Page 130

L100 Inverter

4–19

Reset Inverter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. [RS] When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The Alarm minimum pulse width for [RS] must be 12 ms signal or greater. The alarm output will be cleared within 30 ms after the onset of the Reset command.

12 ms minimum

1 0 approx. 30 ms 1 0 t

WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.

Option Code

Terminal Symbol

18

RS

Function Name Reset Inverter

Input State

Description

ON

The motor output is turned OFF, the Trip Mode is cleared (if it exists), and powerup reset is applied

OFF

Normal power-ON operation

Valid for inputs:

C_01, C_02, C_03, C_04, C_05

Required settings:

(none)

Notes: • When the control terminal [RS] input is already ON

RS

L 5 4 3 2 1 P24

See I/O specs on page 4–6.

• Pressing the Stop/Reset key of the digital operator can generate a reset operation only when an alarm occurs.

• A terminal configured with the [RS] function can only be configured for normally open operation. The terminal cannot be used in the normally closed contact state. • When input power is turned ON, the inverter performs the same reset operation as it does when a pulse on the [RS] terminal occurs. • The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a hand-held remote operator is connected to the inverter. • If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).

Operations and Monitoring at powerup for more than 4 seconds, the remote operator display is “R-ERROR COMM<2>” (the display of the digital operator [OPE-J] is – – –. However, the inverter has no error. To clear the digital operator error, turn OFF the terminal [RS] input and press one of the operator keys.

Example (default input configuration shown - see page 3–32):

Page 131

4–20

Using Intelligent Input Terminals

Thermistor Thermal Protection Motors that are equipped with a thermistor can be protected from overheating. Input terminal [5] has the unique ability to sense a thermistor resistance. When the resistance value of the thermistor connected to terminal [TH] (5) and [L] is more than 3 k Ohms ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the trip status E35. Use this function to protect the motor from overheating. Option Code

Terminal Symbol

19

TH

Function Name Thermistor Thermal Protection

Input State

Sensor When a thermistor is connected to terminals [5] and [L], the inverter checks for over-temperature and will cause trip (E35) and turn OFF the output to the motor Open

Valid for inputs:

C_05 only

Required settings:

(none)

Description

Notes: • Be sure the thermistor is connected to terminals [5] and [L]. If the resistance is above the threshold the inverter will trip. When the motor cools down enough, the thermistor resistance will change enough to permit you to clear the error. Press the STOP/Reset key to clear the error.

An open circuit in the thermistor causes a trip, and the inverter turns OFF the output Example (requires input configuration - see page 3–32): TH

L 5 4 3 2 1 P24 thermistor

MOTOR

Operations and Monitoring

See I/O specs on page 4–6.

Page 132

4–21

L100 Inverter

Using Intelligent Output Terminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The inverter has several output functions that you can assign individually to three physical logic outputs. Two of the outputs are open-collector transistors, and the third output is the alarm relay (form C – normally open and normally closed contacts). The relay is assigned the alarm function by default, but you can assign it to any of the functions that the open-collector outputs use.

Sinking Outputs, Open Collector The open-collector transistor outputs can handle up to 50mA each. We highly recommend that you use an external power source as shown. It must be capable of providing at least 100mA to drive both outputs at full load. To drive loads that require more than 50mA, use external relay circuits as shown below.

L100 Inverter Open collector outputs

Logic output common

CM2

12

11

– + Load Load

If you need output current greater than 50mA, use the inverter output to drive a small relay. Be sure to use a diode across the coil of the relay as shown (reversebiased) in order to suppress the turn-off spike, or use a solid-state relay.

L100 Inverter Open collector outputs

Logic output common

CM2

12

11

– + RY RY

Operations and Monitoring

Sinking Outputs, Open Collector with External Relays

Page 133

4–22

Using Intelligent Output Terminals

Run Signal When the [RUN] signal is selected as an intelligent output terminal, the inverter outputs a signal on that terminal when it is in Run Mode. The output logic is active low, and is the open collector type (switch to ground).

