The text of a manual · part 1 of 3
Range-free Controller FA-M3R Migration Guide for Obsoleted Models, pages 1 to 10
Pages 1 to 10 of 29
The original document is the PDF (441 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Yokogawa F3RZ81 and Hirata F3RZ81
Page 1
Technical Information
Range-free Controller FA-M3R Migration Guide for Obsoleted Models
TI 34M06Z41-01E 2011.03
4th Edition
Page 2
Overview (1) FA Link (H) Module [ F3LP01-0N→F3LP02-0N ] Upward compatible
FL-net Interface Module [F3LX01-0N→F3LX02-1N] FL-net (OPCN-2) Ver.1.0 is replaced with FL-net (OPCN-2) Ver.2.00. Programming-wise upward compatible Communication protocols differ so requires replacement of all connected devices.
Ladder Communication Module [F3RZ81-0N→F3RZ81-0F] Functionally compatible but requires program modification.
Ladder Communication Module [F3RZ91-0N→F3RZ91-0F] Functionally compatible but requires program modification.
1
TI 34M06Z41-01E
Overview (2) Positioning Module [F3YP04/08-0N→F3YP14/18-0N] Upward compatible but requires program modification because of different relay/register configurations. Positioning Module [F3NC95-0N→F3NC96-0N] MECHATROLINK communication interface is replaced with MECHATROLINK-Ⅱ communication interface. Upward compatible but requires replacement of connectors and cables.
Ethernet Interface Module [F3LE01-5T→F3LE01-0T] 100% application compatible but with no AUI interface.
TI 34M06Z41-01E
2
Page 3
Overview (3) NX Interface Module [F3NX01-0N→F3NX01-1N] Application compatible but no 10BASE5 (AUI port) support.
Personal Computer Link Module [F3LC11-N→F3LC11-F] Upward compatible but differs in transmission rate setup, I/O relay numbers and transmission data area for event transmission, as well as current consumption. Programming Tool Cable [KM13-1N→KM13-1S] Only the driver software for USB connection has been changed. No change in cable appearance, specifications and other aspects.
3
TI 34M06Z41-01E
FA Link (H) Module F3LP01-0N→F3LP02-0N (1) Comparison of Specifications Upward compatible Item Number of connected stations Link relays
Link registers Maximum link points per station Link relay/register assignments Number of attached modules Transmission rate Topology Terminating resistors
F3LP01-0N 32 stations per system Up to 1024 points per module F3SP08/21: 2048 F3SP28/53: 8192 F3SP38/58/59: 16384 Up to 1024 points per module F3SP08/21: 2048 F3SP28/53: 8192 F3SP38/58/59: 16384 Same as above Link relays: on 16-point basis Link registers: on 1-point basis F3SP08/21: 2 max F3SP28/38/53/58/59: 8 max
F3LP02-0N 32 stations per system Up to 2048 points per module F3SP08/21: 2048 F3SP28/53: 8192 F3SP38/58/59: 16384 Up to 2048 points per module F3SP08/21: 2048 F3SP28/53: 8192 F3SP38/58/59: 16384 Same as above Link relays: on 16-point basis Link registers: on 1-point basis F3SP08/21: 2 max F3SP28/38/53/58/59: 8 max
250kbps Single bus 110 Ω internal resistor on each end (selectable by hardware switch)
125k/250k/625k/1.25Mbps (by switch setup) Single bus 110 Ω internal resistor on each end (selectable by hardware switch) 1km/500m/200m/100m (depending on transmission rate Token bus Frame synchronization HDLC compliant NRZI mode CRC-CCITT, timeout detection - Local loop-back function - Hardware self-diagnosis - Error detection by special relays and registers Shielded twist-pair cable (AWG20)
Transmission distance
500 m max.
Communication mode Synchronization mode Transmission format Symbolization mode Error control
Token bus Frame synchronization HDLC compliant NRZI mode CRC-CCITT - Local loop-back function - Hardware self-diagnosis - Error detection by special relays and registers Shielded twist-pair cable (AWG20)
RAS function Transmission media
TI 34M06Z41-01E
4
Page 4
FA Link (H) Module F3LP01-0N→F3LP02-0N (2) Programming precautions Upward compatible
When connecting F3LP02-0N and F3LP01-0N: Set the baud rate of F3LP02-0N to 250kbps using hardware switch. Calculate the response time using formulae for F3LP01-0N.
