Page 72
Configuring Drive Parameters In This Chapter....
3 page, Choosing a Programming Device ................... 2, Using Keypad Devices .................................... 3, “D” Group: Monitoring Functions..................... 6, “F” Group: Main Profile Parameters ................ 8, “A” Group: Standard Functions ....................... 9, “B” Group: Fine Tuning Functions ................. 22, “C” Group: Intelligent Terminal Functions...... 32
Page 73
3–2
Choosing a Programming Device
Choosing a Programming Device Introduction Hitachi variable frequency drives (inverters) use the latest electronics technology for getting the right AC waveform to the motor at the right time. The benefits are many, including energy savings and higher machine output or productivity. The flexibility required to handle a broad range of applications has required ever more configurable options and parameters - inverters are now a complex industrial automation component. And this can make a product seem difficult to use, but the goal of this chapter is to make this easier for you. As the powerup test in Chapter 2 demonstrated, you do not have to program very many parameters to run the motor. In fact, most applications would benefit only from programming just a few, specific parameters. This chapter will explain the purpose of each set of parameters, and help you choose the ones that are important to your application.
Configuring Drive Parameters
If you are developing a new application for the inverter and a motor, finding the right parameters to change is mostly an exercise in optimization. Therefore, it is okay to begin running the motor with a loosely tuned system. By making specific, individual changes and observing their effects, you can achieve a finely tuned system.
Introduction to Inverter Programming The front panel keypad is the first and best way to get to know the inverter’s capabilities. Every function or programmable parameter is accessible from the keypad. The other devices simply imitate the keypad’s layout and inverter access, while adding another valuable aspect to the system. For example, the Copy Unit can transfer one inverter’s parameter settings to another inverter, while still providing standard operator keypad control. In this way, you can use a variety of programming devices with basically the same keypad skills. The following table shows various programming options, the features unique to each device, and the cables required.
Device
Part Number
Parameter Access
Parameter setting storage
Cables (choose one) Part number
Length
Inverter keypad, Monitor and program
EEPROM in inverter, - DOP Professional Software (for PC)
DOP–PRO
Monitor and program
PC hard drive or diskette
(Included with software)
2 meters
Digital Operator/ Copy Unit
SRW–0EX
Monitor and program
EEPROM in operator panel
ICS–1
1 meter
ICS–3
3 meters
Operator Monitor
OPE–J
Monitor only none on operator monitor
ICJ–1L
1 meter
ICJ–3L
3 meters
Page 74
L100 Inverter
3–3
Using Keypad Devices Inverter Front Panel Keypad The L100 Series inverter front keypad contains all the elements for both monitoring and programming parameters. The keypad layout is pictured below. All other programming devices for the inverter have a similar key arrangement and function. Power LED
Parameter Display POWER
HITACHI
Run/Stop LED
RUN
Program/Monitor LED Run Key Enable LED
PRG
RUN
5 0.0
Hz A
Potentiometer Enable LED
STOP
RESET MAX
MIN
Run Key Stop/Reset Key
FUNC. 1
Function key
Display Units Hertz / Amperes LEDs
2
STR
Up/Down keys
Potentiometer Store key
Key and Indicator Legend
• Program/Monitor LED - This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode). • Run Key Enable LED - is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled. • Run Key - Press this key to run the motor (the Run Enable LED must be ON first). Parameter F_04, Keypad Run Key Routing, determines whether the Run key generates a Run FWD or Run REV command. • Stop/Reset Key - Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped. • Potentiometer - Allows an operator to directly set the motor speed when the potentiometer is enabled for output frequency control. • Potentiometer Enable LED - ON when the potentiometer is enabled for value entry. • Parameter Display - A 4-digit, 7-segment display for parameters and function codes. • Display Units, Hertz/Amperes - One of these LEDs will be ON to indicate the units associated with the parameter display. • Power LED - This LED is ON when the power input to the inverter is ON. • Function Key - This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. • Up/Down ( 1 , 2 ) Keys - Use these keys alternately to move up or down the lists of parameter and functions shown in the display, and increment/decrement values. • Store ( STR ) Key - When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM.
