Page 92

L100 Inverter

3–21

Accel/Decel Standard acceleration and deceleration is linear. The inverter CPU can also calculate an S-curve acceleration or deceleration curve as shown. This profile is useful for favoring the load characteristics in particular applications.

Output frequency

Accel. curve selection

Target freq.

Curve settings for acceleration and deceleration are independently selected. To enable the S-curve, use function A_97 (acceleration) and A_98 (deceleration).

Linear A_97 = 00 S-curve

A_97 = 01

0 t

Acceleration period

“A” Function Func. Code

–FU (UL)

–FR Units (Jpn)

✘

00

00

00, L

Set the characteristic curve of Acc1 and Acc2, two options: 00 ...linear 01 ...S-curve

✘

00

00

00, L

Set the characteristic curve of Acc1 and Acc2, two options: 00 ...linear 01 ...S-curve

Description

A_97 Acceleration curve selection

A_98 Deceleration curve selection DEC LINE

Configuring Drive Parameters

–FE (CE)

Name / SRW Display

ACCEL LINE

Defaults

Run Mode Edit

Page 93

3–22

“B” Group: Fine Tuning Functions

“B” Group: Fine Tuning Functions The “B” Group of functions and parameters adjust some of the more subtle but useful aspects of motor control and system configuration.

Automatic Restart Mode The restart mode determines how the inverter will resume operation after a fault causes a trip event. The four options provide advantages for various situations. Frequency matching allows the inverter to read the motor speed by virtue of its residual magnetic flux and restart the output at the corresponding frequency. The inverter can attempt a restart a certain number of times depending on the particular trip event: • Over-current trip, restart up to 3 times • Over-voltage trip, restart up to 3 times • Under-voltage trip, restart up to 16 times

Configuring Drive Parameters

When the inverter reaches the maximum number of restarts (3 or 16), you must power cycle the inverter to reset its operation. Other parameters specify the allowable under-voltage level and the delay time before restarting. The proper settings depend on the typical fault conditions for your application, the necessity of restarting the process in unattended situations, and whether restarting is always safe. Power failure > allowable power fail time (B_02), inverter trips

Power failure < allowable power fail time (B_02), inverter resumes Input power 0

Input power 0

Inverter output

Inverter output

0

0 free-running

Motor speed 0

Power fail Allowable power fail time Retry wait time

B 02 t free-running

Motor speed 0 Power fail B 02

B 03 t

Allowable power fail time

Page 94

L100 Inverter

“B” Function Func. Code

Name / SRW Display

B_01 Selection of restart mode IPS POWR

ALM

B_02 Allowable undervoltage power failure time IPS UVTIME 01.0s

IPS WAIT

001.0s

Defaults

Run Mode Edit

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Select inverter restart method, four option codes: 00 ...Alarm output after trip, no automatic restart 01 ...Restart at 0Hz 02 ...Resume operation after frequency matching 03 ...Resume previous freq. after freq. matching, then decelerate to stop and display trip info.

✘

00

00

00, The amount of time a power input under-voltage can occur without tripping the power failure alarm. Range is 0.3 to 25 sec. If under-voltage exists longer than this time, the inverter trips, even if the restart mode is selected.

✘

1.0

1.0

1.0 sec.

Time delay after under-voltage condition goes away, before the inverter runs motor again. Range is 0.3 to 100 seconds.

✘

1.0

1.0

1.0 sec.

Description

Configuring Drive Parameters

B_03 Retry wait time before motor restart

3–23

Page 95

3–24

“B” Group: Fine Tuning Functions

Electronic Thermal Overload Alarm Setting The thermal overload detection protects the Torque inverter and motor from overheating due to Constant torque B_13 = 01 100% an excessive load. It uses a current/inverse time curve to determine the trip point. 80% Reduced torque 60% First, use B_13 to select the torque characB_13 = 00 teristic that matches your load. This allows the inverter to utilize the best thermal 0 Hz overload characteristic for your application. 5 20 60 120 Output frequency The torque developed in a motor is directly proportional to the current in the windings, which is also proportional to the heat generated (and temperature, over time). Therefore, you must set the thermal overload threshold in terms of current (amperes) for parameter B_12. The range is 50% to 120% of the rated current for each inverter model. If the current exceeds the level you specify, the inverter will trip and log an event (error E05) in the history table. The inverter turns the motor output OFF when tripped.