5
TI 34M06Z41-01E
FL-net Interface Module F3LX01-0N→F3LX02-1N (1) Comparison of Specifications Upward compatible Item Number of connected nodes Cyclic transmission
F3LX01-0N
F3LX02-1N
254 max.
254 max.
512 words in area 1
512 words in area 1
8192 words in area 2
8192 words in area 2
Message transmission
1024 bytes max.
1024 bytes max.
Number of installed modules
2 max. (modules cannot be installed in a sub-unit)
2 max. (modules cannot be installed in a sub-unit)
Transmission rate
10Mbps
10Mbps
Topology
Bus
Bus
Transmission distance
500m max. (2.5 km when using repeaters)
500m max. (2.5 km when using repeaters)
Transmission media
Compliant to IEEE802.3
Compliant to IEEE802.3
External power supply
12V DC (when power is supplied via AUI port)
12V DC (when power is supplied via AUI port)
Fuse
2A time lag fuse (not replaceable as it is embedded 2A time lag fuse (not replaceable as it is embedded in in the power supply terminal) the power supply terminal)
Current consumption
580 mA max.
460 mA max.
28.9 (W) x 100 (H) x 83.2 (D) mm
28.9 (W) x 100 (H) x 83.2 (D) mm
(excluding protrusions)
(excluding protrusions)
160 g
130 g
External dimensions Weight
TI 34M06Z41-01E
6
Page 5
FL-net Interface Module F3LX01-0N→F3LX02-1N (2) Programming Precautions Upward compatible
Connected hardware devices All devices connected on the same network must be FL-net(OPCN-2)Ver.2.00 compatible devices. (Intermixing 2)Ver.1.00 and Ver 2.00 compatible devices is not allowed)
replaced with FL-net(OPCN-
Setup Precautions When using a hub employing auto-negotiation, set element 4 of the Condition
Setup switch (4-pole DIP switch) located on the side of the F3LX02-1N module inside the module cover to ON to select the 10BASE-T communication port.
7
TI 34M06Z41-01E
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (1) Comparison of Specifications
0 to 32760 ms in 1 ms increments, accurate to 1 ms (0 means not monitored)
0 to 32760 ms in 1 ms increments, accurate to 1 ms (0 means not monitored)
0 to 32760 ms in 1 ms increments, accurate to 1 ms (0 means not monitored) No Yes 15 m max. 1 (not isolated) 100 mA 120 g
0 to 32760 ms in 1 ms increments, accurate to 1 ms (0 means not monitored) 1 to 32760 ms in 1 ms increments,accurate to 1 ms No 15 m max. 1 (not isolated) 320 mA 120 g
F3RZ81-0N Point to point Full-duplex/half-duplex Start-stop synchronization No protocol 7 or 8 bits 1, 1.5 or 2 bits None, even or odd
Transmission rate
75, 150, 300, 600, 1200, 2400, 4800, 9600, 19200 bps RS control DR check
Control lines CD check ER control Communication buffers
Send buffer Receive buffer Start character
Format of received text
End character (terminator) Text length Character-tocharacter timeout interval
Clear-to-send timeout interval Break transmission interval Xon/Xoff controll Transmission distance Number of ports Current consumption Weight
TI 34M06Z41-01E
1: Always on. 2: Turn on before sending. 1: Ignore DR when sending. 2: Send only when DR is on. 1: Ignore CD when sending. 2: Send only when CD is off. 1: On (ready) 2: Off (not ready) Text buffer (598 bytes max.) 2048-byte rotary buffer - Yes or No - Any single character - Yes or No - Up to 2 characters long, any characters Can be specified as any number between 1 and 596
F3RZ81-0F Point to point Full-duplex/half-duplex Start-stop synchronization No protocol 7 or 8 bits 1 or 2 bits None, even or odd 300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 76800, or 115200 bps 1: Always on. 2: Turn on before sending. 1: Ignore DR when sending. 2: Send only when DR is on. 1: Ignore CD when sending. 2: Send only when CD is off. 1: On (ready) 2: Off (not ready) Text buffer (3584 bytes max.) 8192-byte rotary buffer - Yes or No - Any single character - Yes or No - Up to 2 characters long, any characters Can be specified as any number between 1 and 3584
Item Connection method Transmission mode Synchronization Communication protocol Character length Data format Stop bit length Parity bit
8
Page 6
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (2) Functional Differences Removal of Commands In F3RZ81-0N, a command register and a setup relay is used for communication setup and buffer initialization; In F3RZ81-0F, separate relays are provided for individual functions so no command register setup is required. F3RZ81-0F does not provide a port reset function.
