The text of a manual · part 13 of 23
L100 Series Inverter Instruction Manual: Operations and Monitoring, pages 112 to 120
Pages 112 to 120 of 193, from L100 Series Inverter Instruction Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi L100-040HFU
Page 112
Operations and Monitoring In This Chapter....
4 page, Introduction ..................................................... 2, Connecting to PLCs and Other Devices ......... 4, Using Intelligent Input Terminals ..................... 8, Using Intelligent Output Terminals ................ 21, Analog Input Operation ................................. 29, Analog and Digital Monitor Output ................ 30, PID Loop Operation ...................................... 32, Configuring the Inverter for Multiple Motors .. 33
Page 113
4–2
Introduction
Introduction The previous material in Chapter 3 gave a reference listing of all the programmable functions of the inverter. We suggest that you first scan through the listing of inverter functions to gain a general familiarity. This chapter will build on that knowledge in the following ways: 1. Related functions – Some parameters interact with or depend on the settings in other functions. This chapter lists “required settings” for a programmable function to serve as a cross-reference and an aid in showing how functions interact. 2. Intelligent terminals – Some functions rely on an input signal on a control logic connector terminal, or generate output signals in other cases. 3. Electrical interfaces – This chapter shows how to make connections between the inverter and other electrical devices. 4. PID Loop Operation – The L100 has a built-in PID loop that calculates the optimal inverter output frequency to control an external process. This chapter shows the parameters and input/output terminals associated with PID loop operation. 5. Multiple motors – A single L100 inverter may be used with two or more motors in some types of applications. This chapter shows the electrical connections involved in multiple-motor applications. The topics in this chapter can help you decide the features that are important to your application, and how to use them. The basic installation covered in Chapter 2 concluded with the powerup test and running the motor. Now, this chapter starts from that point and shows how to make the inverter part of a larger control or automation system.
Caution Messages for Operating Procedures
Operations and Monitoring
Before continuing, please read the following Caution messages. CAUTION: The heat sink fins will have a high temperature. Be careful not to touch them. Otherwise, there is the danger of getting burned. CAUTION: The operation of the inverter can be easily changed from low speed to high speed. Be sure check the capability and limitations of the motor and machine before operating the inverter. Otherwise, it may cause injury to personnel. CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage.
Page 114
L100 Inverter
4–3
Warning Messages for Operating Procedures Before continuing, please read the following Warning messages. WARNING: Be sure to turn ON the input power supply only after closing the front case. While being energized, be sure not to open the front case. Otherwise, there is the danger of electric shock. WARNING: Be sure not to operate electrical equipment with wet hands. Otherwise, there is the danger of electric shock. WARNING: While the inverter is energized, be sure not to touch the inverter terminals even when the motor is stopped. Otherwise, there is the danger of electric shock. WARNING: If the Retry Mode is selected, the motor may suddenly restart after a trip stop. Be sure to stop the inverter before approaching the machine (be sure to design the machine so that safety for personnel is secure even if it restarts.) Otherwise, it may cause injury to personnel. WARNING: If the power supply is cut OFF for a short period of time, the inverter may restart operation after the power supply recovers if the Run command is active. If a restart may pose danger to personnel, so be sure to use a lock-out circuit so that it will not restart after power recovery. Otherwise, it may cause injury to personnel. WARNING: The Stop Key is effective only when the Stop function is enabled. Be sure to enable the Stop Key separately from the emergency stop. Otherwise, it may cause injury to personnel.
WARNING: Be sure not to touch the inside of the energized inverter or to put any conductive object into it. Otherwise, there is a danger of electric shock and/or fire. WARNING: If power is turned ON when the Run command is already active, the motor will automatically start and injury may result. Before turning ON the power, confirm that the RUN command is not present. WARNING: When the Stop key function is disabled, pressing the Stop key does not stop the inverter, nor will it reset a trip alarm. WARNING: Be sure to provide a separate, hard-wired emergency stop switch when the application warrants it.
Operations and Monitoring
WARNING: During a trip event, if the alarm reset is applied and the Run command is present, the inverter will automatically restart. Be sure to apply the alarm reset only after verifying the Run command is OFF. Otherwise, it may cause injury to personnel.
