Page 1

PI-J375-001

Rev I3

J375 Modbus Adapter DATA SHEET ’

The J375 Modbus”0 adapter is a communications interface for the Micro 84’m controller. FEATURES l Connects Micro 84 (slave) to Modbus communications system. l l

’

Addressing for 247 slaves on one system Mounting and packaging similar to Micro 84 l/O modules

.

No modifications required to Micro 84

.

One RS-232-C port

.

Compatible with Modicon J378 modem plus many commercial modems

.

Permits simultaneous P370 programming and Modbus communications

.

Comprehensive diagnostic capability and extensive error checking

.

Switch selectable address and system parameters

0

Supports mixed Modicon PC network

GENERAL

I .

DESCRIPTION

The J375 Modbus Adapter is a communications interface module for the Micro 84 controller. As such, it interfaces the Micro 84 to a Modbus industrial communication system. It allows the Micro 84 to be a slave PC to a Modbus master. The adapter is packaged in a modified Micro 84 l/O module case. This case is made of Lexan molded plastic with mounting brackets located on the rear of the case. This makes the J375 lightweight and easy to install. The J375 provides port connections for the following: A P370 Micro 84 Programmer, an RS-232-C device and a Micro 84 controller.

d b

In addition, the adapter is equipped with factory selectable options for 1151220 VAC power. The J375 contains its own power supply that generates all operating voltages for the adapter’s internal processor. The J375 does not require power from the Micro 84 or the data bus. The adapter provides three LED indicators.

“Run”, “Comm Active”, and “Error”. These indicators display both operating status and trouble indications. You can use these indicators for fast troubleshooting. The J375 provides dip switches at the rear of its case for address and system parameter selection. The Modbus adapter supports function codes l-8 and 15-19. In addition, the J375 allows simultaneous use of both the Modbus port and P370 port. In the event of a conflict, the adapter gives the Modbus port the higher priority, and the P370 port monitors operations only. The J375 assures maximum system integrity through parity and message redundancy checks, exception responses, loopback diagnostics and automatic retries. The J375 Modbus Adapter is compatible with all current Modbus products, which allows a mix of Gould PC’s on a Modbus network.

-!!

GOULD Electronics

Page 2

COMMUNICATION

Showing

Placement

MEDIA

Typical Modbus Network of J375 Modbus Adapter

Pl70

Within

Network

Two Possible

Mounting

Configurations

SPECIFICATIONS EIA RS-232-C Signals Supported 1. Transmitted Data (TXD). an output from the J375 2. Received Data (RXD), an input to the J375 3. Request to Send (RTS), an output from the J375 4. Clear to Send (CTS), an input to the J375 5. Data Set Ready (DSR), an input to the J375 6. Data Terminal Ready (DTR), an output from the J375

Functions

Set Single Register x

Read Exception Status

X

0

Loopback

X

1

Initiate Comm Restart

X

2

Return Diagnostic Register

X

4

Force Listen Only Mode

X

10

19,200

Transmission Parity Option mode, stop bits, and parity supported Even Parity

,L

Odd Parity \

No. of Stop Bits

1

2

1

2

1

2

ASCII

X

X

X

X

NS

X

RTU

X

NS

X

NS

X

NS

Sub. Functions

Description

Supported

Read Output Status

X

Read Input Status

X

Read Output Register Read Input Register

X X

Force Single Coil

X

Environment Ambient Temperature Operating

Not Supported

Fetch Event Counter

X X

13

Program (18413641564 PC’s)

X

14

Poll (18413641584 PC’S)

X

15

Force Multiple Coils

X

16

Set MultiDIe Registers

X

I?

Report Slave ID

X

18

Program Commands (Micro 64 PC) (Gould Modicon (Proprietary Command)

X

19’

Reset Link Command

X

F ‘ unction Code 19 is a new function code. This code, via the Modbus master software, changes the values of the system parameters set by the dip switches.

