L100 Series Inverter Instruction Manual: Operations and Monitoring, pages 121 to 129

Pages 121 to 129 of 193, from L100 Series Inverter Instruction Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi L100-040HFU

Page 121

4–10

Using Intelligent Input Terminals

Multi-Speed Select The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are accessible through programming four of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right. These can be any of the five inputs, and in any order. You can use fewer inputs if you need eight or fewer speeds. Note: When choosing a subset of speeds to use, always start at the top of the table, and with the least-significant bit: CF1, CF2, etc. The example with eight speeds in the figure below shows how input switches configured for CF1–CF3 functions can change the motor speed in real time.

Operations and Monitoring

3rd Speed 7th 5th 2nd 1st 6th 4th 0th

1 [CF1] 0 1 [CF2] 0 1 [CF3] 0 1 [FWD] 0

Multispeed

Input Function CF4 CF3 CF2 CF1

Speed 0

0

0

0

0

Speed 1

0

0

0

1

Speed 2

0

0

1

0

Speed 3

0

0

1

1

Speed 4

0

1

0

0

Speed 5

0

1

0

1

Speed 6

0

1

1

0

Speed 7

0

1

1

1

Speed 8

1

0

0

0

Speed 9

1

0

0

1

Speed 10

1

0

1

0

Speed 11

1

0

1

1

Speed 12

1

1

0

0

Speed 13

1

1

0

1

Speed 14

1

1

1

0

Speed 15

1

1

1

1

NOTE: Speed 0 is set by the A_20 parameter value.

t Option Code

Terminal Symbol

02

CF1

03

04

05

CF2

CF3

CF4

Function Name Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB)

Input State

Description

ON

Binary encoded speed select, Bit 0, logical 1

OFF

Binary encoded speed select, Bit 0, logical 0

ON

Binary encoded speed select, Bit 1, logical 1

OFF

Binary encoded speed select, Bit 1, logical 0

ON

Binary encoded speed select, Bit 2, logical 1

OFF

Binary encoded speed select, Bit 2, logical 0

ON

Binary encoded speed select, Bit 3, logical 1

OFF

Binary encoded speed select, Bit 3, logical 0

Page 122

L100 Inverter

Option Code

Terminal Symbol

Function Name

Input State

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

F_01, A_01 = 02, A_20 to A_35

Notes: • When programming the multi-speed settings, be sure to press the Store key each time and then set the next multi-speed setting. Note that when the key is not pressed, no data will be set. • When a multi-speed setting more than 50Hz(60Hz) is to be set, it is necessary to program the maximum frequency A_04 high enough to allow that speed.

4–11

Description Example (some CF inputs require input configuration; some are default inputs - see page 3–32): (MSB) (LSB) CF3 CF1 CF4 CF2

L 5 4 3 2 1 P24

See I/O specs on page 4–6.

While using the multi-speed capability, you can monitor the current frequency with monitor function D_01 during each segment of a multi-speed operation. NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F_01 or change the value of F_01 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F_01 during Run Mode, please monitor D_01 instead of F_01. There are two ways to program the speeds into the registers A_20 to A_35: 1. Standard keypad programming: a. Select each parameter A_20 to A_35. b. Press the FUNC. key to view the parameter value. c. Use the

1 and

2 keys to edit the value.

2. Programming using the CF switches. Set the speed by following these steps: a. Turn the Run command OFF (Stop Mode). b. Turn each switch ON and set it to Multi-speed. Display the value of F_01 on the digital operator. c. Set the desired output frequency by pressing the

1 and

2 keys.

d. Press the STR key once to store the set frequency. When this occurs, F_01 indicates the output frequency of Multi-speed n. e. Press the FUNC. key once to confirm that the indication is the same as the set frequency. f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. It can be set also by parameters A_20 to A_35 in the first procedure 1. a) to 1. d).

Operations and Monitoring d. Use the STR key to save the data to memory.

Page 123

4–12

Using Intelligent Input Terminals

Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to 10 Hz. The frequency for the jogging operation is set by parameter A_38. Jogging does not use an acceleration ramp, so we recommend setting the jogging frequency A_38 to 5 Hz or less to prevent tripping.

1 0 [FW], 1 [RV] 0 [JG]

Jog speed A 38

When the terminal [JG] is turned ON and the Run command is issued, the inverter outputs the programmed jog frequency to the motor. To enable the Run key on the digital operator for jog input, set the value 01(terminal mode) in A_02 (Run command source).