Page 115
4–4
Connecting to PLCs and Other Devices
Connecting to PLCs and Other Devices Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configuration. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device. In a simple application such as single-conveyor speed control, a Run/Stop switch and potentiometer will give the operator all the required control. In a sophisticated application, you may have a programmable logic controller (PLC) as the system controller, with several connections to the inverter. It is not possible to cover all the possible types of application in this manual. It will be necessary for you to know the electrical characteristics of the devices you want to connect to the inverter. Then, this section and the following sections on I/O terminal functions can help you quickly and safely connect those devices to the inverter. CAUTION: It is possible to damage the inverter or other devices if your application exceeds the maximum current or voltage characteristics of a connection point.
Operations and Monitoring
The connections between the inverter and other devices rely on the electrical input/ output characteristics at both ends of each connection, shown in the diagram to the right. The inverter’s inputs require a sourcing output from an external device (such as a PLC). This chapter shows the inverter’s internal electrical component(s) at each I/O terminal. In some cases, you will need to insert a power source in the interface wiring.
Other device Input circuit
Output circuit
Output circuit signal return
Input circuit
PLC +Com
In order to avoid equipment damage and get your application running smoothly, we recommend drawing a schematic of each connection between the inverter and the other device. Include the internal components of each device in the schematic, so that it makes a complete circuit loop.
Inverter P24
+–
24V
1 2 3
Input circuits
4
After making the schematic, then: 1. Verify that the current and voltage for each connection is within the operating limits of each device.
L100 Inverter signal return
5 GND
L
2. Make sure that the logic sense (active high or active low) of any ON/OFF connection is correct. 3. Check the zero and span (curve end points) for analog connections, and be sure the scale factor from input to output is correct. 4. Understand what will happen at the system level if any particular device suddenly loses power, or powers up after other devices.
Page 116
4–5
L100 Inverter
Example Wiring Diagram The schematic diagram below provides a general example of logic connector wiring, in addition to basic power and motor wiring covered in Chapter 2. The goal of this chapter is to help you determine the proper connections for the various terminals shown below for your specific application needs. Breaker, MCCB or GFI
R
L100
U
(L1)
Power source, 3-phase or 1-phase, per inverter model
(T1)
S
V
(L2)
(T2)
T
W
N(L3)
(T3)
Intelligent inputs, 5 terminals
+1 P24
Forward NOTE: For the wiring of intelligent I/O and Reverse analog inputs, be sure to use twisted pair / shielded cable. Attach the shield wire for each signal to its respective common terminal at the inverter end only.
1
24V Input circuits
+ –
Braking unit (optional)
3 4
[5] configurable as discrete input or thermistor input
–
AL0 L FM Analog reference
H
0–10VDC
O
4–20mA
OI
Analog common
L
Operations and Monitoring
AL1
Thermistor
Meter
DC reactor (optional)
+
2
5
Logic input common
Motor
Alarm contacts, type 1 Form C
AL2 Open collector outputs
Output circuits
12
Run signal Load
11
Freq. arrival signal Load
+ –
CM2
Logic output common
Page 117
4–6
Example Wiring Diagram
Specifications of Control and Logic Connections The control logic connectors are located just behind the front panel half-door. The relay contacts are accessible behind the main door. Connector labeling is shown below.
