L100 Series Inverter Instruction Manual: Troubleshooting and Maintenance, pages 152 to 159

Pages 152 to 159 of 193, from L100 Series Inverter Instruction Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi L100-040HFU

Page 152

Troubleshooting and Maintenance In This Chapter....

6 page, Troubleshooting............................................... 2, Monitoring Trip Events, History, & Conditions . 5, Restoring Factory Default Settings ................. 8, Maintenance and Inspection ........................... 9, Warranty........................................................ 16

Page 153

Troubleshooting and Maintenance

6–2

Troubleshooting

Troubleshooting Safety Messages Please read the following safety messages before troubleshooting or performing maintenance on the inverter and motor system. WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock. WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement. Before starting to work, remove any metallic objects from your person (wristwatch, bracelet, etc.). Be sure to use tools with insulated handles. Otherwise, there is a danger of electric shock and/or injury to personnel. WARNING: Never remove connectors by pulling on its wire leads (wires for cooling fan and logic P.C.board). Otherwise, there is a danger of fire due to wire breakage and/or injury to personnel.

General Precautions and Notes • Always keep the unit clean so that dust or other foreign matter does not enter the inverter. • Take special care in regard to breaking wires or making connection mistakes. • Firmly connect terminals and connectors. • Keep electronic equipment away from moisture and oil. Dust, steel filings and other foreign matter can damage insulation, causing unexpected accidents, so take special care.

Inspection Items This chapter provides instructions or checklists for these inspection items: • Daily inspection • Periodic inspection (approximately once a year) • Insulation resistance test

Page 154

L100 Inverter

6–3

Troubleshooting Tips

Symptom/condition

Probable Cause

Solution

• Is the frequency command source

• Make sure the parameter

A_01 parameter setting correct? • Is the Run command source A_02 parameter setting correct?

setting A_01 is correct. • Make sure the parameter setting A_02 is correct.

• Is power being supplied to termi-

• Check terminals [L1], [L2], nals [L1], [L2], and [L3/N]? If so, the POWER lamp should be ON.

and [L3/N], then [U/T1], [V/T2], and [W/T3]. • Turn ON the power supply or check fuses.

• Is there an error code E X X displayed? The inverter outputs [U], [V], [W] are not • Are the signals to the intelligent supplying input terminals correct? voltage. • Is the Run Command active? The motor • Is the [FW] terminal (or [RV]) will not run. connected to [P24] (via switch, etc.)

• Press the Func. key and determine the error type. Eliminate the error cause, then clear the error (Reset).

• Verify the terminal functions for C_01 – C_05 are correct. • Turn ON Run Command enable. • Supply 24V to [FW] or [RV] terminal, if configured.

• Has the frequency setting for F_01

• Set the parameter for F_01 been set greater than zero? • Are the control circuit terminals [H], [O], and [L] connected to the potentiometer?

to a safe, non-zero value. • If the potentiometer is the frequency setting source, verify voltage at [O] > 0V.

• Is the RS (reset) function or FRS

• Turn OFF the command(s).

(free-run stop) function ON? Inverter outputs [U], [V], [W] are supplying voltage.

• Is the motor load too heavy?

The optional remote operator is used (SRW).

• Are the operational settings motor independently.

between the remote operator and the inverter unit correct?

• Are the connections of output

The direction of the motor is reversed.

• Reduce load, and test the terminals [U/T1], [V/T2], and [W/T3] correct? • Is the phase sequence of the motor forward or reverse with respect to [U/T1], [V/T2], and [W/T3]?

• Check the operator type setting.

• Make connections according to the phase sequence of the motor. In general: FWD = U-V-W, and REV=U-W-V.

• Are the control terminals [FW] and • Use terminal [FW] for [RV] wired correctly? • Is parameter F_04 properly set?

forward, and [RV] for reverse. • Set motor direction in F_04.

Troubleshooting and Maintenance

The table below lists typical symptoms and the corresponding solution(s).

Page 155

6–4

Troubleshooting

Troubleshooting and Maintenance

Symptom/condition

Probable Cause

• If using the analog input, is the current or voltage at [O] or [OI]?

Solution

• Check the wiring. • Check the potentiometer or signal generating device.

• Is the load too heavy? The motor speed will not reach the target frequency (desired speed).

overload restriction feature (reduces output as needed).

• Is the inverter internally limiting the output frequency?

• Is the load fluctuation too great? The rotation is unstable.

• Was power turned OFF after a

Inverter data is not correct.

A parameter will not change after an edit (reverts to old setting).

• Check max frequency setting (A_04) • Check frequency upper limit setting (A_61)

• Increase the motor capacity

(both inverter and motor). • Is the supply voltage unstable? • Fix power supply problem. • Is the problem occurring at a partic- • Change the output ular frequency? frequency slightly, or use the jump frequency setting to skip the problem frequency.

The RPM of the motor does not • Is the maximum frequency setting match the inverter output A_04 correct? frequency setting. • Does the monitor function D_01 display the expected output frequency?

No downloads have occurred.

• Reduce the load. • Heavy loads activate the parameter edit but before pressing the Store key?

• Edits to data are permanently stored at power down. Was the time from power OFF to power ON less than six seconds?

• Verify the V/f settings match motor specifications.

• Make sure all scaling (such as A_11 to A_14) is properly set.

• Edit the data and press the Store key once.

• Wait six seconds or more before turning power OFF after editing data.

A download to the inverter was attempted.

• Was the power turned OFF within

• Copy the data to the inverter six seconds after the display changed from REMT to INV?

again, and keep power ON for six seconds or more after copying.

