Page 20
Getting Started
In This Chapter....
1 page, Introduction ..................................................... 2, L100 Inverter Specifications ............................ 5, Introduction to Variable-Frequency Drives .... 18, Frequently Asked Questions ......................... 23
Page 21
1–2
Introduction
Getting Started
Introduction Main Features Congratulations on your purchase of an L100 Series Hitachi inverter! This inverter drive features state-of-the-art circuitry and components to provide high performance. The housing footprint is exceptionally small, given the size of the corresponding motor. The Hitachi L100 product line includes more than a dozen inverter models to cover motor sizes from 1/4 horsepower to 10 horsepower, in either 230 VAC or 460 VAC power input versions. The main features are: • 200V and 400V Class inverters • UL or CE version available • V/f (volts-per-hertz) control algorithm, selectable for either constant or reduced torque loads • Convenient keypad for parameter settings • Built-in RS-422 communications interface to allow configuration from a PC and for field bus external modules.
Model L100-002NFU
• Sixteen programmable speed levels • Two-step acceleration and deceleration curves • PID control adjusts motor speed automatically to maintain a process variable value The design in Hitachi inverters overcomes many of the traditional trade-offs between speed, torque and efficiency. The performance characteristics are: • Output frequency range from 0.5 to 360 Hz • Continuous operation at 100% torque within a 1:10 speed range (6/60 Hz / 5/50 Hz) without motor derating
Page 22
L100 Inverter
1–3
A full line of accessories from Hitachi is available to complete your application: • Dynamic braking unit • Radio noise filters, CE compliance filters, and EMI filters (shown below) • DIN rail mounting adapter (35mm rail size)
EMI Filter
Operator Interface Options The optional SRW-0EX digital operator / copy unit is shown to the right. It has the additional capability of reading (uploading) the parameter settings in the inverter into its memory. Then you can connect the copy unit on another inverter and write (download) the parameter settings into that inverter. OEMs will find this unit particularly useful, as one can use a single copy unit to transfer parameter settings from one inverter to many. Other digital operator interfaces may be available from your Hitachi distributor for particular industries or international markets. Contact your Hitachi distributor for further details.
Digital Operator / Copy Unit
Getting Started
• Digital remote operator keypad
Page 23
1–4
Introduction
Getting Started
Inverter Specifications Label The Hitachi L100 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, motor, and application safety requirements. Regulatory agency approvals
Specifications label
Inverter model number Motor capacity for this model Power Input Rating: frequency, voltage, phase, current Output Rating: Frequency, voltage, current Manufacturing codes: Lot number, date, etc.
Model Number Convention The model number for a specific inverter contains useful information about its operating characteristics. Refer to the model number legend below: L100
004
H
F
U
5 Version number (_, 1, 2, ...) Restricted distribution: E=Europe, U=USA
Series name
Configuration type F = with digital operator (keypad) Input voltage: N = single or three-phase 200V class H = three-phase 400V class L = three phase only, 200V class Applicable motor capacity in kW 022 = 2.2 kW 002 = 0.2 kW 030 = 3.0 kW 004 = 0.4 kW 037 = 3.7 kW 005 = 0.55 kW 040 = 4.0 kW 007 = 0.75 kW 055 = 5.5 kW 011 = 1.1 kW 075 = 7.5 kW 015 = 1.5 kW
Page 24
1–5
L100 Inverter
L100 Inverter Specifications The following tables are specific to L100 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–9 apply to both voltage class groups. Footnotes for all specifications tables follow the table below. Item L100 inverters, 200V models
200V Class Specifications
CE version
002NFE
004NFE
005NFE
007NFE
011NFE
UL version
002NFU
004NFU, 007NFU, kW
0.2
0.4
0.55
0.75
1.1
HP
1/4
1/2
3/4
1
1 1/2
0.5
1.0
1.2
1.6
2.0
Applicable motor size *2
Rated capacity (240V) kVA *10 Rated input voltage
Rated input current (A)
1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%, 3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%, (037LFU, 055LFU & 075LFU 3-phase only)
1-phase
3.1
5.8
6.7
9.0
11.2
3-phase
1.8
3.4
3.9
5.2
6.5
Rated output voltage *3
3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)
1.4
2.6
3.0
4.0
5.0
Efficiency at 100% rated output (%)
91.5
92.8
93.6
94.1
95.4
Watt loss, at 70% output approximate (W) at 100% output
13
21
25
31
38
17
29
32
41
51
Braking
Dynamic braking, approx. % torque, (short time stop from 50 / 60 Hz) *5 DC braking
Weight
100%: ≤ 50 Hz, 50%: ≤ 60 Hz Capacitive feedback type, dynamic braking unit and braking resistor optional, individually installed Variable operating frequency, time, and braking force kg
0.85
0.85
1.3
1.3
2.2 lb
1.87
1.87
2.87
2.87
4.85
Getting Started
Model-specific tables for 200V and 400V class inverters
Page 25
1–6
L100 Inverter Specifications
Getting Started
Footnotes for the preceding table and the tables that follow: Note 1: Note 2:
The protection method conforms to JEM 1030. The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to prevent the rated motor current (50/ 60 Hz) from exceeding the rated output current of the inverter. Note 3: The output voltage decreases as the main supply voltage decreases (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage. Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for the maximum allowable rotation speed. Note 5: The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average deceleration torque varies with motor loss. This value decreases when operating beyond 50 Hz. Note that a braking unit is not included in the inverter. If a large regenerative torque is required, the optional regenerative braking unit should be used. Note 6: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not satisfactory for your application, contact your Hitachi sales representative. Note 7: If operating the inverter in an ambient temperature of 40–50° C, reduce the carrier frequency to 2.1 kHz, derate the output current by 80%, and remove the top housing cover. Note that removing the top cover will nullify the NEMA rating for the inverter housing. Note 8: The storage temperature refers to the short-term temperature during transport. Note 9: Conforms to the test method specified in JIS C0911 (1984). For the model types excluded in the standard specifications, contact your Hitachi sales representative. Note 10: The input voltage of xxLFU is 230V.