Reading Communication Settings In F3RZ81-0N, the current communication settings are always reflected in the register area; In
F3RZ81-0F, the current settings are reflected in the status area only when a user turns on the Read Communication Mode Status output relay.
Xon/Xoff Control Xon/Xoff control is not available in F3RZ81-0F.
Break Signal F3RZ81-0F supports sending and receiving of the Break signal.
9
TI 34M06Z41-01E
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (3)
Error Handling In F3RZ81-0N, a program detects an error by reading the Response Status register after confirming that the “End-of-xx” relay has turned on. In F3RZ81-0F, separate error relays are provided.
Sending In F3RZ81-0N, a program sets the data size and the transmission data in the output registers and turns on the Start-of-Sending relay. The module then sends the specified number of bytes, starting from the byte following the data size. In F3RZ81-0F, a program writes the data size to the Send Data Byte Count register, stores the transmission data to the Send Data Area and turns on the Request to Send relay. The module then sends the specified number of bytes, starting from the first byte of the Send Data Area. F3RZ81-0N
F3RZ81-0F 1
Send Data Area Size
Output registers
Transmission data
301
385
Transmission data
Send Data Byte Count register
Size
1793
601
TI 34M06Z41-01E
10
Page 7
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (4)
Receiving In F3RZ81-0N, the receive status and the size of received data are stored in the Receive Area. In
F3RZ81-0F only the received data is stored in the receive area while the status and data size are stored in separate dedicated registers.
F3RZ81-0N
Input registers
F3RZ81-0F
Status
1
Size
2 385
Received data Received data Receive Data Area 301
897 Receive Data Status
Status
1795
Receive Data Byte Count
Size
1796
11
TI 34M06Z41-01E
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (5) Input Relays F3RZ81-0F has additional input relays, namely, Read Communications Mode
Status Completed relay, Initialize Receive Buffer Completed relay, Send Break Completed relay, Receive Error relay, Send Error relay and Set Communications Mode Error relay. Input Relays of F3RZ81-0F
Input Relays of F3RZ81-0N X□□□01
End-of-Receiving
X□□□01
Receive Completed
X□□□02
End-of-Sending
X□□□02
Send Completed
X□□□03
End-of-Setting
X□□□03
Set Communications Mode Completed
X□□□04 to X□□□32
Reserved
X□□□04
Read Communications Mode Status Completed
TI 34M06Z41-01E
X□□□05
Initialize Receive Buffer Completed
X□□□06
Send Break Completed
X□□□07
Receive Error
X□□□08
Send Error
X□□□09
Set Communications Mode Error
X□□□10 to X□□□32
Reserved
12
Page 8
Ladder Communication Module F3RZ81-0N→F3RZ81-0F (6) Output Relays F3RZ81-0F has additional output relays, namely, Request to Read Communications Mode Status relay, Request to Initialize Receive Buffer relay and Request to Send Break relay. Output Relays of F3RZ81-0F
Output Relays of F3RZ81-0N Y□□□33
End-of-Reading
Y□□□34
Start-of-Sending
Y□□□35
Start-of-Setting
Y□□□36 to Y□□□64
Read Received Data Completed
Y□□□33
Reserved
Programming Precautions
Y□□□34
Request to Send
Y□□□35
Request to Set Communications Mode
Y□□□36
Request to Read Communications Mode Status
Y□□□37
Request to Initialize Receive Buffer
Y□□□38
Request to Send Break
Y□□□39 to Y□□□64
Reserved
See sample program at the end of the presentation. 13
TI 34M06Z41-01E
Ladder Communication Module F3RZ91-0N→F3RZ91-0F (1) Comparison of Specifications Item Connection method
F3RZ91-0N
F3RZ91-0F
Point to point
Point to point
Transmission mode
Full-duplex/half-duplex
Full-duplex/half-duplex
Synchronization
Start-stop synchronization
Start-stop synchronization
Communication protocol
No protocol
No protocol
Character length
7 or 8 bits
7 or 8 bits
Stop bit length
1, 1.5 or 2 bits
1 or 2 bits
Parity bit
None, even, or odd
None, even, or odd
75, 150, 300, 600, 1200, 2400, 4800, 9600, 19200 bps
300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 76800, or 115200 bps
Shielded twisted pair cable (AWG20-16)
Shielded twisted pair cable (AWG20-16)
Data format
Transmission rate Transmission media Send buffer
Text buffer (598 bytes max.)
