Page 41

Serial Communications Module (2, 4 channel) Specification Table

Characteristics

Communications Module Specifications

Function

Provides 2 or 4 asynchronous serial communication channels to be used with serial interface devices

Part number

2 channel - M.1016.9143 (old # 502-03676-23) 4 channel - M.1016-9140 (old # 502-03676-03)

Dedicated processor

80C186, 8 MHz, 32K x 16 EPROM, 8K x 16 RAM

Ports 1, 2, 3, and 4

RS232 or RS422/485 electrical interface Supports RTS/CTS hardware handshaking Baud rates to 19.2 Kbps

Logic side power requirements (typical)

420 mA @ +5V 450 mA @ +5V 5 mA @ +15V 5 mA @ -15V

(2 ch) (4 ch)

50 mA per terminated RS422/485 channel @ +5V 5 mA per active RS232 channel @ +15V 6 mA per active RS232 channel @ -15V Operating temperature range

7° C to 55° C (45° F to 131° F)

Storage temperature range

-40° C to 85° C (-40° F to 185° F)

Humidity

5 to 95%, non-condensing

EMC Compliant Emissions Noise immunity

Operates with emissions below EN55011/ CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per IEC 1000-4-2 • RF electromagnetic fields per IEC 1000-4-3 • Electrical fast transients per IEC 1000-4-4 on incoming power lines Refer to the EMC Guidelines for more information.

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

37

Page 42

Serial Communications Module (2, 4 channel)

CE Marked

Conforms to Directives 73/23/EEC, 89/336/EEC, 92/ 31/EEC, 93/68/EEC by conforming to the following standards: EN 50081-2:1993 EMC Generic Industrial Emissions EN 50082-2:1995 EMC Generic Industrial Immunity EN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllers Operates with emissions below EN5501/CISPR 11 Class A limits Immune to: • Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 • RF electromagnetic fields per EN61100-4-3, ENV50141, and ENV50204

UL and C/UL Listed

File No. E126417 NRAQ Programmable Controllers

Physical size

1.6" wide x 12" high x 8.4" deep (including latch) 41 mm x 305 mm x 213 mm

Vibration (per IEC 68-2-6)

10-57 Hz (constant amplitude .15mm) 57-2000 Hz (acceleration 2g)

Shock (per IEC 68-2-27)

38

Four shocks per axis (15g/11msec)

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 43

I/O Expansion

I/O Expansion Local I/O Expansion

Local I/O Expansion allows additional PiC900 or PiC90 racks of input/output modules to be connected to a PiC900 master rack within the same cabinet. The diagram below shows three expansion racks connected to a master rack.

Local I/O Expansion

CSM CPU

RSM

I/O Driver

IO

RSM

I O

I/O Driver

RSM I/O

I O

I O

NOTE: When a PiC900 rack is used for expansion, an RSM (or CSM) module is placed in slot 1 and the I/O driver module is placed in slot 2. When a PiC90 rack is used for expansion, the RSM I/O driver module is placed in slot 1/2. Expansion Modules

Expansion is accomplished with a PiC9XX CPU module with communication capabilities in the master rack and an I/O expansion driver for each additional rack. Up to seven expansion drivers with the PiC9XX can be linked to a master rack. Wiring

All cables are twisted pairs of wires. The maximum distance (from rack to rack) is 40 feet. Addressing

All addressing of modules is software defined - no address switches are required.

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

39

Page 44

I/O Expansion Remote I/O Expansion

Remote I/O Expansion allows for additional racks of input/output module in remote cabinets to be connected to the PiC900 master rack. The diagram below shows two expansion racks. NOTE: It is possible to combine local and remote expansion racks in the same system. Use twisted pair wiring to connect racks that are in the same cabinet (local) as the master rack and use fiber optic cable to connect racks that are up to 2000 feet apart (remote). Expansion Modules

Communication with expansion is accomplished by using the following: CSM CPU

IO

RSM

I/O Driver

I O

RSM I/O

I O

• For the PiC900 Master Rack, a PiC9XX CPU module with communication capabilities. • For a PiC900 Expansion Rack, a RSM or CSM module in slot 1 and an I/O driver module in slot 2. • For a PiC90 Expansion Rack, an RSM I/O module in slot 1/2. Seven (with the PiC9XX) expansion drivers can be linked to a master rack. Wiring

All cables are fiber optic. The maximum distance (rack to rack) is 2000 feet. (The maximum loop distance is 4000 feet.) Circuitry

Expansion circuitry on the I/O driver modules provides for parallel to serial and serial to parallel conversions. Addressing

All addressing of modules is software defined - no address switches are required.

40

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 45

Block I/O Expansion

Block I/O Expansion Block I/O is a self-contained I/O interface with its own logic power supply derived from an external 24V DC source. Each block has a communication interface that includes two transmitters (RS485) and two receivers (optically isolated). Blocks differ as to the type of I/O interface (analog or digital) provided. Block I/O is an alternative to PiC900 rack I/O expansion. It is used to distribute small groups of interface logic close to the actual location of I/O devices. It allows you to replace long runs of I/O cables with twisted pairs of communication wires. The Block I/O footprint has been minimized for easy installation into small enclosures or junction boxes. NOTE: Block I/O cannot be intermixed within a rack I/O expansion loop. Block I/O uses a slower data rate and optical isolation to accommodate longer distances between modules. Block I/O can be used with MMCs, PiC900s and PiC90s. One possible layout for PiC expansion using block I/O modules is shown below. There can be up to 200 feet between block I/O modules. The recommended wire is Belden 9729, 24 AWG stranded conductors, twisted pair (100Ω characteristic impedance) with shield.

