L100 Series Inverter Instruction Manual: Operations and Monitoring, pages 139 to 144

Pages 139 to 144 of 193, from L100 Series Inverter Instruction Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi L100-040HFU

Page 139

4–28

Using Intelligent Output Terminals The alarm output terminals are connected as shown below (left) by default. The contact logic can be inverted as shown (below right) by using the parameter setting C_33. The relay contacts normally open (N.O.) and normally closed (N.O.) convention uses “normal” to mean the inverter has power and is in Run or Stop Mode. The relay contacts switch to the opposite position when it is in Trip Mode or when input power is OFF. N.C. contacts (after initialization)

During normal running

When an alarm occurs or power is turned OFF

AL0 AL1 AL2

Operations and Monitoring

N.O. contact (inverted by C_33 setting)

AL0 AL1 AL2

During normal running or power is turned OFF

When an alarm occurs

AL0 AL1 AL2

Contact

Power

Run State

AL0AL1

AL0AL2

N.C. (after initialize, C_33=01)

ON

Normal Closed

Open

ON

Trip

Open

Closed

OFF, Open

Closed

AL0 AL1 AL2

Contact

Power

Run State

AL0AL1

AL0AL2

N.O. (set C_33=00)

ON

Normal

Open

Closed

ON

Trip

Closed

Open

OFF, Open

Closed

Page 140

L100 Inverter

4–29

Analog Input Operation The L100 inverters provide for analog input H O OI L FM CM2 12 11 to command the inverter frequency output +V Ref. value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals Voltage input on the control connector, which provide for Current input Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L]. A GND If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type. If terminal [AT] is OFF, the voltage input [O] can command the inverter output frequency. If terminal [AT] is ON, the current input [OI] can command the inverter output frequency. The [AT] terminal function is covered in “Analog Input Current/Voltage Select” on page 4–18. Remember that you must also set A_01 = 01 to select analog input as the frequency source.

V/I input select [AT]

A 01 Frequency setting

H O OI L FM CM2 12 11 4-20 mA, AT= ON +–

0-10 V, AT= OFF

NOTE: If no logic input terminal is configured for the [AT] function, then inverter sums the voltage and current input to determine the desired input value.

Voltage Input – The voltage input circuit uses terminals [L] and [O]. Attach the signal cable’s shield wire only to terminal [L] on the inverter. Maintain the voltage within specifications (do not apply negative voltage).

H O OI L FM CM2 12 11 0 to 9.6 VDC, 0 to 10V nominal +–

Current Input – The current input circuit H O OI L FM CM2 12 11 uses terminals [OI] and [L]. The current comes from a sourcing type transmitter; a 4 to 19.6 mA DC, sinking type will not work! This means the 4 to 20 mA nominal current must flow into terminal [OI], and terminal [L] is the return back to the transmit- See I/O specs on page 4–6. ter. The input impedance from [OI] to [L] is 250 Ohms. Attach the cable shield wire only to terminal [L] on the inverter.

Operations and Monitoring

Using an external potentiometer is a common H O OI L FM CM2 12 11 way to control the inverter output frequency (and a good way to learn how to use the analog inputs). The potentiometer uses the built-in 10V reference [H] and the analog ground [L] for excitation, and the voltage 1 to 2kΩ, 2W input [O] for the signal. By default, the [AT] terminal selects the voltage input when it is OFF. Take care to use the proper resistance for the potentiometer, which is 1 to 2 k Ohms, 2 Watts.

Page 141

4–30

Analog and Digital Monitor Output

Analog and Digital Monitor Output In the system design for inverter applications it is useful to monitor the inverter operation from a remote location. In some cases, this requires only a panel-mounted analog meter (moving-coil type). In other cases, a controller device such as a PLC may command the inverter frequency and other functions. Sometimes it is useful to have the inverter transmit the (real-time) output frequency value back to the controller to confirm actual operation. The monitor output function [FM] serves these purposes. The inverter provides an analog/digital output H O OI L FM CM2 12 11 primarily for frequency monitoring on terminal [FM] (frequency monitor). It uses terminal [L] as A GND analog GND reference. You can configure Analog/digital Output terminal [FM] to transmit the inverter current output or frequency output in pulse-width See I/O specs on page 4–6. modulated format (PWM). You can also configure terminal [FM] to output the frequency value in a frequency-modulated (FM) format. The following table lists terminal [FM] configurations. Use function C_23 to configure. Func.

Code

Description

00 C_23

Waveform

Full Scale value

Output frequency

PWM

0 – Max. frequency (Hz)

01

Output current

PWM

0 – 200%

02

Output frequency

FM

0 – Max. frequency (Hz)

Operations and Monitoring

PWM Signal Type The pulse-width modulated signal at terminal [FM] is primarily designed for driving a movingcoil meter. The PWM signal is automatically averaged by the inertia of the moving-coil mechanism - converting the PWM signal to an analog representation. Be sure to use a 10V full-scale DC voltmeter.

H O OI L FM CM2 12 11 –

+

0 to 10V, 1 mA

The signal characteristics of terminal [FM] in PWM configuration is shown below: Pulse-width modulation (analog) [FM] t

[FM] Output = --tT C_23 = 00 Inverter output frequency

10V

C_23 = 01 Inverter output current 0V T

T = 4 ms t

B 81 PWM scale factor

To calibrate the meter reading, generate a full-scale output (always ON) at terminal [FM]. Then use parameter B_81(gain setting from 0 to 255) to adjust the corresponding full-scale reading of the meter. For example, when the inverter output frequency is 60 Hz, change the value of B_81 so that the meter reads 60 Hz.