Configuring Drive Parameters

“B” Function Func. Code

Name / SRW Display

B_12 Level of electronic thermal setting E-THM LVL 03.00A B_13 Electronic thermal characteristic E-THM CHAR

CRT

Description

Run Mode Edit

Defaults –FE (CE)

–FU (UL)

–FR Units (Jpn)

Set a level between 50% and 120% for the rated inverter current.

✘

Rated current for each inverter model *See note

%

Select from two curves, option codes: 00 ...Reduced torque 01 ...Constant torque

✘

01, 01

00

WARNING: When parameter B_12, level of electronic thermal setting, is set to device FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor overload protection at 115% of device FLA or equivalent. Parameter B_12, level of electronic thermal setting, is a variable parameter.

NOTE: For inverter models 005NFE, 011NFE, and 030HFE, the thermal value is less than the rated amperes (is the same as models 004NFE, 007NFE, and 040HFE respectively). Therefore, be sure to set the electronic thermal overload according to the actual motor driven by the particular inverter.

Page 96

L100 Inverter

3–25

Overload Restriction If the inverter’s output current exceeds a preset current level you specify during acceleration or constant speed, the overload restriction feature automatically reduces the output frequency to restrict the overload. This feature does not generate an alarm or trip event. You can instruct the inverter to apply overload restriction only during constant speed, thus allowing higher currents for acceleration. Or, you may use the same threshold for both acceleration and constant speed.

Motor Current Restriction area

B 22 0 t Output frequency 0 t

B 23

When the inverter detects an overload, it must decelerate the motor to reduce the current until it is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower the output current. “B” Function

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Select the operating mode during overload conditions, three options, option codes: ON 00 ...Disabled 01 ...Enabled for acceleration and constant speed 02 ...Enabled for constant speed only

✘

01

01

01, Sets the level for overload restriction, between 50% and 150% of the rated current of OLOAD LVL 03.75A the inverter, setting resolution is 1% of rated current

✘

Rated current x 1.25

A

✘

1.0, Name / SRW Display

B_21 Overload restriction operation mode OLOAD MODE

Description

B_22 Overload restriction setting

B_23 Deceleration rate at overload restriction OLOAD CONST 01.0

Sets the deceleration rate when inverter detects overload, range is 0.1 to 30.0, resolution is 0.1.

1.0

1.0

Configuring Drive Parameters

Func. Code

Defaults

Run Mode Edit

Page 97

3–26

“B” Group: Fine Tuning Functions

Software Lock Mode The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B_31 to select from various protection levels.

Configuring Drive Parameters

The table below lists all combinations of B_31 option codes and Run the ON/OFF state of the [SFT] input. Each Check ✔ or Ex ✘ Mode indicates whether the corresponding parameter(s) can be edited. Edit The Standard Parameters column below shows access is permit✘ ted for some lock modes. These refer to the parameter tables ✔ throughout this chapter, each of which includes a column titled Run Mode Edit as shown to the right. The marks (Check ✔ or Ex ✘) under the “Run Mode Edit” column title indicate whether access applies to each parameter as defined in the table below. In some lock modes, you can edit only F_01 and the Multi-speed parameter group that includes A_20, A220, A_21–A_35, and A_38 (Jog). However, it does not include A_19, Multi-speed operation selection. The editing access to B_31 itself is unique, and is specified in the right-most two columns below. B_31 Lock Mode

[SFT] Intelligent Input

00

Standard Parameters

F_01 and Multi-Speed

B_31

Stop

Run

Stop & Run

Stop

Run

OFF

✔

Run mode edit access

✔

✔

✘

ON

✘

✘

✘

✔

✘

OFF

✔

Run mode edit access

✔

✔

✘

ON

✘

✘

✔

✔

✘

02

(ignored)

✘

✘

✘

✔

✘

03

(ignored)

✘

✘

✔

✔

✘

01

NOTE: Since the software lock function B_31 is always accessible, this feature is not the same as password protection used in other industrial control devices.