O’C to 60°C - 40°C to + 85OC

Hum.idity

O-95% (non-condensing)

X

Fetch Communications Event Log

Dimensions (W x H x D)

Storage

X

11

J

X = Supported NS = Not Supported

Program (484 PC only) Poll (484 PC only)

12 by J375

No Parity

Not Suppofled Supported

6

9

9,600

300 600

Descrlstlon

7

4,800 l!iD .-_

Function Codes

Sub-

Codes

8

Modbus Compatibility Baud Rate supported by J375 75 1,200 110 2.4or-I _, .__ 134.5

Function

Weight

1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm) 2 Ibs, 2.5 oz (0.978 kg)

NOTES 1. Install as the last module in the l/O structure, if J378 modem not used.

2. Install anywhere wlthin the range of the Micro 84 cable (cable is 6 ft. long and interchangeable with P370 cable).

iii

GOULD Electronics

Page 3

PI-J3/8-Uul nev u

J378 Modem DATA SHEET Y

The J378 Modem allows shielded cable network.

a J375 Modbus @ Adapter

FEATURES Allows short-haul data transfer plant Micro 84’” controller Allows transmission twisted pair cable to be used with a 4-wire, twisted pair, fully for in- over a 4-wire,

Designed for harsh industrial environment Low cost Easy to install Operates asynchronously to 19,200 bps at speeds up

Uses frequency shift keying (FSK) to maximize noise immunity Tolerates dB a maximum

Operates mode in half-duplex signal loss of 35 transmission

Does not require an additional power supply Monitors LEDs certain

EIA control

Mounting and packaging Micro 84 l/O modules Compatible

GENERAL signals similar via to with Gould J478 Modem

DESCRIPTION

The J378 Modem allows a J375 Modbus Adapter to be used with a 4-wire, twisted pair cable network, when the cable is used in a multipoint environment. It attaches to the right side of the J375 and receives both power and W-232-C signals from the adapter. It connects to the 4-wire, twisted pair cable by way of a terminal strip on the front of the modem.

i

The J378 uses FSK modulation that is compatible with the J478 Stand-alone Modem. The J378 meets or exceeds the specifications for the J478 Modem, except for voice communications. The J378 does not have voice communication capability.

The J378 attaches to the right side of the J375 Modbus Adapter through the RS-232-C port on the adapter. Attaching the modem to the adapter dedicates for use by the modem.

the RS-232-C port

The J378 interfaces with the Modbus twisted-pair cable network through four terminals on the front of the modem. You simply connect the twisted-pairs directly to the terminals on the front of the unit. The terminals are clearly marked as to which is receive and which is transmit. The J378 supports the Modbus 4-wire, twisted pair cable network only. The J378 uses four LED indicator display operating status. XMIT D RCV D CD RTS lights to

(Transmit Data to cable) (Receive Data from cable) (Carrier Detect from cable) (Request to Send from J375 Adapter) 1

=!!!!!!GOULD Nectronics

Page 4

SLAVE PROGRAYYISLE CONTROLLER WITH MODEM m J375

J37S

7 ‘ t,:‘!::?:::

P3ro

Showing

Typical Modbus Network Placement of J378 Modem Within Network

*ADAPTER CAN BE MOUNTED EITHER ABOVE OR BELOW THE COHTROLLER AS A STAND-ALONE DEVICE

Two Possible

Mounting

Configurations

SPECIFICATIONS Electrical

Characteristics

Mark Frequency

50 kHz

Space

80 kHz

Frequency

Maximum

Data Rate

Form of Modulation

15,000 ft*

Transmission

Four conductor, fully shielded twisted-pair cable (i.e., Belden 8777)

Media

20 kHz Frequency Keying

Allowable Signal Attenuation

35 dB

Max. No. of Drops

32*

Shift

Environment Ambient Temperature Operating Storage Humidity

Max. Cable Length

Type of Transmission

Asynchronous

*Main cable, drop lengths, and number of slaves are all inter-related parameters. For instance, the 15,000 ft. maximum length can be increased if less than 32 slaves are used. Dimensions

0’ to 60°C -5OOto +85OC 0 to 95% (noncondensing)

(W x H x D) 1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm)

Weight 1 lb, 5.5 oz (0.610 kg)

NOTES 1. Install as the last module in the l/O structure. 2. Install anywhere within the range of the Micro 84 cable (cable is 6 ft. long and interchangeable with P370 cable).

