Manual · Gould
J375 Modbus Adapter Data Sheet
Manual6 pagesPDF 643 KB
Data sheet for the Gould Modicon J375 Modbus adapter, the communications interface that connects a Micro 84 controller to Modbus.
Covers · 4 models
The models it covers
Summary
What is in it
Gould's data sheet for the J375 Modbus Adapter, a communications interface module that connects the Micro 84 controller as a slave to a Modbus network. It describes the features, the case and mounting, the ports for the P370 programmer, an RS-232-C device and the Micro 84, the built-in power supply, LED indicators and DIP switches, the supported Modbus function codes, a typical network, the RS-232-C signals, transmission modes and parity, and the environmental and other specifications.
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Gould Modicon data sheets for the J375 Modbus Adapter, followed by the sheets for the J378 Modem and the Micro 84/P190 Programmer/Tape Loader cartridge. The J375 connects a Micro 84 controller to a Modbus network as a slave. The sheets give its ports, function codes, specifications and mounting notes, and show how the modem and the P190 programmer work with it.
- Device
- Modbus communications interface module that makes a Micro 84 controller a slave to a Modbus master p. 1
- Ports
- P370 Micro 84 Programmer, one RS-232-C device and the Micro 84 controller p. 1
- Addressing
- Up to 247 slaves on one system; address and system parameters set by dip switches at the rear p. 1
- Power
- Own built-in power supply with factory-selectable AC options; draws no power from the Micro 84 or the data bus p. 1
- Indicators
- Three LEDs: Run, Comm Active and Error p. 1
- Function codes
- Modbus function codes 1-8 and 15-19 p. 1
- RS-232-C signals
- TXD, RXD, RTS, CTS, DSR and DTR p. 2
- Baud rates
- 75 to 19,200 p. 2
- Dimensions (W x H x D)
- 1.63 x 10.50 x 5.50 in (41.40 x 266.70 x 139.70 mm) p. 2
- Weight
- 2 lb 2.5 oz (0.978 kg) p. 2
- Compatible modems
- Modicon J378 modem plus many commercial modems p. 1
- Micro 84 cable
- 6 ft long, interchangeable with the P370 cable p. 2
- J378 modem
- Attaches to the J375's right side; 4-wire twisted pair link using FSK, up to 19,200 bps p. 3
- J378 cable
- Four conductor, fully shielded twisted pair (Belden 8777); up to 32 drops p. 4
What this manual walks you through
- Connecting a Micro 84 to a Modbus network as a slave p. 1
- Setting the address and system parameters with the dip switches p. 1
- Changing the dip switch parameters from the Modbus master with function code 19 p. 2
- Adding a J378 modem for a 4-wire twisted pair network p. 3
- Programming a Micro 84 from a P190 programmer through the J375 p. 5
- Loading, recording and comparing Micro 84 programs on P190 tape p. 5
Good to know
- When the Modbus port and the P370 port conflict, Modbus has priority and the P370 port only monitors. p. 1
- Without a J378 modem, the J375 is installed as the last module in the I/O structure. p. 2
- Attaching the J378 modem dedicates the adapter's RS-232-C port to the modem. p. 3
- The J378 modem has no voice communication capability. p. 3
- The J378 network's 15,000 ft maximum length can be increased when fewer than 32 slaves are used. p. 4
Questions this manual answers
What does the Gould J375 do?
It is a communications interface module that connects a Micro 84 controller to a Modbus network as a slave to a Modbus master. p. 1
How many slaves can a J375 Modbus system address?
Up to 247 slaves on one system, with the address set by dip switches at the rear of the case. p. 1
Does the J375 take power from the Micro 84?
No. It has its own power supply and needs no power from the Micro 84 or the data bus. p. 1
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file