Page 211

CHAPTER 25 SYSTEM PARAMETERS

25.5.3 Parameter CPC SPEED CPC F.F.GAIN SPLINE SPEED A-CAL SPEED INCHING SPEED EXPANSION 1 PTP WEIGHT EXPANSION 2 LOCAL CODINATE W AXIS ACCEL W AXIS DECEL OPTION DATA 1 OPTION DATA 2 OPTION DATA 3 EXPANSION 3 EXPANSION 4

RESPONSE Description

Digit

(Displayed data) CPC (interpolation) speed setting (Displayed data) F.F. gain (Displayed data) Spline speed (Displayed data) A-CAL speed (Displayed data) Inching speed (Displayed data) A-CAL sequence (Displayed data) Total work weight (Displayed data) For expansion Not used. (Displayed data) W-Axis acceleration (Displayed data) W-Axis deceleration Option data 1 Option data 2 Option data 3 Future expansion Future expansion

Minimum unit

Standard value

Note Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only Display only

25-6

Set value

Page 212

APPENDIX

Appendix Appendix A

I/O Allocation

The following table describes the DI/DO signal allocation and description for each signal during the automatic operation in AUTO mode. Table A.1 Assignment of DI Signals in AUTO Mode (Standard) No. IN0 IN1 IN2 IN3

SELECT START NEXT HOLD

Signal

IN4

POS/INCH

IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15

STOP ADDRESS 8 [256]/axis ADDRESS 9 [512]/high speed ADDRESS 0 [1] /+X(+R) ADDRESS 1 [2] /-X(-R) ADDRESS 2 [4] /+Y(+C) ADDRESS 3 [8] /-Y(-C) ADDRESS 4 [16] /↑Z ADDRESS 5 [32] /↓Z ADDRESS 6 [64] /+W ADDRESS 7 [128] /-W

Function A-CAL request Positioning start Positioning to next address Not used. (Normally servo lock ON) Select signal from IN6 to IN15 ON : Positioning address signal OFF : Manual operation signal in INCH mode ON : Stop of operation Selecting at “IN4” ・ Position address designation in binary (in [ ]) at PTP movement. ・ Signal to manipulate axis at INCHING. IN6: Select signal IN8 to IN11 ON : R and C-Axes OFF : X and Y-Axes IN7 ON : High-speed inching

Table A.2 Assignment of DO Signals in AUTO Mode (Standard) DO No. OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

Signal READY ERROR PCA AUTO BP・AREA ZONE CPOUT A-CAL MOUT0(1) MOUT1(2) MOUT2(4) MOUT3(8) MOUT4(10) MOUT5(20) MOUT6(40) MOUT7(80)

/C /R /W /Z /Y /X / / / /

Function Ready for automatic operation Error indication Positioning completion acknowledgement AUTO mode indication Pass PTP output or base area position output Z-Axis zone output CPC movement output A-CAL completion

Output signals assigned by M-data or error code displayed in binary code ( ).

Appendix-1

Page 213

APPENDIX

The MOUT signals are related to the M-data, which is the output pattern to the output port of the robot driver. M-data can be set from 0 to 99 and output in the combinations below (BCD i ). The first digit is described by the MOUT 0-3 signal and the MOUT 4-7 signal for the second digit. For example, M-data=15 means the combination of M-data=10 and Mdata=5 is output. The blanks in the table mean OFF. At the END POINT (M-data=??), all of the MOUT signals are ON. Table A.3 M-Data Output MOUT

0

M-data 0 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 ?? (END POINT)

1

2

3

4

5

6

7

ON ON

ON ON

ON ON

ON ON

ON ON ON ON ON ON

ON

ON ON

ON ON

ON ON

ON ON

ON ON ON ON ON ON

ON ON

ON i

: BCD (Binary-Coded Decimal Notation)

Appendix-2

ON

ON

ON

ON

ON

Page 214

APPENDIX

Appendix B

Extended AUTO Mode I/O Assignment

To enter extended AUTO mode, set the data by System Generation, 「ORIGIN」→「SET-UP SYSTEM」→「AUTO/ON-LINE」 to “EXT AUTO.” This mode is almost same as the AUTO mode except that the assignment of DI signals. The assignment of DI signals in extended AUTO mode is shown below. DO signals are same as the signals, which are standard, in AUTO mode. Table A.4 Assignment of DI Signals in AUTO Mode (Extension) No.

Signal

IN0 IN1

SELECT START

IN2

POS/INCH

IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15

STOP ADDRESS 0[1] /+X ADDRESS 1[2] /-X ADDRESS 2[4] /+Y ADDRESS 3[8] /-Y ADDRESS 4[16] /↑Z ADDRESS 5[32] /↓Z ADDRESS 6[64] /+W ADDRESS 7[128] /-W ADDRESS 8[256] /+R ADDRESS 9[512] /-R ADDRESS 10[1024] /+C ADDRESS 11[2148] /-C

Function Ready for automatic operation Positioning start Select signal from IN4 to IN15 ON : Positioning address signal OFF : Manual operation signal in INCH mode ON : Stop of operation

Selecting at “IN2” ・ Position address designation in binary (in [ ]) at PTP movement. ・ Signal to manipulate axis at INCHING.

Table A.5 Assignment of DO Signals in AUTO Mode (Extension=Standard) DO No. OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

Signal READY ERROR PCA AUTO BP・AREA ZONE CPOUT A-CAL MOUT0(1) MOUT1(2) MOUT2(4) MOUT3(8) MOUT4(10) MOUT5(20) MOUT6(40) MOUT7(80)

/C /R /W /Z /Y /X / / / /

Function Ready for automatic operation Error indication Positioning completion acknowledgement AUTO mode indication Pass PTP output or base area position output Z-Axis zone output CPC movement output A-CAL completion

Output signals assigned by M-data or error code displayed in binary code ( ).