Configuring Drive Parameters
• Run/Stop LED - ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode).
Page 75
3–4
Using Keypad Devices
Keypad Navigational Map You can use the inverter’s front panel keypad to navigate to any parameter or function. The diagram below shows the basic navigational map to access these items. Monitor Mode
Program Mode
PRG LED=OFF Display Data
0 0 0.0 FUNC.
1 d 09
PRG LED=ON Select Parameter powerdown
Select Function or Group
Store as powerup default
1
C 91 1
1
2
Configuring Drive Parameters
1
1
FUNC.
1
1
1
FUNC.
1 2 3.4
F 04
2
FUNC.
2 STR
2
A 01
2
2
Edit
2
A 98
2
A -1
2 b 01
2 b - 1
2 b 92
2
C -1
Increment/ decrement value
C 01 d 01 1
Edit Parameter
Write data to EEPROM
FUNC.
1
2
F 01
Return to parameter list
2
NOTE: The inverter 7-segment display shows lower case “b” and “d,” meaning the same as the upper case letters “B” and “D” used in this manual (for uniformity “A to F”). NOTE: The Store Key saves the edited parameter (shown in the display) to the inverter’s EEPROM. Upload or download of parameters to/from external devices is accomplished through a different command - do not confuse Store with Download or Upload.
Page 76
3–5
L100 Inverter
Operational Modes The RUN and PGM LEDs tell just part of the story; Run Mode and Program Modes are independent modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode. This is a very important ability, for it shows that a technician can approach a running machine and change some parameters without shutting down the machine. The occurrence of a fault during operation will cause the inverter to enter the Trip Mode as shown. An event such as an output overload will cause the inverter to exit the Run Mode and turn OFF its output to the motor. In the Trip Mode, any request to run the motor is ignored. You must clear the error by pressing the Stop/Reset switch. See page “Monitoring Trip Events, History, & Conditions” on page 6–5.
STOP
RESET
Run
Stop
RUN
FUNC.
Monitor
Program
STOP
RESET
Run
Stop RUN STOP
RESET
Fault Trip
Fault
Run Mode Edits
The parameter tables in this chapter have a column titled “Run Mode Edit.” An Ex mark ✘ means the parameter cannot be edited; a Check mark ✔ means the parameter can be edited. The Software Lock Setting (parameter B_31) determines when the Run Mode access permission is in effect and access permission in other conditions, as well. It is the responsibility of the user to choose a useful and safe software lock setting for the inverter operating conditions and personnel. Please refer to “Software Lock Mode” on page 3–26 for more information.
Run Mode Edit ✘ ✔
Control Algorithms The motor control program in the L100 inverter has two PWM sinusoidal switching algorithms. The intent is that you select the best algorithm for the motor characteristics in your application. Both algorithms generate the frequency output in a unique way. Once configured, the algorithm is the basis for other parameter settings as well (see “Torque Control Algorithms” on page 3–13). Therefore, choose the best algorithm early in your application design process.
Inverter Control Algorithms
Variable freq. control, constant torque Output Variable freq. control, reduced torque
Configuring Drive Parameters
The inverter can be in Run Mode (inverter output is controlling motor) and still allow you to edit certain parameters. This is useful in applications that must run continuously, yet need some inverter parameter adjustment.
