Page 82

L100 Inverter

“A” Function Func. Code

Name / SRW Display

Description

A_16 External frequency filter time constant IN F-SAMP

Range n = 1 to 8, where n = number of samples for avg.

3–11

Defaults

Run Mode Edit

–FE (CE)

–FU (UL)

✘

8

8

–FR Units (Jpn) 8

Samples

8

Configuring Drive Parameters

Page 83

3–12

“A” Group: Standard Functions

Multi-speed and Jog Frequency Setting The L100 inverter has the capability to store and output up to 16 preset frequencies to the motor (A_20 to A_35). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter. The inverter applies the current acceleration or deceleration setting to change from the current output frequency to the new one. The jog speed setting is used whenever the Jog command is active. The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The acceleration to the jog frequency is instantaneous, but you can choose from three modes for the best method for stopping the jog operation. “A” Function Func. Code

SPD FS

Configuring Drive Parameters

–FE (CE)

–FU (UL)

Defines the first speed of a multi-speed profile, range is 0 to 360 Hz

✔

0

0

0

Hz

Defines 15 more speeds, range is 0 to 360 Hz. A_21= Speed 2... A_35 = Speed 16

✔ see next row see next row see next row

Hz

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

5 10 15 20 30 40 50 60 0 0 0 0 0 0 0

Name / SRW Display

Description

A_20 Multi-speed frequency setting 000.0Hz

A_21 Multi-speed frequency to settings A_35 SPD 1 SPD 2 SPD 3 SPD 4 SPD 5 SPD 6 SPD 7 SPD 8 SPD 9 SPD 10 SPD 11 SPD 12 SPD 13 SPD 14 SPD 15

000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz 000.0Hz

✔

1.0

1.0

1.0

Hz

Define how end of jog stops the motor; three options: 0 00 ...Free-run stop 01 ...Controlled deceleration 02 ...DC braking to stop

✘

00

00

00, 01.00Hz

A_39 Jog stop mode Jog Mode

A_21 A_22 A_23 A_24 A_25 A_26 A_27 A_28 A_29 A_30 A_31 A_32 A_33 A_34 A_35

–FR Units (Jpn)

Defines limited speed for jog, range is 0.5 to 9.99 Hz

A_38 Jog frequency setting Jogging

Defaults

Run Mode Edit

Page 84

3–13

L100 Inverter

Torque Control Algorithms The inverter generates the motor output according to the V/f algorithm selected. Parameter A_44 selects the inverter algorithm for generating the frequency output, as shown in the diagram to the right. The factory default is 00 (constant torque).

Inverter Torque Control Algorithms A44 V/f control, constant torque

00 Output

Review the following description to help you choose the best torque control algorithm for your application.

V/f control, variable torque

01

The built-in V/f curves are oriented toward developing constant torque or variable torque characteristics (see graphs below). You can select either constant torque or reduced torque V/f control. Constant and Variable (Reduced) Torque – The graph below (left) shows the constant torque characteristic from 0Hz to the base frequency A_03. The voltage remains constant for output frequencies higher than the base frequency. The graph below (right) shows the general variable (reduced) torque curve. The range from 0Hz to the base frequency is the variable characteristic. V 100%

A_44 = 00 Constant torque

0 Base freq.

Max. freq.

Hz

A_44 = 01

Variable torque

0 Base freq.

Hz Max. freq.

Torque Boost – The Constant and A_42 = 11 V Variable Torque algorithms feature an 100% adjustable torque boost curve. When the Torque boost motor load has a lot of inertia or starting A friction, you may need to increase the low 11.8% frequency starting torque characteristics by boosting the voltage above the normal V/f ratio (shown at right). The boost is 0 applied from zero to 1/2 the base 6.0Hz 30.0Hz f base = frequency. You set the breakpoint of the 60Hz A_43 = 10 (%) boost (point A on the graph) by using parameters A_42 and A_43. The manual boost is calculated as an addition to the standard straight V/f line (constant torque curve).

Hz

Be aware that running the motor at a low speed for a long time can cause motor overheating. This is particularly true when manual torque boost is ON, or if the motor relies on a built-in fan for cooling.

Configuring Drive Parameters

V 100%

Page 85

3–14

“A” Group: Standard Functions Voltage Gain – Using parameter A_45 you V can modify the voltage gain of the inverter (see 100% graph at right). This is specified as a percentage of the full scale setting (Automatic Voltage Regulation) AVR level in parameter F_03. The 50% gain can be set from 50% to 100%. It should be adjusted in accordance with the motor specifi0 cations.

