The text of a manual · part 12 of 23
L100 Series Inverter Instruction Manual: Configuring Drive Parameters, pages 102 to 111
Pages 102 to 111 of 193, from L100 Series Inverter Instruction Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi L100-040HFU
Page 102
L100 Inverter
“B” Function Func. Code
Name / SRW Display
Description
B_88 Restart mode after FRS RUN FRS
Selects how the inverter resumes operation when the ZST free-run stop (FRS) is cancelled, two options: 00... Restart from 0Hz 01... Restart from frequency detected from real speed of motor (frequency matching)
B_89 Data select for digital operator OPE-J PANEL d01
Defaults –FU (UL)
–FR Units (Jpn)
✘
00
00
00, ✔
01
01
01, Configuring Drive Parameters
Select the monitoring data to send to the optional remote hand-held digital operator, seven option codes: 01... Output frequency (D_01) 02... Output current (D_02) 03... Motor direction (D_03) 04... PID PV feedback (D_04) 05... Input states for input terminals (D_05) 06... Output states for output terminals (D_06) 07... Scaled output frequency (D_07)
Run Mode –FE Edit (CE)
3–31
Page 103
3–32
“C” Group: Intelligent Terminal Functions
“C” Group: Intelligent Terminal Functions The five input terminals [1], [2], [3], [4], and [5] can be configured for any of fifteen different functions. The next two tables show how to configure the five terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1. The inverter comes with default options for the five terminals. These default settings are initially unique, each one having its own setting. Note that European and US versions have different default settings. You can use any option on any terminal, and even use the same option twice to create a logical OR (though usually not required). NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a thermistor device when the PTC function (option code 19) is assigned to that terminal.
Configuring Drive Parameters
Input Terminal Configuration Functions and Options –The function codes in the following table let you assign one of fifteen options to any of the five logic inputs for the L100 inverters. The functions C_01through C_05 configure the terminals [1] through [5] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options. For example, if you set function C_01=00, you have assigned option 00 (Forward Run) to terminal [1]. The option codes and the specifics of how each one works are in Chapter 4. “C” Function Func. Code
Name / SRW Display
Description
C_01 Terminal [1] function IN-TM 1
FW
C_02 Terminal [2] function IN-TM 2
RV
C_03 Terminal [3] function IN-TM 3
AT
C_04 Terminal [4] function IN-TM 4
USP
C_05 Terminal [5] function IN-TM 5
2CH
Run Mode Edit
Defaults –FE (CE)
–FU (UL)
–FR Units (Jpn)
Select terminal [1] function, 15 options (see next section)
✘
00 [FW]
00 [FW]
00 [FW], Select terminal [2] function, 15 options (see next section)
✘
01 [RV]
01 [RV]
01 [RV], Select terminal [3] function, 15 options (see next section)
✘
02 [CF1]
16 [AT]
02 [CF1], Select terminal [4] function, 15 options (see next section)
✘
03 [CF2]
13 [USP]
03 [CF2], Select terminal [5] function, 16 options (see next section)
✘
18 [RS]
18 [RS]
18 [RS]
Page 104
L100 Inverter
3–33
The input logic convention is programmable for each of the five inputs. Most inputs default to normally open (active high), but you can select normally closed (active low) in order to invert the sense of the logic. “C” Function
Defaults –FE (CE)
–FU (UL)
–FR Units (Jpn)
C_11 Terminal [1] active state Select logic convention, two option codes: IN-TM O/C-1 NO 00 ...normally open [NO] 01 ...normally closed [NC]
✘
00
00
00, C_12 Terminal [2] active state Select logic convention, two option codes: IN-TM O/C-2 NO 00 ...normally open [NO] 01 ...normally closed [NC]
✘
00
00
00, C_13 Terminal [3] active state Select logic convention, two option codes: IN-TM O/C-3 NO 00 ...normally open [NO] 01 ...normally closed [NC]
✘
00
00
00, C_14 Terminal [4] active state Select logic convention, two option codes: IN-TM O/C-4 NC 00 ...normally open [NO] 01 ...normally closed [NC]
✘
00
01
00, C_15 Terminal [5] active state Select logic convention, two option codes: IN-TM O/C-5 NO 00 ...normally open [NO] 01 ...normally closed [NC]
✘
00
00
00, Func. Code
Name / SRW Display
Description
NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.
Intelligent Input Terminal Overview Each of the five intelligent terminals may be assigned any of the options in the following table. When you program one of the option codes for terminal assignments C_01 to C_05, the respective terminal assumes the function role of that option code. The terminal functions have a symbol or abbreviation that we use to label a terminal using that function. For example the “Forward Run” command is [FW]. The physical label on the terminal block connector is simply 1, 2, 3, 4, or 5. However, schematic examples in this manual also use the terminal symbol (such as [FW]) to show the assigned option. The option codes for C_11 to C_15 determines the active state of the logical input (active high or active low).