Block I/O Layout for PiC90/900 Expansion PiC900/90 Master Rack T R

Block I/O Modules T R

R

T

T

R

R

T

T

R

R

T

R

T

R

T

The distance between block I/O modules can be up to 200 feet.

T

R

T

R

T

R

T

R

R

T

R

T

R

T

R

T

Up to 77 modules T

R

R

T

NOTE: Unlike wiring for I/O expansion racks, it is not necessary to return the last block I/O module back to the PiC. The interconnecting cable between block I/O modules contains both a forward and a return communication path.

Giddings & Lewis

PiC900 Controls Motion Solutions Product Guide

41

Page 46

Block I/O Expansion Ordering Information

I/O expansion requires a PiC9XX CPU or a PiC904X CSM/CPU module with communication capabilities. Also required is an RSM (or CSM) module and an I/ O driver module installed in PiC900 expansion racks and an RSM I/O driver module installed in PiC90 expansion racks.

PiC94X master rack

Part number

Description

M.1016.9627 (old # 502-04111-11)

CPUs with

M.1016.9510 (old # 502-04011-11)

Communication Capabilities on Board

M.1016.9491 (old # 502-03994-11) M.1016.9629 (old # 502-04112-11) PiC904X master rack

M1016.9617 (old # 502-04104-11)

CSM/CPUs with

M.1016.9679 (old # 502-04125-11)

Communication Capabilities on Board

M.1016.9682 (old # 502-04126-10) PiC900 M.1016.9243 (old # 502-03732-03) expansion rack M.1016.9308 (old # 502-03817-03)

RSM-50W Module or RSM-60W Module or

M.1016.8879 (old # 502-03512-03) M.1016.9294 (old # 502-03813-03)

CSM-50W Module or CSM-60W Module and

M.1016.9105 (old # 502-03657-03)

I/O driver Module

PiC90 M.1016.9385 (old # 502-03876-02) expansion rack

RSM I/O driver Module

Remote I/O requires fiber optic cable: Length of Fiber Optic Cable for Above

Part Number

10’

M.1016.9210 (old # 502-03700-10)

25’

M.1016.9215 (old # 502-03700-25)

50’

M.1016.9217 (old # 502-03700-50)

75’

M.1016.9219 (old # 502- 03700-75)

100’

M.1016.9222 (old # 502-03701-00)

125’

M.1016.9225 (old # 502-03701-25)

150’

M.1016.9227 (old # 502-03701-50)

175’

M.1016.9228 (old # 502-03701-75)

*Refer to the I/O expansion section of the Product Guide to determine the number of fiber optic cables required for your application. 42

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis

Page 47

PiC900 CONTROLS MOTION SOLUTIONS PRODUCT GUIDE

PiC 900 Discrete I/O Modules

Giddings & Lewis

Page 48

This page is a scan with no text; see it in the PDF.

Page 49

Input 24V DC Module (32 or 16 points)

Input 24V DC Module (32 or 16 points) The 24V DC input module converts DC signals from 32 or 16 devices into logic levels that the CPU can use. Each signal is converted into a corresponding logic 1 or 0 which is transmitted through the system bus to the CPU module. An "on" signal is nominally 24 V DC, but can be any level between 14 and 30 volts. An "off" signal is any level below 5V. The wiring configurations may be sink or source. 32 or 16 LEDs in the upper section of the module indicate the logic state of each input. The DIAG LED goes on briefly while the diagnostics tests are running.

Input 24V DC Module (32 and 16 Points)

INPUT

24 V DC

Name of Module Diagnostic LED

INPUT

24 V DC

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

Giddings & Lewis

Screw terminal connector

Door

Name of Module Diagnostic LED

Indicator LEDs

1 3 5 7 9 11 13 15 17 19 21 23 25

Screw terminal connector

Door

PiC900 Controls Motion Solutions Product Guide

45

Page 50

Input 24V DC Module (32 or 16 points) Specification Table

Characteristic Function Part number

Input 24V DC module specifications Monitors on/off states from DC voltage inputs 32 point M.1016.9010 (old # 502-03605-00)) 16 point M.1016.8929 (old # 502-03548-00) Field side connector 32 point 40-pin card edge connector, screw terminals 16 point 25-pin card edge connector, screw terminals Input signals (exceed IEC standards) Nominal 24V DC on, 0V DC off UH Max (max. allowed voltage) 30V DC IH Max (max. current @ 30V DC) 7.5 mA UL Min Polarity independent Guaranteed on 14V DC IH Min (min. current @ UH Min) 2.8 mA Guaranteed off 5V DC IT Min (current allowed when off) .75 mA Time delay on 1 ms max. Time delay off 1 ms max. Protection of logic circuits Optical isolation between the logic and field sides, 4000V peak Input groups Four groups of 8 or 4 IEC Type 1 inputs per NEMA Standard, ICS 3-1983, Table 3-304-2. UL 508 spacing Indicator lights, input circuits An LED indicates the logic state of each input Indicator light, module The DIAG LED goes OFF when the module passes power-on diagnostic tests Logic side power requirements 32 point 29 mA @+5 V (typical) 7 mA per energized input @+5 V 16 point 2 mA @+5 V 7 mA per energized input @+5 V Field side power dissipation, worst 32 point 7.2 W case 16 point 3.6 W Operating temperature range 7°C to 55°C (45°F to 131°F) Storage temperature range -40°C to 85°C (-40°F to 185°F) Humidity 5 to 95%, non-condensing

46

PiC900 Controls Motion Solutions Product Guide

Giddings & Lewis