with a PiC9XX CPU module with communication capabilities in the master rack and an I/O expansion driver for each additional rack. Up to seven expansion drivers with the PiC9XX can be linked to a master rack. Wiring
All cables are twisted pairs of wires. The maximum distance (from rack to rack) is 40 feet. Addressing
All addressing of modules is software defined - no address switches are required.
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
39
Page 44
I/O Expansion Remote I/O Expansion
Remote I/O Expansion allows for additional racks of input/output module in remote cabinets to be connected to the PiC900 master rack. The diagram below shows two expansion racks. NOTE: It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are in the same cabinet (local) as the master rack and use fiber optic cable to connect racks that are up to 2000 feet apart (remote). Expansion Modules
Communication with expansion is accomplished by using the following: CSM CPU
IO
RSM
I/O Driver
I O
RSM I/O
I O
• For the PiC900 Master Rack, a PiC9XX CPU module with communication capabilities. • For a PiC900 Expansion Rack, a RSM or CSM module in slot 1 and an I/O driver module in slot 2. • For a PiC90 Expansion Rack, an RSM I/O module in slot 1/2. Seven (with the PiC9XX) expansion drivers can be linked to a master rack. Wiring
All cables are fiber optic. The maximum distance (rack to rack) is 2000 feet. (The maximum loop distance is 4000 feet.) Circuitry
Expansion circuitry on the I/O driver modules provides for parallel to serial and serial to parallel conversions. Addressing
All addressing of modules is software defined - no address switches are required.
40
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 45
Block I/O Expansion
Block I/O Expansion Block I/O is a self-contained I/O interface with its own logic power supply derived from an external 24V DC source. Each block has a communication interface that includes two transmitters (RS485) and two receivers (optically isolated). Blocks differ as to the type of I/O interface (analog or digital) provided. Block I/O is an alternative to PiC900 rack I/O expansion. It is used to distribute small groups of interface logic close to the actual location of I/O devices. It allows you to replace long runs of I/O cables with twisted pairs of communication wires. The Block I/O footprint has been minimized for easy installation into small enclosures or junction boxes. NOTE: Block I/O cannot be intermixed within a rack I/O expansion loop. Block I/O uses a slower data rate and optical isolation to accommodate longer distances between modules. Block I/O can be used with MMCs, PiC900s and PiC90s. One possible layout for PiC expansion using block I/O modules is shown below. There can be up to 200 feet between block I/O modules. The recommended wire is Belden 9729, 24 AWG stranded conductors, twisted pair (100Ω characteristic impedance) with shield.
Block I/O Layout for PiC90/900 Expansion PiC900/90 Master Rack T R
Block I/O Modules T R
R
T
T
R
R
T
T
R
R
T
R
T
R
T
The distance between block I/O modules can be up to 200 feet.
T
R
T
R
T
R
T
R
R
T
R
T
R
T
R
T
Up to 77 modules T
R
R
T
NOTE: Unlike wiring for I/O expansion racks, it is not necessary to return the last block I/O module back to the PiC. The interconnecting cable between block I/O modules contains both a forward and a return communication path.
Giddings & Lewis
PiC900 Controls Motion Solutions Product Guide
41
Page 46
Block I/O Expansion Ordering Information
I/O expansion requires a PiC9XX CPU or a PiC904X CSM/CPU module with communication capabilities. Also required is an RSM (or CSM) module and an I/ O driver module installed in PiC900 expansion racks and an RSM I/O driver module installed in PiC90 expansion racks.
PiC94X master rack
Part number
Description
M.1016.9627 (old # 502-04111-11)
CPUs with
M.1016.9510 (old # 502-04011-11)
Communication Capabilities on Board
M.1016.9491 (old # 502-03994-11) M.1016.9629 (old # 502-04112-11) PiC904X master rack
M1016.9617 (old # 502-04104-11)
CSM/CPUs with
M.1016.9679 (old # 502-04125-11)
Communication Capabilities on Board
M.1016.9682 (old # 502-04126-10) PiC900 M.1016.9243 (old # 502-03732-03) expansion rack M.1016.9308 (old # 502-03817-03)
RSM-50W Module or RSM-60W Module or
M.1016.8879 (old # 502-03512-03) M.1016.9294 (old # 502-03813-03)
CSM-50W Module or CSM-60W Module and
M.1016.9105 (old # 502-03657-03)
I/O driver Module
PiC90 M.1016.9385 (old # 502-03876-02) expansion rack
RSM I/O driver Module
Remote I/O requires fiber optic cable: Length of Fiber Optic Cable for Above
Part Number
10’
M.1016.9210 (old # 502-03700-10)
25’
M.1016.9215 (old # 502-03700-25)
50’
M.1016.9217 (old # 502-03700-50)
75’
M.1016.9219 (old # 502- 03700-75)
100’
M.1016.9222 (old # 502-03701-00)
125’
M.1016.9225 (old # 502-03701-25)
150’
M.1016.9227 (old # 502-03701-50)
175’
M.1016.9228 (old # 502-03701-75)
*Refer to the I/O expansion section of the Product Guide to determine the number of fiber optic cables required for your application. 42
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis
Page 47
PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE
PiC 900 Discrete I/O Modules
Giddings & Lewis
Page 48
Page 49
Input 24V DC Module (32 or 16 points)
Input 24V DC Module (32 or 16 points) The 24V DC input module converts DC signals from 32 or 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 24 V DC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 32 or 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running.
Input 24V DC Module (32 and 16 Points)
INPUT
24 V DC
Name of Module Diagnostic LED
INPUT
24 V DC
Indicator LEDs
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
Giddings & Lewis
Screw terminal connector
Door
Name of Module Diagnostic LED
Indicator LEDs
1 3 5 7 9 11 13 15 17 19 21 23 25
Screw terminal connector
Door
PiC900 Controls Motion Solutions Product Guide
45
Page 50
Input 24V DC Module (32 or 16 points) Specification Table
Characteristic Function Part number
Input 24V DC module specifications Monitors on/off states from DC voltage inputs 32 point M.1016.9010 (old # 502-03605-00)) 16 point M.1016.8929 (old # 502-03548-00) Field side connector 32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals Input signals (exceed IEC standards) Nominal 24V DC on, 0V DC off UH Max (max. allowed voltage) 30V DC IH Max (max. current @ 30V DC) 7.5 mA UL Min Polarity independent Guaranteed on 14V DC IH Min (min. current @ UH Min) 2.8 mA Guaranteed off 5V DC IT Min (current allowed when off) .75 mA Time delay on 1 ms max. Time delay off 1 ms max. Protection of logic circuits Optical isolation between the logic and field sides, 4000V peak Input groups Four groups of 8 or 4 IEC Type 1 inputs per NEMA Standard, ICS 3-1983, Table 3-304-2. UL 508 spacing Indicator lights, input circuits An LED indicates the logic state of each input Indicator light, module The DIAG LED goes OFF when the module passes power-on diagnostic tests Logic side power requirements 32 point 29 mA @+5 V (typical) 7 mA per energized input @+5 V 16 point 2 mA @+5 V 7 mA per energized input @+5 V Field side power dissipation, worst 32 point 7.2 W case 16 point 3.6 W Operating temperature range 7°C to 55°C (45°F to 131°F) Storage temperature range -40°C to 85°C (-40°F to 185°F) Humidity 5 to 95%, non-condensing
46
PiC900 Controls Motion Solutions Product Guide
Giddings & Lewis