Configuring Drive Parameters
Run Mode Edit
Page 105
3–34
“C” Group: Intelligent Terminal Functions Input Function Summary Table – This table shows all fifteen intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4–8. Input Function Summary Table
Option Code
Terminal Symbol
Function Name
00
FW
Forward Run/Stop
01
02
03
Configuring Drive Parameters
04
05
06
09
11
12
13
RV
CF1 *1
CF2
CF3
CF4
JG
2CH
FRS
EXT
USP
Description ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
Multi-speed Select, Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
Multi-speed Select, Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
Multi-speed Select, Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
Multi-speed Select, Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
Jogging
ON
Inverter is in Run Mode, output to motor runs at jog parameter frequency
OFF
Inverter is in Stop Mode
ON
Frequency output uses 2nd-stage acceleration and deceleration values
OFF
Frequency output uses standard acceleration and deceleration values
ON
Causes output to turn OFF, allowing motor to free run (coast) to stop
OFF
Output operates normally, so controlled deceleration stops motor
ON
When assigned input transitions OFF to ON, inverter latches trip event and displays E12
OFF
No trip event for ON to OFF, any recorded trip events remain in history until Reset
ON
On powerup, the inverter will not resume a Run command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run command that was active before power loss
Reverse Run/Stop
2-stage Acceleration and Deceleration
Free-run Stop
External Trip
Unattended Start Protection
Page 106
L100 Inverter
3–35
Input Function Summary Table Option Code
Terminal Symbol
15
SFT
16
18
19
AT
RS
PTC
Software Lock
Description ON
The keypad and remote programming devices are prevented from changing parameters
OFF
The parameters may be edited and stored
Analog Input Voltage/current Select
ON
Terminal [OI] is enabled for current input (uses terminal L for power supply return)
OFF
Terminal [O] is enabled for voltage input (uses terminal [L] for power supply return)
Reset Inverter
ON
The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
ANLG
When a thermistor is connected to terminals [5] and [L], the inverter checks for overtemperature and will cause trip event and turn OFF output to motor
OPEN
A disconnect of the thermistor causes a trip event, and the inverter turns OFF the motor
PTC Thermistor Thermal Protection
When using the Multi-speed Select settings CF1 to CF4, do not display parameter F_01 or change the value of F_01 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F_01 during Run Mode, please monitor D_01 instead of F_01.
Configuring Drive Parameters
Note 1:
Function Name
Page 107
3–36
“C” Group: Intelligent Terminal Functions
Output Terminal Configuration The inverter provides configuration for logic (discrete) and analog outputs, shown in the table below. “C” Function Func. Code
Name / SRW Display
Description
C_21 Terminal [11] function OUT-TM 1
FA1
C_22 Terminal [12] function OUT-TM 2
RUN
C_23 [FM] signal selection MONITOR
A-F
Run Mode Edit
Defaults –FE (CE)
–FU (UL)
–FR Units (Jpn)
01 [FA1]
Select terminal [11] function, 6 options (see next section)
✘
01 [FA1]
01 [FA1], Select terminal [12] function, 6 options (see next section)
✘
00 00 00 [RUN] [RUN] [RUN], Select terminal [FM] function, 3 options (see next section)
✘
00 [A–F], 00 [A–F]
00 [A–F]
Configuring Drive Parameters
The output logic convention is programmable for terminals [11] and [12]. The opencollector output terminals [11] and [12] default to normally open (active low), but you can select normally closed (active high) for these terminals in order to invert the sense of the logic. You can invert the logical sense of the alarm relay output as well. “C” Function Func. Code
Name / SRW Display
OUT-TM O/C-1
–FE (CE)
–FU (UL)
–FR Units (Jpn)
Select logic convention, two option codes: 00 ...normally open [NO] 01 ...normally closed [NC]
✘, 00, - (reserved) DO NOT EDIT
✘
00, 00, Select logic convention, two option codes: 00 ...normally open [NO] 01 ...normally closed [NC]
✘, 00, - (reserved) DO NOT EDIT
✘
00, 00, ✘
01
01
01, Description
C_31 Terminal [11] active state (–FU) NO
Reserved (–FE / –FR)
Defaults
Run Mode Edit
(not displayed) C_32 Terminal [12] active state (–FU) OUT-TM O/C-2
NO
Terminal [11] active state (–FE / –FR) OUT-TM O/C-1
NO
C_33 Alarm relay active state Select logic convention, two option codes: OUT-TM O/C-RY NO 00 ...normally open [NO] 01 ...normally closed [NC]
Page 108