Logic inputs
L 5 4 3 2 1 P24 H O OI L FM CM2 12 11 Analog inputs
Analog output
AL0 AL1 AL2 Relay contacts
Logic outputs
Specifications for the logic connection terminals are in the following table: Terminal Name
Operations and Monitoring
[P24]
Description
Ratings
+24V for logic inputs
24VDC, 30 mA max (do not short to terminal L)
[1], [2], [3], [4], [5] Discrete logic inputs
27VDC max. (use P24 or an external supply referenced to terminal L)
[L] (top row) *1
GND for logic inputs sum of input 1-5 currents (return)
[11], [12]
Discrete logic outputs
50mA maximum ON state current, 27 VDC maximum OFF state voltage
[CM2]
GND for logic outputs
100 mA: sum of 11 and 12 currents (return)
[FM]
PWM (analog/digital) output 0 to 10VDC, 1 mA, PWM and 50% duty digital
[L] (bottom row) *1 GND for analog inputs sum of OI, O, and H currents (return)
[OI]
Analog input, current
4 to 19.6 mA range, 20 mA nominal
[O]
Analog input, voltage
0 to 9.6 VDC range, 10VDC nominal, input impedance 10 kΩ
[H]
+10V analog reference
10VDC nominal, 10 mA max
[AL0]
Relay common contact
250 VAC, 2.5A (R load) max., 250 VAC, 0.2A (I load, P.F.=0.4) max. Relay contact, normally 100 VAC, 10mA min. closed during RUN 30 VDC, 3.0A (R load) max. Relay contact, normally open 30 VDC, 0.7A (I load, P.F.=0.4) max. 5 VDC, 100mA min. during RUN
[AL1] [AL2]
Note 1:
The two terminals [L] are electrically connected together inside the inverter.
Page 118
4–7
L100 Inverter
Terminal Listing Use the following tables to locate pages for intelligent input and output material in this chapter. Intelligent Inputs Symbol
Code
Name
Page
FW
00
Forward Run/Stop
4–9
RV
01
Reverse Run/Stop
4–9
CF1
02
Multi-speed Select, Bit 0 (LSB)
4–10
CF2
03
Multi-speed Select, Bit 1
4–10
CF3
04
Multi-speed Select, Bit 2
4–10
CF4
05
Multi-speed Select, Bit 3
4–10
JG
06
Jogging
4–12
2CH
09
2-stage Acceleration and Deceleration
4–13
FRS
11
Free-run Stop
4–14
EXT
12
External Trip
4–15
USP
13
Unattended Start Protection
4–16
SFT
15
Software Lock
4–17
AT
16
Analog Input Voltage/current Select
4–18
RS
18
Reset Inverter
4–19
TH
19
Thermistor Thermal Protection
4–20
Symbol
Code
Name
Page
RUN
00
Run Signal
4–22
FA1
01
Frequency Arrival type 1 – Constant Speed
4–23
FA2
02
Frequency arrival type 2 – Over-frequency
4–23
OL
03
Overload Advance Notice Signal
4–25
OD
04
Output Deviation for PID Control
4–26
AL
05
Alarm Signal
4–27
Operations and Monitoring
Intelligent Outputs
Page 119
4–8
Using Intelligent Input Terminals
Using Intelligent Input Terminals Terminals [1], [2], [3], [4], and [5] are identical, programmable inputs for general use. The input circuits can use the inverter’s internal (isolated) +24V field supply (P24) to power the inputs. The input circuits are internally connected to the power supply ground. As the diagram shows, you can use a switch (or jumper) to activate an input terminal that has been configured. If you use an external supply, its GND terminal must connect to the [L] terminal on the inverter to complete the input circuit. Current can only flow into each input, so they are sinking inputs, whether powered internally or externally. NOTE: We recommend using the top row [L] logic GND for logic input circuits and the [L] GND on the bottom row of terminals for analog I/O circuits.
L100 Inverter 24V
Sinking inputs, internal supply
+–
Operations and Monitoring
P24
Input circuits
L
Sinking inputs, external supply
5
4
3
2
1
L100 Inverter 24V
+–
P24
Input circuits
L – + 24V
5
4
3
2
1
Page 120
L100 Inverter
4–9
Forward Run/Stop and Reverse Run/Stop Commands: When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low). Option Code
Terminal Symbol
Function Name
State
00
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
Valid for inputs:
C_01, C_02, C_03, C_04, C_05
Required settings:
A_02 = 01
Notes: • When the Forward Run and Reverse Run commands are active at the same time, the inverter enters the Stop Mode. • When a terminal associated with either [FW] or [RV] function is configured for normally closed, the motor starts rotation when that terminal is disconnected or otherwise has no input voltage.
Description
Example (default input configuration shown - see page 3–32): RV FW
L 5 4 3 2 1 P24
See I/O specs on page 4–6.
WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.
Operations and Monitoring
NOTE: The parameter F_04, Keypad Run Key Routing, determines whether the single Run key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] and [RV] input terminal operation.