Page 98

L100 Inverter

“B” Function Func. Code

Name / SRW Display

B_31 Software lock mode selection S-LOCK

MD1

Description Prevents parameter changes, in four options, option codes: 00 ...all parameters except B_31 are locked when [SFT] terminal is ON 01 ...all parameters except B_31 and output frequency F01 when SFT from terminal is ON 02 ...all parameters except B_31 are locked 03 ...all parameters except B_31 and output frequency F_01 setting are locked

3–27

Defaults

Run Mode Edit

–FE (CE)

–FU (UL)

–FR Units (Jpn)

✘

01

01

01, Configuring Drive Parameters

NOTE: To disable parameter editing when using B_31 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “Software Lock” on page 4–17.

Page 99

3–28

“B” Group: Fine Tuning Functions

Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. This section covers some of the most important settings you may need to configure. B_32: Reactive current setting – The inverter’s D_02 monitor function displays the motor current. The display accuracy is normally ±20%, provided that the following conditions exist: • A single motor with standard frame size and characteristics is connected • The inverter’s output frequency is at 50% or higher of the maximum output frequency • The inverter’s output current is within the rated current However, it will be necessary to calibrate the display accuracy via B_32 adjustment of the internal no-load reactive motor current if any of these conditions exist: • The motor is smaller than the standard maximum recommended for the inverter • The motor is a two-pole motor type

Configuring Drive Parameters

• Two or more motors are connected in parallel to the inverter (be sure to multiply the current by the number of motors when setting B_32) If you do not know the reactive or no-load current for your particular motor, you can calibrate the L100 as follows: 1. Connect the motor directly across the AC line with no load attached to the shaft. WARNING: Use a disconnect switch or breaker to ensure that you do not connect the motor or inverter to live wiring. Otherwise, there is the danger of electric shock. 2. Run the motor, and measure the no-load current with an AC current clamp, recording the value. 3. Disconnect the motor from the AC line connection, and connect the motor to the L100 inverter output (still with no load attached). 4. Run the motor at the base frequency (value of parameter A_03), and monitor the motor current with function D_02. 5. If the D_02 display value does not match the current clamp value recorded in Step 2, adjust parameter B_32 up or down until the best match is achieved. NOTE: Parameter setting B_32 affects the inverter’s electronic thermal protection (B_12 setting) and its overload restriction function (B_22 setting). B_83: Carrier frequency adjustment – The internal switching frequency of the inverter circuitry (also called the chopper frequency). It is called the carrier frequency because the lower AC output frequency of the inverter “rides” the carrier. The faint, high-pitched sound you hear when the inverter is in Run Mode is characteristic of switching power supplies in general. The carrier frequency is adjustable from 500 Hz to 16 kHz. The audible sound decreases at the higher frequencies, but RFI noise and leakage current may be increased. Refer to the specification derating curves in Chapter 1 to determine the maximum allowable carrier frequency setting for your particular inverter and environmental conditions.

Page 100

L100 Inverter

3–29

NOTE: When DC braking is performed, the inverter automatically holds the carrier frequency at 1 kHz. NOTE: The carrier frequency setting must stay within specified limits for inverter-motor applications that must comply with particular regulatory agencies. For example, a European CE-approved application requires the inverter carrier to be less than 5 kHz.