A 39 Jog decel type t

The type of deceleration used to end a motor jog operation is selectable by programming function A_39. The options are: • 00 Free-run stop (coasting) • 01 Deceleration (normal level) and stop

Operations and Monitoring

• 02 Use DC braking and stop

Option Code

Terminal Symbol

06

JG

Function Name Jogging

Input State

Description

ON

Inverter is in Run Mode, output to motor runs at jog parameter frequency

OFF

Inverter is in Stop Mode

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

A_02= 01, A_38 > B_82, A_38 > 0, A_39

Notes: • No jogging operation is performed when the set value of jogging frequency A_38 is smaller than the start frequency B_82, or the value is 0 Hz. • Be sure to stop the motor when switching the function [JG] ON or OFF.

Example (requires input configuration - see page 3–32): JG

L 5 4 3 2 1 P24

See I/O specs on page 4–6.

Page 124

L100 Inverter

4–13

Two-stage Acceleration and Deceleration When terminal [2CH] is turned ON, the Output inverter changes the rate of acceleration and frequency deceleration from the initial settings (F_02 second and F_03) to use the second set of accelerainitial tion/deceleration values. When the terminal is turned OFF, the inverter is returned to the 1 [2CH] original acceleration and deceleration time 0 (F_02 acceleration time 1, and F_03 decelera- [FW], 1 [RV] 0 tion time 1). Use A_92 (acceleration time 2) and A_93 (deceleration time 2) to set the second stage acceleration and deceleration times.

target frequency t

In the graph shown above, the [2CH] becomes active during the initial acceleration. This causes the inverter to switch from using acceleration 1 (F_02) to acceleration 2 (A_92). Option Code

Terminal Symbol

09

2CH

Function Name 2-stage Acceleration and Deceleration

Input State

Description

ON

Frequency output uses 2nd-stage acceleration and deceleration values

OFF

Frequency output uses the initial acceleration 1 and deceleration 1 values

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

A_92, A_93, A_94=00

Notes: • Function A_94 selects the method for second stage

Example (requires input configuration - see page 3–32): 2CH

L 5 4 3 2 1 P24

See I/O specs on page 4–6.

Operations and Monitoring acceleration. It must be set = 00 to select the input terminal method in order for the [2CH] terminal assignment to operate.

Page 125

4–14

Using Intelligent Input Terminals

Free-run Stop When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power to the motor if the Run command is still active. The free-run stop feature works with other parameters to provide flexibility in stopping and starting motor rotation. In the figure below, parameter B_88 selects whether the inverter resumes operation from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS] terminal turns OFF. The application determines the best setting. Parameter B_03 specifies a delay time before resuming operation from a free-run stop. To disable this feature, use a zero delay time. Resume from motor speed B_88 = 01

B_88 = 00 Zero-frequency start

B 03 wait time

Motor speed

Motor speed

1 0 [FW], 1 [RV] 0

1 FRS 0 [FW], 1 [RV] 0

Operations and Monitoring

FRS

Option Code

Terminal Symbol

11

FRS t

Function Name Free-run Stop

Input State t

Description

ON

Causes output to turn OFF, allowing motor to free run (coast) to stop

OFF

Output operates normally, so controlled deceleration stops motor

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

B_03, B_88, C_11 to C_15

Notes: • When you want the [FRS] terminal to be active low

Example (requires input configuration - see page 3–32): FRS

L 5 4 3 2 1 P24

(normally closed logic), change the setting (C_11 to C_15) that corresponds to the input (C_01 to C_05) that is assigned the [FRS] function. See I/O specs on page 4–6.

Page 126

4–15

L100 Inverter

External Trip When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of the error depends on what you connect to the [EXT] terminal. Even if the [EXT] input is turned OFF, the inverter remains in the trip state. You must reset the inverter or cycle power to clear the error, returning the inverter to the Stop Mode. In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter lets the motor free-run to a stop, and the alarm output turns ON immediately. When the operator initiates a Reset command, the alarm and error are cleared. When the Reset is turned OFF, the motor begins rotation since the Run command is already active. [EXT] terminal Motor revolution speed [RS] terminal Alarm output terminal RUN command [FW, RV]

1 0 1 0 1 0 1 0 1 0 free run t

Option Code

Terminal Symbol

12

EXT

Function Name External Trip

Input State

Description

ON

When assigned input transitions OFF to ON, inverter latches trip event and displays E12

OFF

No trip event for ON to OFF, any recorded trip events remain in history until Reset

C_01, C_02, C_03, C_04, C_05

Required settings:

(none)

Notes: • If the USP (Unattended Start Protection) feature is

Example (requires input configuration - see page 3–32): EXT

L 5 4 3 2 1 P24 in use, the inverter will not automatically restart after cancelling the EXT trip event. In that case, it must receive either another Run command (OFFto-ON transition), a keypad Reset command, or an [RS] intelligent terminal input signal. See I/O specs on page 4–6.