Voltage Gain

A 45

Hz

The following table shows the methods of torque control selection. “A” Function Func. Code

Name / SRW Display

V-Boost

Mode

0

Configuring Drive Parameters

A_42 Manual torque boost value V-Boost code 11

A_43 Manual torque boost frequency adjustment V-Boost

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Two options: 00 ...Manual torque boost 01 ...Automatic torque boost

✘

00

00

00, Can boost starting torque between 0 and 99% above normal V/f curve, from 0 to 1/2 base frequency

✔

11

11

11, Sets the frequency of the V/f breakpoint A in graph (top of previous page) for torque boost

✔

10.0

10.0

10.0

%

✘

00

00

00, ✔

100

100

100

%

Description

A_41 Torque boost method selection

F 10.0%

A_44 V/f characteristic curve selection CONTROL

Two available V/f curves; three select codes: 00 ...Constant torque SLV 01 ...Reduced torque

A_45 V/f gain setting V-Gain

100%

Defaults

Run Mode Edit

Sets voltage gain of the inverter from 50 to 100%

Page 86

L100 Inverter

3–15

DC Braking Settings The DC braking feature can provide + Running Free run DC braking additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful 0 at low speeds when normal decelerat tion torque is minimal. When you A 53 A 55 enable DC braking, the inverter injects – a DC voltage into the motor windings during deceleration below a frequency you can specify (A_52). The braking power (A_54) and duration (A_55) can both be set. You can optionally specify a wait time before DC braking (A_53), during which the motor will free run (coast). CAUTION: Be careful to avoid specifying a braking time that is long enough to cause motor overheating. If you use DC braking, we recommend using a motor with a built-in thermistor, and wiring it to the inverter’s thermistor input (see “Thermistor Thermal Protection” on page 4–20). Also refer to the motor manufacturer’s specifications for duty-cycle recommendations during DC braking. “A” Function Name / SRW Display

A_51 DC braking enable DCB SW

00.5Hz

A_53 DC braking wait time DCB WAIT

0.0s

A_54 DC braking during deceleration DCB V

–FR Units (Jpn)

✘

00

00

00, The frequency at which DC braking occurs, range is 0.5 to 10 Hz

✘

0.5

0.5

0.5

Hz

The delay from the end of Run command to start of DC braking (motor free runs until DC braking begins)

✘

0.0

0.0

0.0 sec.

Applied level of DC braking force, settable from 0 to 100%

✘

0

0

0

%

Sets the duration for DC braking, range is 0.1 to 60.0 seconds

✘

0.0

0.0

0.0 sec.

000

A_55 DC braking time for deceleration DCB T

–FU (UL)

Two options; select codes: 00 ...Disable OFF 01 ...Enable

A_52 DC braking frequency setting DCB F

–FE (CE)

Description

00.0s

Configuring Drive Parameters

Func. Code

Defaults

Run Mode Edit

Page 87

3–16

“A” Group: Standard Functions

Frequency-related Functions Frequency Limits – Upper and lower Output limits can be imposed on the inverter frequency output frequency. These limits will apply regardless of the source of the speed refer- A 61 Upper limit ence. You can configure the lower frequency limit to be greater than zero as shown in the graph to the right. The upper Lower limit must not exceed the rating of the A 62 limit motor or capability of the machinery. 0

“A” Function Func. Code

Name / SRW Display

Configuring Drive Parameters

A_61 Frequency upper limit setting LIMIT H

000.0Hz

A_62 Frequency lower limit setting LIMIT L

000.0Hz

Settable range

Frequency command

Defaults

Run Mode Edit

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Sets a limit on output frequency less than the maximum frequency (A_04) Range is 0.5 to 360.0 Hz 0.0 ..setting is disabled >0.1 setting is enabled

✘

0.0

0.0

0.0

Hz

Sets a limit on output frequency greater than zero Range is 0.5 to 360.0 Hz 0.0 ..setting is disabled >0.1 setting is enabled

✘

0.0

0.0

0.0

Hz

Description

Page 88

L100 Inverter

3–17

Jump Frequencies – Some motors or machines exhibit resonances at particular speed(s), which can be destructive for prolonged running at those speeds. The inverter has up to three jump frequencies as shown in the graph. The hysteresis around the jump frequencies causes the inverter output to skip around the sensitive frequency values Output frequency A 68 A 68

A 67 Jump frequencies A 66 A 66

A 65

Hysteresis values

A 64 A 64

A 63 0

Frequency command

“A” Function Name / SRW Display

Description

Defaults –FU (UL)

–FR Units (Jpn)

A_63, Jump (center) frequency A_65, setting A_67 JUMP F1 000.0Hz JUMP F2 000.0Hz JUMP F3 000.0Hz

Up to 3 output frequencies can be defined for the output to jump past to avoid motor resonances (center frequency) Range is 0.0 to 360.0 Hz

✘

0.0 0.0 0.0

0.0 0.0 0.0

0.0 0.0 0.0

Hz

A_64, Jump (hysteresis) A_66, frequency width setting A_68 JUMP W1 00.50Hz JUMP W2 00.50Hz JUMP W3 00.50Hz

Defines the distance from the center frequency at which the jump around occurs Range is 0.0 to 10.0 Hz