B_84, B_85: Initialization codes – These functions allow you to restore the factory default settings. Please refer to “Restoring Factory Default Settings” on page 6–8. B_86: Frequency display scaling – You can convert the output frequency monitor on D_01 to a scaled number (engineering units) monitored at function D_07. For example, the motor may run a conveyor that is monitored in feet per minute. Use this formula: Scaled output frequency (D_07) = Output frequency (D_01) × Factor (B_86)

“B” Function Name / SRW Display

Description

Defaults –FE (CE)

–FU (UL)

–FR Units (Jpn)

B_32 Reactive current setting Calibrate detection of motor’s no load (reactive) current to IO 0.00A improve D_02 display accuracy, range is 0 to 32 Amperes

✔

58% rated current

A

B_81 [FM] terminal analog meter adjustment

Adjust 8-bit gain to analog meter connected to terminal [FM], range is 0 to 255

✔

80

80

80, Sets the starting frequency for the inverter output, range is 0.5 to 9.9 Hz

✘

0.5

0.5

0.5

Hz

Sets the PWM carrier (internal switching frequency), range is 0.5 to 16.0 kHz

✘

5.0

5.0

12.0 kHz

Select the type of initialization to occur, two option codes: 00 ...Trip history clear 01 ...Parameter initialization

✘

00

00

00, B_85 Country code for initial- Select default parameter values ization for country on initialization, four options, option codes: INIT SEL USA 00 ...Japan version 01 ...Europe version 02 ...US version 03 ...reserved (do not set)

✘

01

02

00, ADJ

080

B_82 Start frequency adjustment Fmin

0.5Hz

B_83 Carrier frequency setting CARRIER

05.0kHz

B_84 Initialization mode (parameters or trip history) INIT MODE

TRP

Configuring Drive Parameters

Func. Code

Run Mode Edit

Page 101

3–30

“B” Group: Fine Tuning Functions

“B” Function Func. Code

Name / SRW Display

/Hz01.0

0.00

B_87 STOP key enable STOP-SW

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Specify a constant to scale the displayed frequency for D_07 monitor, range is 0.1 to 99.9

✘

1.0

1.0

1.0, Select whether the STOP key on the keypad is enabled, two option codes: 00 ...enabled 01 ...disabled

✘

00

00

00, Description

B_86 Frequency scaling conversion factor

ON

Defaults

Run Mode Edit

Configuring Drive Parameters

B_88: Restart Mode Configuration – You can configure how the inverter resumes motor output control after a free-run stop. Setting B_88 determines whether the inverter will ensure the motor always resumes at 0 Hz, or whether the motor resumes from its current coasting speed (also called frequency matching). The Run command may turn OFF briefly, allowing the motor to coast to a slower speed from which normal operation can resume. In most applications a controlled deceleration is desirable. However, applications such as HVAC fan control will often use a free-run stop. This practice decreases dynamic stress on system components, prolonging system life. In this case, you will typically set B_88=01 in order to resume from the current speed after a free-run stop (see diagram below, right). Note that using the default setting, B_88=00, can cause trip events when the inverter attempts to force the load quickly to zero speed. NOTE: Other events can cause (or be configured to cause) a free-run stop, such as power loss (see “Automatic Restart Mode” on page 3–22), or an intelligent input terminal [FRS] signal. If all free-run stop behavior is important to your application (such as HVAC), be sure to configure each event accordingly. An additional parameter further configures all instances of a free-run stop. Parameter B_03, Retry Wait Time Before Motor Restart, sets the minimum time the inverter will free-run. For example, if B_03 = 4 seconds and the cause of the free-run-stop lasts 10 seconds, the inverter will free-run (coast) for a total of 14 seconds before driving the motor again. B_88 = 00 Resume from 0Hz

B_88 = 01 Resume from current speed B 03 Wait time

Zero-frequency start Motor speed

Motor speed

[FRS]

[FRS]

[FW, RV]

[FW, RV] t t