Page 26
1–7
L100 Inverter L100 Inverter Specifications, continued...
L100 inverters, 200V models
200V Class Specifications, continued
CE version
015NFE
022NFE, - - UL version
015NFU
022NFU
037LFU
055LFU
075LFU kW
1.5
2.2
3.7
5.5
7.5
HP
2
3
5
7.5
10
2.9
4.1
6.3
9.6
12.7
Applicable motor size *2
Rated capacity (240V) kVA *10 Rated input voltage
Rated input current (A)
1-phase: 200 to 240V +5%/–10%, 50/60 Hz ±5%, 3-phase: 200 to 240V +5%/–10%, 50/60 Hz ±5%, (037LFU, 055LFU & 075LFU 3-phase only)
1-phase
16.0
22.5, - - 3-phase
9.3
13.0
20.0
30.0
40.0
Rated output voltage *3
3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)
7.1
10.0
15.9
24
32
Efficiency at 100% rated output (%)
95.3
95.6
95.5
96.1
96.2
Watt loss, at 70% output approximate (W) at 100% output
50
71
118
152
204
70
97
166
216
288
Braking
Dynamic braking, approx. % torque, (short time stop from 50 / 60 Hz) *5 DC braking
Weight
100%: ≤ 50Hz 50%: ≤ 60Hz
40%: ≤ 50Hz 20%: ≤ 60Hz
20%: ≤ 50Hz 20%: ≤ 60Hz
Capacitive feedback type, dynamic braking unit and braking resistor optional, individually installed Variable operating frequency, time, and braking force kg
2.2
2.8
2.8
5.5
5.7 lb
4.85
6.17
6.17
12.13
12.57
Getting Started
Item
Page 27
1–8
L100 Inverter Specifications
Getting Started
Item L100 inverters, 400V models
400V Class Specifications
CE version
004HFE
007HFE
015HFE
022HFE
UL version
004HFU
007HFU
015HFU
022HFU kW
0.4
0.75
1.5
2.2
HP
1/2
1
2
3
1.1
1.9
3.0
4.3
Applicable motor size *2
Rated capacity (460V) kVA *10 Rated input voltage
3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A)
2.0
Rated output voltage *3
3-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A)
1.5
2.5
3.8
5.5
Efficiency at 100% rated output (%)
92.0
93.7
95.7
95.8
Watt loss, at 70% output approximate (W) at 100% output
25
33
48
68
32
44
65
92
Braking
Dynamic braking, approx. % torque, (short time, stopping from 50 / 60 Hz) *5 DC braking
Weight
3.3
5.0
100%: ≤ 50Hz 50%: ≤ 60Hz
7.0
40%: ≤ 50Hz, 20%: ≤ 60Hz
Capacitive feedback type, dynamic braking unit and braking resistor optional, individually installed Variable operating frequency, time, and braking force kg
1.3
1.7
1.7
2.8 lb
2.87
3.75
3.75
6.17
Page 28
1–9
L100 Inverter
Item CE version
030HFE
040HFE
055HFE
075HFE
UL version, 040HFU
055HFU
075HFU kW
3.0
4.0
5.5
7.5
HP
4
5
7.5
10
6.2
6.8
10.4
12.7
Applicable motor size *2
Rated capacity (460V) kVA *10 Rated input voltage
3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A)
10.0
Rated output voltage *3
3-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A)
7.8
8.6
13
16
Efficiency at 100% rated output (%)
95.4
96.2
96.0
96.5
Watt loss, at 70% output approximate (W) at 100% output
100
108
156
186
138
151
219
261
Braking
Dynamic braking, approx. % torque, (short time stop from 50 / 60 Hz) *5
16.5
40%: ≤ 50Hz, 20%: ≤ 60Hz
20.0
20%: ≤ 50Hz 20%: ≤ 60Hz
Capacitive feedback type, dynamic braking unit and braking resistor optional, individually installed
DC braking Weight
11.0
Variable operating frequency, time, and braking force kg
2.8
2.8
5.5
5.7 lb
6.17
6.17
12.13
12.57
General Specifications The following table applies to all L100 inverters. Item
General Specifications
Protective housing *1
IP20
Control method
Sine wave pulse-width modulation (PWM) control
Output frequency range *4
0.5 to 360 Hz
Frequency accuracy
Digital command: 0.01% of the maximum frequency Analog command: 0.1% of the maximum frequency (25°C ± 10°C)
Frequency setting resolution
Digital: 0.1 Hz; Analog: max. frequency/1000
Volt./Freq. characteristic
V/f optionally variable, V/f control (constant torque, reduced torque)
Overload current rating
150%, 60 seconds
Acceleration/deceleration time
0.1 to 3000 sec., (linear accel/decel), second accel/decel setting available
Getting Started
L100 inverters, 400V models
400V Class Specifications, continued