✘

0.5 0.5 0.5

0.5 0.5 0.5

0.5 0.5 0.5

Hz

Configuring Drive Parameters

Func. Code

Run Mode –FE Edit (CE)

Page 89

3–18

“A” Group: Standard Functions

PID Control When enabled, the built-in PID loop calculates an ideal inverter output value to cause a loop feedback process variable (PV) to move closer in value to the setpoint (SP). The current frequency command serves as the SP. The PID loop algorithm will read the analog input for the process variable (you specify the current or voltage input) and calculate the output. • A scale factor in A_75 lets you multiply the PV by a factor, converting it into engineering units for the process. • Proportional, integral, and derivative gains are all adjustable. • See “PID Loop Operation” on page 4–32 for more information. “A” Function Func. Code

Name / SRW Display

A_71 PID Enable

Configuring Drive Parameters

PID SW

OFF

A_72 PID proportional gain PID P

1.0

A_73 PID integral time constant PID I

01.00

A_76 PV source setting PID INPT

–FU (UL)

–FR Units (Jpn)

Enables PID function, two option codes: 00 ...PID Disable 01 ...PID Enable

✘

00

00

00, Proportional gain has a range of 0.2 to 5.0

✘

1.0

1.0

1.0, Integral time constant has a range of 0.0 to 150 seconds

✘

1.0

1.0

1.0 sec.

Derivative time constant has a range of 0.0 to 100 seconds

✘

0.0

0.0

0.0 sec.

Process Variable (PV) scale factor (multiplier), range of 0.01 to 99.99

✘

1.00

1.00

1.00, Selects source of Process Variable (PV), option codes: 00 ...[OI] terminal (current in) 01 ...[O] terminal (voltage in)

✘

00

00

00, 00.0

A_75 PV scale conversion PID CONV

–FE (CE)

Description

001.0s

A_74 PID derivative time constant PID D

Defaults

Run Mode Edit

CUR

NOTE: The setting A_73 for the integrator is the integrator’s time constant Ti, not the gain. The integrator gain Ki = 1/Ti. When you set A_73 = 0, the integrator is disabled.

Page 90

L100 Inverter

3–19

Automatic Voltage Regulation (AVR) Function The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage fluctuations. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage. If you enable this feature, be sure to select the proper voltage class setting for your motor. “A” Function Func. Code

Name / SRW Display

Description

A_81 AVR function select AVR MODE

Automatic (output) voltage regulation, selects from three DOFF type of AVR functions, three option codes: 00 ...AVR enabled 01 ...AVR disabled 02 ...AVR enabled except during deceleration

A_82 AVR voltage select AVR AC

–FE (CE)

–FU (UL)

–FR Units (Jpn)

✘

02

00

02, ✘

230/ 400

230/ 460

200/ 400

V

Configuring Drive Parameters

200V class inverter settings: .......200/220/230/240 230V 400V class inverter settings: .......380/400/415/440/460

Defaults

Run Mode Edit

Page 91

3–20

“A” Group: Standard Functions

Second Acceleration and Deceleration Functions The L100 inverter features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape. You can specify the frequency transition point, the point at which the standard acceleration (F_02) or deceleration (F_03) changes to the second acceleration (A_92) or deceleration (A_93). Select a transition frequency method via A_94 as depicted below. A_94 = 00 Transition via 2CH input Output frequency

A_94 = 01 Transition via freq. level Output frequency

Accel 2

Accel 2

A 95

Accel 1

Accel 1

0 2CH input

Frequency transition point

0 t t

1 0 t

Configuring Drive Parameters

“A” Function

Defaults

Run Mode Edit

–FE (CE)

–FU (UL)

–FR Units (Jpn)

Duration of 2nd segment of acceleration, range is: 0.1 to 3000 sec.

✔

15.0

15.0

15.0 sec.

Duration of 2nd segment of deceleration, range is: 0.1 to 3000 sec.

✔

15.0

15.0

15.0 sec.

A_94 Select method to switch Two options for switching to Acc2/Dec2 profile from 1st to 2nd accel/decel: 00 ...2CH input from terminal ACC CHG TM 01 ...transition frequency

✘

00

00

00, A_95 Acc1 to Acc2 frequency Output frequency at which transition point Accel1 switches to Accel2, range is 0.0 to 360.0 Hz ACC CHFr 000.0Hz

✘

0.0

0.0

0.0

Hz

A_96 Dec1 to Dec2 frequency Output frequency at which transition point Decel1 switches to Decel2, range is 0.0 to 360.0 Hz DEC CHFr 000.0Hz

✘

0.0

0.0

0.0

Hz

Func. Code

Name / SRW Display

A_92 Acceleration (2) time setting ACC 2

0015.0s

A_93 Deceleration (2) time setting DEC 2

0015.0s

Description

NOTE: For A_95 and A_96, if you set a very rapid Acc1 or Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or Dec2 before reaching the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in order to achieve the second ramp to the target frequency.