Page 77
3–6
“D” Group: Monitoring Functions
“D” Group: Monitoring Functions Parameter Monitoring Functions You can access important system parameter values with the “D” Group monitoring functions, whether the inverter is in Run Mode or Stop Mode. After selecting the function code number for the parameter you want to monitor, press the Function key once to show the value on the display. In Functions D_05 and D_06, the intelligent terminals use individual segments of the display to show ON/OFF status. If the inverter display is set to monitor a parameter and powerdown occurs, the inverter stores the present monitor function setting. For your convenience, the display automatically returns to the previously monitored parameter upon the next powerup. “D” Function Func. Code
Name / SRW Display
D_01 Output frequency monitor
Configuring Drive Parameters
FM
0000.00Hz
D_02 Output current monitor Im 0.0A
0.0%
D_03 Rotation direction monitor Dir
STOP
D_04 Process variable (PV), PID feedback monitor PID-FB
0000.00%
D_05 Intelligent input terminal status TERM
Run Mode Edit
Range and Units
Real-time display of output frequency to motor, from 0.0 to 360.0 Hz, 0.0 to 360.0 Hz
Filtered display of output current to motor (100 ms internal filter time constant), A
Three different indications: “F”..... Forward “| |” .. Stop “r”..... Reverse, - Displays the scaled PID process variable (feedback) value (A_75 is scale factor), - Displays the state of the intelligent input terminals:, - - - Description
LLL LLLLLL
ON OFF 6 5 4 3 2 1 Terminal numbers
D_06 Intelligent output terminal status TERM
Displays the state of the intelligent output terminals:
LLL LLLLLL
ON OFF AL 12 11 Terminal numbers
Page 78
L100 Inverter
“D” Function Func. Code
Name / SRW Display
Description
D_07 Scaled output frequency Displays the output frequency monitor scaled by the constant in B_86. Decimal point indicates range: /Hz01.0 0.00 XX.XX 0.01 to 99.99 XXX.X 100.0 to 999.9 XXXX. 1000 to 9999 XXXX 10000 to 99990
Run Mode Edit
Range and Units, Hz
3–7
Trip Event and History Monitoring The trip event and history monitoring feature lets you cycle through related information using the keypad. See “Monitoring Trip Events, History, & Conditions” on page 6–5 for more details. “D” Function Name / SRW Display
ERR1 EEPROM ERR1 0.0Hz ERR1 0.0A ERR1 324.3Vdc ERR1 RUN 000000H D_09 Trip history monitor ERR2 EEPROM ERR2 0.0Hz ERR2 0.0A ERR2 330.0Vdc ERR2 RUN 000000H ERR3 EEPROM ERR3 0.0Hz ERR3 0.0A ERR3 328.7Vdc ERR3 RUN 000000H Cumulative operation RUN time monitor RUN, 000000H
Trip count ERROR COUNT
Displays the current trip event. information., - Displays the previous two events and their causes., - Displays total time the inverter has been in RUN mode in hours., hours
Displays cumulative number of trip events., trips
Description
D_08 Trip event monitor, Range and Units
009
Configuring Drive Parameters
Func. Code
Run Mode Edit
Page 79
3–8
“F” Group: Main Profile Parameters
“F” Group: Main Profile Parameters The basic frequency (speed) profile is Output defined by parameters contained in the “F” frequency F 02 F 03 Group as shown to the right. The set running frequency is in Hz, but acceleraF 01 tion and deceleration are specified in the time duration of the ramp (from zero to maximum frequency, or from maximum 0 frequency to zero). The motor direction t parameter determines whether the keypad Run key produces a FWD or REV command. This parameter does not affect the intelligent terminal [FWD] and [REV] functions, which you configure separately. Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main profile. Accel and decel values for an alternative profile are specified by using parameters A_92 through A_93. The motor direction selection (F_04) determines the direction of rotation as commanded only from the keypad.
Configuring Drive Parameters
“F” Function Func. Code
Name / SRW Display
F_01 Output frequency setting TM 000.0
0.0Hz
F_02 Acceleration 1 time setting ACC 1
Defaults –FU (UL)
–FR Units (Jpn)
Standard default target frequency that determines constant motor speed, range is 0 to 360 Hz
✔
0.0
0.0
0.0
Hz
Standard default acceleration, range is 0.1 to 3000 sec.
✔
10.0
10.0
10.0 sec.
Standard default deceleration, range is 0.1 to 3000 sec.
✔
10.0
10.0
10.0 sec.