Page 142

L100 Inverter

4–31

TIP: When using the analog meter for monitoring, adjust the meter so it has a zero reading when the [FM] output is zero. Then use scale factor B_81 to adjust the [FM] output so the maximum frequency in the inverter corresponds to a full-scale reading on the meter. The following accuracy notes apply for PWM monitor outputs: • The monitor accuracy for frequency monitoring after adjustment is about ±5%. Depending on the motor, the accuracy may exceed this value. • The monitor display accuracy for current (normally ± 20%, depending on the connected motor’s characteristics) can be improved by adjusting parameter B_32. • The accuracy of the current reading is given by the equation: Imc – Im --------------------× 100 ≤ ± 20% Ir

Im = Inverter output current (measured) Imc = Monitor display current Ir = Inverter rated current

• If precise current measurement is necessary, use the moving-coil type ammeter between the inverter and the motor.

FM Signal Type The frequency-modulated output at terminal [FM] varies its frequency with the inverter output frequency (C_23=02). The multiplier is 10, such that the maximum [FM] signal frequency is 10 x 360 = 3.6 kHz, or 10 times the inverter’s maximum output frequency. The signal at [FM] uses the parameter A_04 Maximum frequency setting. For example, if A_04 = 60 Hz, then the maximum signal value at [FM] will be 10 x 60 = 600 Hz. This frequency is digitally controlled for accuracy, and does not use the B_81 gain setting when C_23=02 (frequency modulation selection). [FM]

50% fixed duty cycle

10V

1 [FM] Output value = --------------T × 10

0V

C_23 = 02 Selects FM type output T t

1 T = -------------------------------------------------------[FM] Output value × 10

Operations and Monitoring

PWM Smoothing Circuit – You may also wish to smooth the PWM signal at the [FM] H O OI L FM CM2 12 11 – + terminal and convert it to an analog signal. The [FM] terminal will then generate a relatively stable DC analog voltage that 82kΩ + represents the output value. To do this, use + the circuit shown to the right. Note the 33kΩ 1µF Volts output impedance of the circuit is at least – 82kΩ, so the monitoring device needs an input impedance of 1MΩ or greater. Other- See I/O specs on page 4–6. wise, the impedance of the smoothing circuit will cause a non-linearity in the reading.

Page 143

4–32

PID Loop Operation

PID Loop Operation In standard operation, the inverter uses a reference source selected by parameter A_01 for the output frequency, which may be a fixed value (F_01), a variable set by the front panel potentiometer, or value from an analog input (voltage or current). To enable PID operation, set A_71 = 01. This causes the inverter to calculate the target frequency, or setpoint. A calculated target frequency can have a lot of advantages. It lets the inverter adjust the motor speed to optimize some other process of interest, potentially saving energy as well. Refer to the figure below. The motor acts upon the external process. To control that external process, the inverter must monitor the process variable. This requires wiring a sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).

Setpoint SP

∑

Error

PID Freq. Inverter Calculation

Motor

External Process

PV Process Variable (PV)

Sensor

When enabled, the PID loop calculates the ideal output frequency to minimize the loop error. This means we no longer command the inverter to run at a particular frequency, but we specify the ideal value for the process variable. That ideal value is called the setpoint, and is specified in the units of the external process variable. For a pump application it may be gallons/minute, or it could be air velocity or temperature for an HVAC unit. Parameter A_75 is a scale factor that relates the external process variable units to motor frequency. The figure below is a more detailed diagram of the PID function. Standard setting

Operations and Monitoring

F 01 Multi-speed settings

Setpoint (Target) Scale factor reciprocal 1

Scale factor

A 75

F 01

Frequency source select

A 01

A 75

P gain

A 20 to A 35

A 72

Potentiometer on keypad

Error SP

V/I input select [AT]

∑

I gain

A 73

∑

Frequency setting

PV Process Variable (Feedback)

Voltage

D gain

A 74

Analog input scaling

O A GND L

A 12

Scale factor

Monitor

A 11

A 75

D 04

A 15 A 13 A 14 OI Current

A 76

PID V/I input select

Page 144

L100 Inverter

4–33

Configuring the Inverter for Multiple Motors Simultaneous Connections For some applications, you may need to connect two or more motors (wired in parallel) to a single inverter’s output. For example, this is common in conveyor applications where two separate conveyors need to have approximately the same speed. The use of two motors may be less expensive than making the mechanical link for one motor to drive multiple conveyors. Some of the characteristics of using multiple motors with one drive are: • The inverter output must be rated to handle the sum of the currents from the motors. • You must use separate thermal protection switches or devices to protect each motor. Locate the device for each motor inside the motor housing or as close to it as possible.

L100

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

Motor 1

Motor 2 to Nth motor

• The wiring for the motors must be permanently connected in parallel (do not remove one motor from the circuit during operation). NOTE: The motor speeds are identical only in theory. That is because slight differences in their loads will cause one motor to slip a little more than another, even if the motors are identical. Therefore, do not use this technique for multi-axis machinery that must maintain a fixed position reference between its axes.

Operations and Monitoring