Manual · Hitachi
L100 Series Inverter Instruction Manual
Manual193 pagesPDF 5.1 MB
Instruction manual for Hitachi L100 Series inverters (variable-frequency drives), including the 400V class L100-040HFU.
Covers · 1 model
The models it covers
Summary
What is in it
The instruction manual for the Hitachi L100 Series inverters in the single-phase 200V, three-phase 200V and three-phase 400V classes, a family that includes the L100-040HFE/HFU. It gives the specifications and derating curves, an introduction to variable-frequency drives, step-by-step mounting, wiring and powerup testing, the front panel keypad, every drive parameter group (D, F, A, B and C), use of the intelligent input and output terminals, PID and analog operation, accessories such as dynamic braking, and troubleshooting and maintenance.
Its parts
- Getting Started
- Inverter Mounting and Installation
- Configuring Drive Parameters
- Operations and Monitoring
- Inverter System Accessories
- Troubleshooting and Maintenance
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the Hitachi L100 Series Inverter Instruction Manual (NB576XE, December 2003), covering the whole L100 line of 200V and 400V class inverters, the L100-040HFU among them. It gives specifications, installation, parameter setup, terminal wiring, accessories, error codes and maintenance.
- What it is
- L100-040HFU: Hitachi L100 series inverter, 400V class three-phase input, with digital operator (keypad) p. 21, 23
- Motor size
- L100-040HFU: 4.0 kW (5 HP) p. 23, 28
- Input power
- L100-040HFU: 3-phase 380 to 460V ±10%, 50/60 Hz ±5% p. 28
- Rated output
- L100-040HFU: 8.6 A, 3-phase 380 to 460V p. 28
- Weight
- L100-040HFU: 2.8 kg (6.17 lb) p. 28
- Output frequency
- 0.5 to 360 Hz p. 28
- Temperature
- Operating (ambient) -10 to 50°C, derating above 40°C; storage -25 to 70°C p. 25, 29
- Housing
- IP20 p. 28
- Communications
- Built-in RS-422 interface for PC configuration and field bus modules p. 21
- Overload rating
- 150%, 60 seconds p. 28
- Intelligent terminals
- Inputs: FW, RV, CF1~CF4, JG, 2CH, FRS, EXT, USP, SFT, AT, RS, PTC; outputs: RUN, FA1,2, OL, OD, AL p. 29
- Alarm relay
- 250 VAC, 2.5A (R load) max.; 30 VDC, 3.0A (R load) max. p. 30
- Options
- SRW-0EX digital operator / copy unit, dynamic braking unit, FFL100 series EMI filter, DIN rail mounting adapter (35mm rail) p. 22, 148
What this manual walks you through
- Reading the inverter model number p. 23
- Choosing a carrier frequency from the derating curves p. 31
- Choosing reactors, noise filters and braking accessories p. 146, 147, 148
- Troubleshooting a motor that will not run, runs the wrong way or misses its speed p. 154, 155
- Reading and clearing error codes p. 156, 157
- Clearing the trip history p. 156
- Daily and periodic inspection p. 153
Good to know
- Wait at least five minutes after turning off input power before maintenance or inspection. p. 153
- Between 40 and 50° C ambient, reduce the carrier frequency to 2.1 kHz, derate output current by 80% and remove the top cover, which nullifies the NEMA rating. p. 25
- A braking unit is not included in the inverter. p. 25
- Ground fault detection at powerup protects the inverter, not people. p. 157
- After editing data, wait six seconds or more before turning power off. p. 155
Questions this manual answers
What does error E05 mean on a Hitachi L100?
Overload protection: the electronic thermal function detected a motor overload, so the inverter tripped and turned off its output. p. 156
How do I clear a fault on the L100 inverter?
Press the Stop/Reset key. p. 156
What does E08 mean on the L100?
An EEPROM error, caused by noise or excessive temperature; afterward, confirm the parameter values are still correct. p. 156, 157
What input voltage does the L100-040HFU need?
3-phase 380 to 460V ±10%, 50/60 Hz ±5%. p. 28
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 23 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 151-15
- Table of Contents16-19
- Getting Started, pages 20 to 2820-28
- Getting Started, pages 29 to 3729-37
- Getting Started, pages 38 to 4438-44
- Inverter Mounting and Installation, pages 45 to 5345-53
- Inverter Mounting and Installation, pages 54 to 6254-62
- Inverter Mounting and Installation, pages 63 to 7163-71
- Configuring Drive Parameters, pages 72 to 8172-81
- Configuring Drive Parameters, pages 82 to 9182-91
- Configuring Drive Parameters, pages 92 to 10192-101
- Configuring Drive Parameters, pages 102 to 111102-111
- Operations and Monitoring, pages 112 to 120112-120
- Operations and Monitoring, pages 121 to 129121-129
- Operations and Monitoring, pages 130 to 138130-138
- Operations and Monitoring, pages 139 to 144139-144
- Inverter System Accessories145-151
- Troubleshooting and Maintenance, pages 152 to 159152-159
- Troubleshooting and Maintenance, pages 160 to 167160-167
- Glossary and Bibliography168-175
- Drive Parameter Settings Tables176-182
- CE-EMC Installation Guidelines183-188
- Index189-193
The file