✘
00
00
00, 0010.0s
F_03 Deceleration 1 time setting DEC 1
Description
Run Mode –FE Edit (CE)
0010.0s
F_04 Keypad Run key routing Two options; select codes: 00... Forward INIT DOPE FWD 01... Reverse
Page 80
3–9
L100 Inverter
“A” Group: Standard Functions Basic Parameter Settings These settings affect the most fundamental behavior of the inverter - the outputs to the motor. The frequency of the inverter’s AC output determines the motor speed. You may select from three different sources for the reference speed. During application development you may prefer using the potentiometer, but you may switch to an external source (control terminal setting) in the finished application, for example. The base frequency and maximum frequency settings interact according to the graph below (left). The inverter output operation follows the constant V/f curve until it reaches the full-scale output voltage. This initial straight line is the constant-torque part of the operating characteristic. The horizontal line over to the maximum frequency serves to let the motor run faster, but at a reduced torque. If you want the motor to output constant torque over its entire operating range (limited to the motor nameplate voltage and frequency rating), then set the base frequency and maximum frequency equal as shown (below right). A 03 V 100%
A 03
V 100%
A 04
A 04 Constant torque f Base Frequency
“A” Function Func. Code
Name / SRW Display
A_01 Frequency source setting F-SET-SELECT TRM A_02 Run command source setting F/R SELECT TRM A_03 Base frequency setting F-BASE
060Hz
A_04 Maximum frequency setting F-MAX
060Hz
0 f
Maximum Frequency
Base frequency = maximum frequency
Defaults
Run Mode Edit
–FE (CE)
–FU (UL)
–FR Units (Jpn)
Three options; select codes: 00 ...Keypad potentiometer 01 ...Control terminal 02 ...Function F01 setting
✘
01
01
00, Two options; select codes: 01 ...Control terminal 02 ...Run key on keypad, or digital operator
✘
01
01
02, Settable from 50 Hz to the maximum frequency
✘
50.0
60.0
60.0
Hz
Settable from the base frequency up to 360 Hz
✘
50.0
60.0
60.0
Hz
Description
Configuring Drive Parameters
0
Page 81
3–10
“A” Group: Standard Functions
Analog Input Settings The inverter has the capability to accept an external analog input that can command the output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are available on separate terminals ([O] and [OI], respectively). Terminal [L] serves as signal ground for the two analog inputs. The analog input settings adjust the curve characteristics between the analog input and the frequency output. In the graph below (left), A_13 and A_14 select the active portion of the input voltage or current range. The parameters A_11 and A_12 select the start and end frequency of the converted output frequency range, respectively. Together, these four parameters define a line segment as shown (below, right). When the line does not begin at the origin, A_15 defines whether the inverter outputs 0Hz or the A_11 frequency when the analog input value is less than the A_13 setting (determines the non-linear part of the translation). Frequency
Frequency
A 12
A 12 A_15 = 00
Configuring Drive Parameters
A 11 0 0V A 13 A 14 10V 4mA 20mA % Input scale
A 11 %
“A” Function Func. Code
Name / SRW Display
A_11 O/OI–L input active range start frequency IN EXS
000.0Hz
A_12 O/OI–L input active range end frequency IN EXE
000.0Hz
A_13 O/OI–L input active range start voltage IN EX%S
%
0V A 13 A 14 10V 4mA 20mA % Input scale
Defaults
Run Mode Edit
–FE (CE)
–FU (UL)
–FR Units (Jpn)
The output frequency corresponding to the analog input range starting point
✘
0.0
0.0
0.0
Hz
The output frequency corresponding to the analog input range ending point
✘
0.0
0.0
0.0
Hz
The starting point (offset) for the active analog input range
✘
0
0
0
%
The ending point (offset) for the active analog input range
✘
100
100
100
%
Two options; select codes: 00 ...Use offset (A_11 value) 01 ...Use 0 Hz
✘
01
01
01, Description
100%
A_15 O/OI–L input start frequency enable IN LEVEL
0
000%
A_14 O/OI–L input active range end voltage IN EX%E
A_15 = 01
0Hz