[FW], 1 [RV] 0 B 82 Output freq.

start freq.

Run 1 Signal 0

ON t

Option Code

Terminal Symbol

00

RUN

Function Name Run Signal

Valid for outputs:

11, 12

Required settings:

(none)

Output State

Description

ON when inverter is in Run Mode

OFF when inverter is in Stop Mode

Notes: • The inverter outputs the [RUN] signal whenever the inverter output exceeds the start frequency specified by parameter B_82. The start frequency is the initial inverter output frequency when it turns ON.

Example (default output configuration shown - see page 3–36): RUN

Inverter output terminal circuit

H O OI L FM CM2 12 11 + –

RY

Operations and Monitoring

See I/O specs on page 4–6.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Page 134

L100 Inverter

4–23

Frequency Arrival Signals The Frequency Arrival group of outputs help coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F_01). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility. For example, you can have an output turn ON at one frequency during acceleration, and have it turn OFF at a different frequency during deceleration. All transitions have hysteresis to avoid output chatter if the output frequency is near one of the thresholds. Option Code

Terminal Symbol

01

FA1

02

FA2

Function Name Frequency Arrival Type 1 – Constant Speed Frequency Arrival Type 2 – Overfrequency

Valid for outputs:

11, 12

Required settings:

(none)

Output State

Description

ON when output to motor is at the set frequency

OFF when output to motor is OFF, or in any acceleration or deceleration ramp

ON when output to motor is at or above the set frequency thresholds for, even if in acceleration or deceleration ramps

OFF when output to motor is OFF, or during acceleration or deceleration before the respective thresholds are crossed

Notes: • For most applications you will need to use only one

Inverter output terminal circuit

FA1

H O OI L FM CM2 12 11

See I/O specs on page 4–6.

+ –

RY

Operations and Monitoring type of frequency arrival outputs (see examples). However, it is possible assign both output terminals to output functions [FA1] and [FA2]. • For each frequency arrival threshold, the output anticipates the threshold (turns ON early) by 1.5Hz. • The output turns OFF as the output frequency moves away from the threshold, delayed by 0.5Hz. • The delay time of the output signal is 60 ms (nominal).

Example (default output configuration shown - see page 3–36):

Page 135

4–24

Using Intelligent Output Terminals

Operations and Monitoring

Frequency arrival output [FA1] uses the Output standard output frequency (parameter freq. F_01) as the threshold for switching. In the figure to the right, Frequency Arrival [FA1] turns ON when the output frequency gets within 0.5 Hz below or 1.5 Hz above the target constant 0 frequency. This provides hysteresis that prevents output chatter near the threshold FA1 value.The hysteresis effect causes the signal output to turn ON slightly early as the speed approaches the threshold. Then the turn-OFF point is slightly delayed. The timing is further modified by a small 60 ms delay. Note the active low nature of the signal, due to the open collector output.

0.5 Hz

Frequency arrival output [FA2] works the Output same way; it just uses two separate freq. Thresholds thresholds as shown in the figure to the right. These provide for separate acceler- C 42 accel. ation and deceleration thresholds to C 43 decel. provide more flexibility than for [FA1]. 0 [FA2] uses C_42 during acceleration for the ON threshold, and C_43 during decelFA2 eration for the OFF threshold. This signal signal also is active low and has a 60 ms delay after the frequency thresholds are crossed. Having different accel and decel thresholds provides an asymmetrical output function. However, you can use equal ON and OFF thresholds, if desired.

F 01

1.5 Hz

F 01 1.5 Hz

0.5 Hz t ON

ON t 60 ms

60 ms

0.5 Hz

1.5 Hz t ON

60 ms

60 ms

Page 136

L100 Inverter

4–25

Overload Advance Notice Signal When the output current exceeds a preset value, the [OL] terminal signal turns ON. The parameter C_41 sets the overload threshold. The overload detection circuit operates during powered motor operation and during regenerative braking. The output circuits use open-collector transistors, and are active low.