Text buffer (1792 bytes max.)
Receive buffer
2048-byte rotary buffer
8192-byte rotary buffer
Start character
- Yes or no - Any single character
- Yes or no - Any single character
End character (terminator)
- Yes or no - Up to 2 characters long, any characters
- Yes or no - Up to 2 characters long, any characters
Text length
1 to 596 characters
1 to 1792 characters
Character-to-character timeout interval
Yes or no
Yes or no
Break signal transmission
No
Yes
Xon/Xoff control
Yes
No
Transmission distance
1200 max.
1200 max.
Communication buffers
Format of received text
Number of ports
1 (isolated)
1 (isolated)
Current consumption
210 mA
350 mA
Weight
140 g
120 g
TI 34M06Z41-01E
14
Page 9
Ladder Communication Module F3RZ91-0N→F3RZ91-0F (2) Functional Differences Removal of Commands In F3RZ91-0N, a command register and a setup relay is used for communication setup and buffer initialization; In F3RZ91-0F, separate relays are provided for individual functions so no command register setup is required. F3RZ91-0F does not provide a port reset function.
Reading Communication Settings In F3RZ91-0N, the current communication settings are always reflected in the register area; In
F3RZ91-0F, the current settings are reflected in the status area only when a user turns on the Read Communication Mode Status output relay.
Xon/Xoff Control Xon/Xoff control is not available in F3RZ91-0F.
Break Signal F3RZ91-0F supports sending and receiving of the Break signal.
15
TI 34M06Z41-01E
Ladder Communication Module F3RZ91-0N→F3RZ91-0F (3)
Error Handling In F3RZ91-0N, a program detects an error by reading the Response Status register after confirming that the “End-of-xx” relay has turned on. In F3RZ91-0F, individual error relays are provided.
Sending In F3RZ91-0N, a program sets the data size and the transmission data in the output registers and turns on the Start-of-Sending relay. The module then sends the specified number of bytes, starting from the byte following the data size. In F3RZ91-0F, a program writes the data size to the Send Data Byte Count register, stores the transmission data to the Send Data Area and turns on the Request to Send relay. The module then sends the specified number of bytes, starting from the first byte of the Send Data Area. F3RZ91-0N
F3RZ91-0F 1
Send Data Area Size
Output registers
Transmission data
301
385
Transmission data
Send Data Byte Count register
Size
897
601
TI 34M06Z41-01E
16
Page 10
Ladder Communication Module F3RZ91-0N→F3RZ91-0F (4)
Receiving In F3RZ91-0N, the receive status and the size of received data are stored in the Receive Area. In
F3RZ91-0F only the received data is stored in the receive area while the status and data size are stored in separate dedicated registers.
17
TI 34M06Z41-01E
Ladder Communication Module F3RZ91-0N→F3RZ91-0F (5) Input Relays F3RZ91-0F has additional input relays, namely, Read Communications Mode
Status Completed relay, Initialize Receive Buffer Completed relay, Send Break Completed relay, Receive Error relay, Send Error relay and Set Communications Mode Error relay. Input Relays of F3RZ91-0F
Input Relays of F3RZ91-0N
X□□□01
Receive Completed
X□□□02
Send Completed
End-of-Setting
X□□□03
Set Communications Mode Completed
Reserved
X□□□04
Read Communications Mode Status Completed
X□□□01
End-of-Receiving
X□□□02
End-of-Sending
X□□□03 X□□□04 to X□□□32
TI 34M06Z41-01E
X□□□05
Initialize Receive Buffer Completed
X□□□06
Send Break Completed
X□□□07
Receive Error
X□□□08
Send Error
X□□□09
Set Communications Mode Error
X□□□10 to X□□□32
Reserved
18