-i

GOULD Electronics

Page 5

PI-M84A-002

Rev A

Micro 84/Pl90 Programmer/Tape Loader DATA SHEET ,

The Gould Modicon Programmer/Tape Controller

Loader cartridge permits programming of the Micro 84 Programmable by the P190 CRT Programmer.

FEATURES searching. Network

Programmer and Tape Loader Functions

Editing offers the additional capability of deleting, replacing, exchanging, compressing, and expanding networks.

Element Editing Network

Editing

Four Tape Loader functions

4 x 7 Ladder Logic Display Element Status Display

1. 2.

Partial and Full Reference Screens Network

Create, Replace, Exchange and Delete

Program Documentation

7j

Record the Micro 84 memory onto the P190

3.

Compare the Micro 84 memory with the P190 tape.

4.

Write the Micro 84 memory onto the program track.

GENERAL DESCRIPTION

The Load function allows the user to construct new programs by loading and later editing selected

The Gould Modicon Programmer/Tape Loader cartridge, used in conjunction with the Micro 84 Programmable Controller, the J375 Modbus Adapter, and the P190 full-family CRT Program-networks from a previously prepared program. Record enables the user to preserve a copy of the program on a P 190 tape for later use. A program may also be recorded on a Micro 84 program pack by Writing the program pack function.

mer, provides programming functions for program preparation, editing, documentation, debug, and system maintenance.

With Programmer/Tape

Loader, the user can perform local programming functions on the plant floor or expand the Micro 84 controller’s versatility by performing remote programming and tape loading operations. In addition, it provides control for starting and stopping the Micro 84 controller, reporting its configuration, and writing the program pack. There are two programming options: Element Editing and Network Editing. Element Editing permits the user to make entries and/or changes directly into the Micro 84 controller’s memory. Network Editing permits the user to make changes in the PI90 programmer’s memory before making changes in the Anicro 84 controller’s memory. With Network Editing, the user can experiment with network changes while preserving existing logic. Both editors can read existing networks, create new networks, edit networks, disable and force elements, report full or partial reference tables, j

Load from the P190 tape to the Micro 84.

tape.

Logic Expand and Compress Program Load, Record and Compare allow the user to:

report coil usage tables, and perform element

Compare is used to verify that the Micro 84 controller’s memory contains the same program as that on a P190 tape. Comparison may be performed on all memory, selected networks, or selected registers. The user may also select a log-and-pause or continuous-log mode for reporting miscompares.

The Programmer/Tape Loader cartridge plugs directly into the PI90 tape transport. Local use requires a Gould Modicon J375 Modbus Interface. Remote use requires a J375 plus Gould Modicon J378 and J478 modems (or commercial equivalents). A P190 cable (either AS-W806-OXX or AS-W364-OXX) provides the communications link between the PI90 and J375. When using a J375, the user must set port parameters and address selection on both the J375 and P190 programmer. A hard copy printout of the P190 programmer’s CRT screen is obtained by connecting an RS-232-C compatible printer to the PI 90 programmer’s second communications port.

I)

GOULD

Page 6

LOCAL

PROGRAMMING

MA-liO5-000 CABLE

SPECIFICATIONS Operations Start PC stop PC Program Tape Loader Attach Detach Clear PC. (logic and/or references) PC Configuration

Network Editor (only) Create Network Delete Network Dummy References or Presets Replace Network Flip Network Exchange Network Expand/Compress Network

Element and Network Editor Read Network Edit Network Force On/Off Enable/Disable Hold/Release Reference Display Coils Used Full Reference Display Partial Reference Display Search Display Search List Print (any PI90 display)

Tape Loader Load Record Compare Program Pack

Compare PC All Memory Selected Networks Selected Registers Error Halt Mode Error Log Mode Maximum Miscompare Count

Media 3 “son” ready-to-use cartridge tapes (nonreproducible) Scotch DClOOA or equivalent.

Load PC All Memory Selected Networks Selected Registers Record PC Set Title Set Date Set Serial Number

-i

GOULD Electronics