Current threshold

C 41 power running

C 41 regeneration threshold

[OL] 1 Signal 0

ON

ON t Option Code

Terminal Symbol

03

OL

Function Name Overload Advance Notice Signal

Valid for outputs:

11, 12

Required settings:

C_41

Output State

Description

ON when output current is more than the set threshold for the overload signal

OFF when output current is less than the set threshold for the overload signal

Notes: • The default value is 100%. To change the level

Example (requires output configuration - see page 3–36): OL

Inverter output terminal circuit from the default, set C_41 (overload level).

• The accuracy of this function is the same as the function of the output current monitor on the [FM] terminal (see page “Analog and Digital Monitor Output” on page 4–30).

H O OI L FM CM2 12 11 + –

RY

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Operations and Monitoring

See I/O specs on page 4–6.

Page 137

4–26

Using Intelligent Output Terminals

Output Deviation for PID Control The PID loop error is defined as the magnitude (absolute value) of the difference between the Setpoint (target value) and the Process Variable (actual value). When the error magnitude exceeds the preset value for C_44, the [OD] terminal signal turns ON. Refer to “PID Loop Operation” on page 4–32.

SP, PV

Process variable

C 44

Setpoint

C 44

[OD] 1 Signal 0

ON

ON t Option Code

Terminal Symbol

04

OD

Function Name

Output State

Output Deviation for PID Control

Valid for outputs:

11, 12

Required settings:

C_44

ON when PID error is more than the set threshold for the deviation signal

OFF when PID error is less than the set threshold for the deviation signal

Notes: • The default difference value is set to 3%. To change this value, change parameter C_44 (deviation level).

Description

Example (requires output configuration - see page 3–36): OD

Inverter output terminal circuit

H O OI L FM CM2 12 11

Operations and Monitoring

+ –

RY

See I/O specs on page 4–6.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Page 138

4–27

L100 Inverter

Alarm Signal The inverter alarm signal is active when a fault has occurred and it is in the Trip Mode (refer to the diagram at right). When the fault is cleared the alarm signal becomes inactive.

STOP

RESET

Run

Stop RUN STOP

RESET We must make a distinction between the alarm Fault Trip Fault signal AL and the alarm relay contacts [AL0], [AL1] and [AL2]. The signal AL is a logic function, which you can assign to the open collecAlarm signal active tor output terminals [11] or [12]. The relay is dedicated to the function AL, thus the labeling of its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic signal interface or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum).

Option Code

Terminal Symbol

05

AL

Function Name Alarm Signal

Valid for outputs:

11, 12

Required settings:

C_33

Output State

Description

ON when an alarm signal has occurred and has not been cleared

OFF when no alarm has occurred since the last clearing of alarm(s)

Notes: • When the alarm output is set to normally closed, a

AL

Inverter output terminal circuit

H O OI L FM CM2 12 11 + –

RY

Example for terminals [AL0], [AL1], [AL2] (default output configuration shown - see page 3–36): Inverter logic circuit board Relay position shown is during normal running (no alarm).

See I/O specs on page 4–6.

AL

AL0 AL1 AL2 Power supply

Load

Operations and Monitoring time delay of less than 2 seconds occurs until the contact is closed when the power is turned ON. • Terminals 11 and 12 are open collector outputs, so the electric specifications of [AL] are different from the contact output terminals [AL0], [AL1], [AL2]. • When the inverter power supply is turned OFF, the alarm signal output is valid as long as the external control circuit has power. • This signal output has the delay time (300 ms nominal) from the fault alarm output. • The relay contact specifications are in “Specifications of Control and Logic Connections” on page 4–6. The contact diagrams for different conditions are on the next page.

Example for terminal [11] or [12] (requires output configuration - see page 3–36):