Appendix-3

Page 215

APPENDIX

Appendix C

Error Code

When an error occurs in the controller during automatic operation, error message are displayed on the Teach Pendant (Refer to 23.3, “Error Message.”) and the error codes below are outputs to external devices simultaneously. Table A.6 Error Code to the External Devices

Error Message

Description

A-CAL ERR *0 Not Find A-CAL ERR *1 Not Off A-CAL ERR *2 Other On A-CAL ERR *3 Not Zero A-CAL ERR *4 Lower A-CAL ERR *5 Upper A-CAL ERR *6 Minus A-CAL ERR *7 Error

A-CAL is not executed normally.

The value for the input or motion address is out of range in the system data, 「ADDRESS MAX」 i. The designated value is out of the operational AREA ERROR ****** area of the robot. CPU LOW BATTERY Battery voltage on the CPU board becomes low. DRIVER ERROR ****** Error is occurred in the servo amplifier/driver. DRIVER NOT ONLINE Servo amplifier/driver disconnection DRIVER TIME OUT Servo amplifier/driver disconnection ENC BATTERY ****** Encoder battery voltage becomes low. EMERGENCY STOP Inputted Emergency Stop signal. OVERRUN ****** The robot is in overrun area. Positioning is not completed even the robot reached at the target position. POS.ERROR ****** Excessive load Excessive acceleration/deceleration Improper adjustment for the servo amplifier/driver. Reading data from the memory card is failed POSITION DATA ERROR during automatic operation. POSITIONING ERROR Positioning is not able to performed. SERVO DATA ERROR Servo parameters are abnormal or not be entered. SERVO ON ERROR Unable to be in servo lock condition Internal processing error. STATUS ERROR Error which is not supported is occurred. Contact your distributor. SYSTEM DATA ERROR System data is corrupted. SYSTEM ERROR Internal processing error. #:Axis ******:Axis status ADDRESS ERROR i

: System Generation, 「LIIMIT」→「ADDRESS MAX」→「ADDRESS MAX」

Appendix-4

Output Code ON-LINE AUTO Mode Mode

2#

20

30

30

4#

40

70 A# A0 A0 7# 10 5#

70 A# A0 A0 7# 10 5#

0#

09

64

64

96 67 B0

96 67 B0

16

16

63 68

63 68

Page 216

APPENDIX

Appendix D

Motor Code

Preprogrammed motor code parameters set to system configuration are shown below. Table A.7 Motor Code Table Motor Code Decimal 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79

Am p

Motor Part #

15A

30A

Motor Power

Max.Rev. (rpm)

65ZBM001D 65ZBM002D 65ZBM003D 65ZBM007D 65ZBM010D 68ZBM025H P50B03003D P50B04006D P50B04010D P50B05005D P50B05010D P50B05020D P50B07010D P50B07020D P50B07030D P30B04003D P30B04005D P30B04010D P30B06020D P30B06010D

30 50 100 180 300 480 30 60 100 50 100 200 100 200 300 30 50 100 200

4500 4500 4500 4500 4500 3000 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500

65ZBM014D 65ZBM020D 65ZBM030H 65ZBM040H 68ZBM035H P50B07040D P50B08040D P50B08050D P50B08075H P50B08100H P30B06040D P30B08075D 61BM030B 61BM060B P80B15075H P60B13050H

400 500 750 1000 660 400 400 500 750 1000 400 750 500 1000 750 500

4500 4500 3000 3000 3000 4500 4500 4500 3000 3000 4500 4500 2000 2000 3000 3000

Motor Code Decimal 96 97 98 99 100 101 102 103 104 105 106 128 129 130 131 132 133 134 135

160 161 162 163 164 165 166 167 168 169 170

Appendix-5

Amp

50A

100A

150A

Motor Part #

Motor Power

Max.Rev. (rpm)

65ZBM030D 65ZBM040D 68ZBM065H 68ZBM090H P50B08075D P50B08100D 61BM090B 61BM120B P80B18120H P60B13100H P60B13150H

750 1000 1200 1600 750 1000 1400 2000 1200 1000 1500

4500 4500 3000 3000 4500 4500 2000 2000 3000 3000 3000

68ZBM140H 68ZBM220R 61BM220B 61BM330B P80B22250H P80B22350R P60B13200H P60B18200H

2500 3600 3300 4500 2500 3500 2000 2000

3000 2500 2000 2000 3000 2500 3000 3000

68ZBM330R 61BM470M P80B22350H P80B22450R P60B15300H P60B18350H P60B18450R P60B22550M P60B22700S P60B18550R P60B22700M

4500 5200 3500 4500 3000 3500 4500 5500 7000 5500 7000

2500 1500 3000 2500 3000 3000 2500 1500 1000 2500 1500

Page 217

APPENDIX

Appendix E

Data Backup and Data Load Table A.8 Back Up and Data Load Stored Location

Backup

System Data (System Generation, System Parameters)

RAM

Memory card

Servo Parameters

RAM

Memory card

Position data

RAM

Memory card

Configuration

EE-PROM

None

Data

Default Value Setting

Data Load

Refer to Chapter 21, “Initializing System Data.”

Download from the memory card.

Refer to Chapter 21, “Initializing System Data.” Refer to Chapter 22, “Initializing Position Data.” None

Download from the memory card. Download from the memory card. Replace EE-PROM.

Appendix-6