True for certain parameters

• Is the inverter in Run Mode? Some • Put inverter in Stop Mode

True for all parameters

• If you’re using the [SFT] intelligent • Change the state of the SFT parameters cannot be edited during Run Mode. input (software lock function) - is the [SFT] input ON?

(press the Stop/reset key). Then edit the parameter. input, and check the B_31 parameter (SFT mode).

Page 156

L100 Inverter

6–5

Fault Detection and Clearing The microprocessor in the inverter detects a variety STOP RESET of fault conditions and captures the event, recordRun Stop ing it in a history table. The inverter output turns RUN OFF, or “trips” similar to the way a circuit breaker STOP trips due to an over-current condition. Most faults RESET Fault occur when the motor is running (refer to the Trip Fault diagram to the right). However, the inverter could have an internal fault and trip in Stop Mode. In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you can clear the inverter’s cumulative trip history by performing the procedure “Restoring Factory Default Settings” on page 6–8 (setting B_84=00 will clear the trip history but leave inverter settings intact).

Error Codes An error code will appear on the display automatically when a fault causes the inverter to trip. The following table lists the cause associated with the error. Error Code

E 01 E 02 E 03 E 04

Name

Cause(s)

Over current event while at constant speed

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF.

Over current event during deceleration Over current event during acceleration

The dual-voltage motor is wired incorrectly.

Over current event during other conditions

E 05

Overload protection

When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.

E 07

Over voltage protection

When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.

E 08

EEPROM error

When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.

E 09

Under-voltage error

A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its output.

CPU error

A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.

E1 1 E22

Troubleshooting and Maintenance

Monitoring Trip Events, History, & Conditions

Page 157

Troubleshooting and Maintenance

6–6

Monitoring Trip Events, History, & Conditions

Error Code

Name

Cause(s)

E1 2

External trip

A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.

E1 3

USP

When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode until the error is cleared.

E1 4

Ground fault

The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests. This feature protects the inverter, and does not protect humans.

E1 5

Input over-voltage

When the input voltage is higher than the specified value, it is detected 100 seconds after powerup and the inverter trips and turns OFF its output.

E21

Inverter thermal trip

When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF.

E35

Thermistor

When a thermistor is connected to terminals [5] and [L] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output.

(brown- - - Under-voltage out) with output shutoff

Due to low input voltage, the inverter turns its output OFF and tries to restart. If it fails to restart, then the alarm trips to record the under-voltage error event.

NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct. If the power is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPROM error will occur when power is restored.

Page 158

6–7

L100 Inverter

Trip History and Inverter Status

The following Monitor Menu map shows how to access the error codes. When fault(s) exist, you can review their details by first selecting the proper function: D_08 displays current trip data, and D_09 displays trip history. Monitor Menu

2

2 d 08

1 d 01

2

1

FUNC.

d 09

FUNC.

Current Trip Conditions Error exists?

No

E 09

No No history

Yes Error Code

FUNC.

1 0.0

Trip History Error(n-1) exists?

Yes

Output frequency at trip point

2

E 03

Previous error #1

___ FUNC.

FUNC.

FUNC.

0.25

Motor current at trip point

FUNC.

1 8 9.8

DC bus voltage at trip point

Error(n-2) exists?

No No history

Yes

FUNC.

E 05 ___ FUNC.

No error

FUNC.

Previous error #2

___ FUNC.

Troubleshooting and Maintenance

We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor functions (D_xx) and select D_08 for details about the present fault (En), or the error code for the past two trip events (En-1 and En-2) using the D_09 Trip History function.

Page 159

Troubleshooting and Maintenance

6–8

Restoring Factory Default Settings

Restoring Factory Default Settings You can restore all inverter parameters to the original factory (default) settings for the intended country of use. After initializing the inverter, use the powerup test in Chapter 2 to get the motor running again. To initialize the inverter, follow the steps below. No.

Action

1

Use the FUNC. , 1 , and 2 keys to navigate to the “B” Group.

2

Press the FUNC. key.

3

Press and hold the

4

Press the FUNC. key.

5

Confirm the country code is correct. Do not change it unless you are absolutely sure the power input voltage range and frequency match the country code setting.

1

Display key until -> b - -

“B” Group selected b 01

First “B” parameter selected b 85

Country code for initialization selected

02

To change the country code, press

1

Func./Parameter or

2

00 = Japan, 01 = Europe, 02 = U.S.

to set, STR to store.

b 85

Country code for initialization selected key.

b 84

Initialization function selected

8

Press the FUNC. key.

00

00 = initialization disabled, clear fault history only

9

Press the key.

01

01 = initialization enabled

10

Press the STR key.

b 84

Initialization now enabled to restore all defaults

11

Press and hold the FUNC. , b 84

First part of special key sequence b 84

Final part of special key sequence d 01

Initialization begins when display starts blinking

6

Press the FUNC. key.

7

Press the

2

12

2

1

1

, and keys. Do not release yet.

Holding the keys above, press and STOP hold the RESET (STOP) key for 3 sec. 13

STOP Release only the RESET (STOP) key, and wait for the display d 0 1 to appear and begin blinking.

14

Now release the FUNC. ,

15

Initialization is complete.

, and 2 keys only after the d 0 1 display function begins blinking. 1

EU USA d 01

Default parameter country code shown during initialization process (left-most char displays alternating pattern) Function code for output frequency monitor shown

NOTE: Initialization cannot be performed with a remote operator panel. Disconnect the device and use the inverter’s front panel keypad.