Operations and Monitoring

Valid for inputs:

Page 127

4–16

Using Intelligent Input Terminals

Unattended Start Protection If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that automatic startup, so that the inverter will not run without outside intervention. When USP is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key. In the figure below, the [UPS] feature is enabled. When the inverter power turns ON, the motor does not start, even though the Run command is already active. Instead, it enters the USP trip state, and displays E13 error code. This requires outside intervention to reset the alarm by turning OFF the Run command per this example (or applying a reset). Then the Run command can turn ON again and start the inverter output.

Operations and Monitoring

1 RUN command [FW, RV] 0 1 [USP] terminal 0 1 Alarm output terminal 0 1 Inverter output frequency 0 1 Inverter power supply 0 Events: Alarm E13 display Option Code

Terminal Symbol

13

USP

Function Name Unattended Start Protection

Input State

Alarm cleared

Run command t

Description

ON

On powerup, the inverter will not resume a Run command (mostly used in the US)

OFF

On powerup, the inverter will resume a Run command that was active before power loss

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

(none)

Notes: • Note that when a USP error occurs and it is canceled by a reset from a [RS] terminal input, the inverter restarts running immediately. • Even when the trip state is canceled by turning the terminal [RS] ON and OFF after an under voltage protection E09 occurs, the USP function will be performed. • When the running command is active immediately after the power is turned ON, a USP error will occur. When this function is used, wait for at least three (3) seconds after the powerup to generate a Run command.

Example (default input configuration shown for –FU models; –FE and –FR models require input configuration - see page 3–32): USP

L 5 4 3 2 1 P24

See I/O specs on page 4–6.

Page 128

L100 Inverter

4–17

Software Lock When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequency, depending on the setting of B_31) is locked (prohibited from editing). When the data is locked, the keypad keys cannot edit inverter parameters. To edit parameters again, turn OFF the [SFT] terminal input. Use parameter B_31 to select whether the output frequency is excluded from the lock state or is locked as well. Option Code

Terminal Symbol

15

SFT

Function Name Software Lock

Input State

Description

ON

The keypad and remote programming devices are prevented from changing parameters

OFF

The parameters may be edited and stored

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

B_31 (excluded from lock)

Notes: • When the [SFT] terminal is turned ON, only the

Example (requires input configuration - see page 3–32): SFT

L 5 4 3 2 1 P24 output frequency can be changed.

• Software lock can include the output frequency by setting B_31. • Software lock by the operator is also possible without the [SFT] terminal being used (B_31).

See I/O specs on page 4–6.

Operations and Monitoring

Page 129

4–18

Using Intelligent Input Terminals

Analog Input Current/Voltage Select The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input terminals for external frequency control. When intelligent input [AT] is ON, you can set the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency. Note that you must also set parameter A_01 = 01 to enable the analog terminal set for controlling the inverter frequency. Option Code

Terminal Symbol

16

AT

Function Name Analog Input Voltage/current Select

Input State

Description

ON

Terminal OI is enabled for current input (uses terminal L for power supply return)

OFF

Terminal O is enabled for voltage input (uses terminal L for power supply return)

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

A_01 = 01

Example (default input configuration shown for –FU models; –FE and –FR models require input configuration - see page 3–32):

Notes: • If the [AT] option is not assigned to any intelligent

Operations and Monitoring input terminal, then inverter uses the algebraic sum of both the voltage and current inputs for the frequency command (and A_01=01). • When using either the analog current and voltage input terminal, make sure that the [AT] function is allocated to an intelligent input terminal. • Be sure to set the frequency source setting A_01=01 to select the analog input terminals.

AT

L 5 4 3 2 1 P24

H O OI L FM CM2 12 11 4-20 mA when AT= ON +–

0-10 V when AT= OFF

See I/O specs on page 4–6.