L100 Inverter
3–37
Output Function Summary Table – This table shows all six functions for the logical outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4–21. Output Function Summary Table Option Code
Terminal Symbol
00
RUN
01
02
03
05
FA2
OL
OD
AL
Run Signal
ON when inverter is in Run Mode
OFF when inverter is in Stop Mode
Frequency Arrival Type 1 – Constant Speed
ON when output to motor is at the set frequency
OFF when output to motor is OFF, or in any acceleration or deceleration ramp
Frequency Arrival Type 2 – Overfrequency
ON when output to motor is at or above the set frequency, even if in accel. or decel. ramps
OFF when output to motor is OFF, or at a level below the set frequency
Overload Advance Notice Signal
ON when output current is more than the set threshold for the overload signal
OFF when output current is less than the set threshold for the overload signal
Output Deviation for ON PID Control when PID error is more than the set threshold for the deviation signal
OFF when PID error is less than the set threshold for the deviation signal
ON when an alarm signal has occurred and has not been cleared
OFF when no alarm has occurred since the last clearing of alarm(s)
Alarm Signal
Configuring Drive Parameters
04
FA1
Description
Function Name
Page 109
3–38
“C” Group: Intelligent Terminal Functions Analog Function Summary Table – This table shows all three functions for the analog output [FM] (frequency meter) terminal. Detailed descriptions, related parameters and settings, and example wiring diagrams are in “Analog and Digital Monitor Output” on page 4–30. Analog Function Summary Table
Configuring Drive Parameters
Option Code
Function Name
Description
00
Analog Frequency Monitor
PWM (pulse-width-modulated) voltage output that has a duty cycle proportional to the inverter output frequency
01
Analog Current Output Monitor
PWM (pulse-width-modulated) voltage output that has a duty cycle proportional to the inverter output current to the motor. It reaches 100% duty cycle when the output reaches 200% of the rated inverter current.
02
Digital Frequency Output Monitor
FM (frequency-modulated) voltage output with a constant 50% duty cycle. Its frequency = inverter output frequency.
Page 110
L100 Inverter
3–39
Output Function Adjustment Parameters The following parameters work in Motor current conjunction with the intelligent output C 41 function, when configured. The overload level parameter (C_41) sets the motor 0 current level at which the overload signal [OL] turns ON. The range of settings is Overload signal 1 from 0% to 200% of the rated current for 0 the inverter. This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).
t t
The frequency arrival signal, [FA1] or Output frequency [FA2], is intended to indicate when the C 42 inverter output has reached (arrived at) the target frequency. You can adjust the timing 0 of the leading and trailing edges of the Arrival signal via two parameters specific to accelsignal 1 eration and deceleration ramps, C_42 and 0 C_43.
C 43 t
The Error for the PID loop is the magnitude (absolute value) of the difference between the Setpoint (desired value) and Process Variable (actual value). The PID output deviation signal [OD] (output terminal function option code 04) indicates when the error magnitude has exceeded a magnitude you define.
PID Error (PV–SP) deviation threshold PV Output SP C 44
0 t Deviation signal 1 0 t
“C” Function Func. Code
Name / SRW Display
Description
C_41 Overload level setting OV Load
Sets the overload signal level between 0% and 200% (from 0 03.00A to two times the rated current of the inverter)
C_42 Frequency arrival setting for acceleration ARV ACC
000.0Hz
Sets the frequency arrival setting threshold for the output frequency during acceleration
Run Mode Edit
Defaults –FE (CE)
–FU (UL)
–FR Units (Jpn)
✘
Rated current for each inverter, ✘
0.0
Hz
0.0
0.0
Configuring Drive Parameters t
Page 111
3–40
“C” Group: Intelligent Terminal Functions
“C” Function Func. Code
Name / SRW Display
C_43 Arrival frequency setting for deceleration ARV DEC
000.0Hz
C_44 PID deviation level setting OV PID
003.0%
C_91 Debug mode selection
Configuring Drive Parameters
INIT DEBG
OFF
Defaults
Run Mode Edit
–FE (CE)
–FU (UL)
–FR Units (Jpn)
Sets the frequency arrival setting threshold for the output frequency during deceleration
✘
0.0
0.0
0.0
Hz
Sets the allowable PID loop error magnitude (absolute value), SP - PV, range is 0.0 to 100%, resolution is 0.1%
✘
3.0
3.0
3.0
%
(Reserved) DO NOT EDIT
✘
00
00
00, Description