Page 160

L100 Inverter

6–9

Monthly and Yearly Inspection Chart Inspection Cycle

Item Inspected

Check for... Month

Control circuit

Criteria

Ambient environment

Extreme temperatures & humidity

✔

Thermometer, hygrometer

Ambient temperature between -10 to 40°C, non-condensing

Major devices

Abnormal noise & vib.

✔

Visual and aural

Stable environment for electronic controls

Power supply voltage

Voltage tolerance

✔

Digital volt meter, measure between inverter terminals [L1], [L2], [L3]

200V class: 200 to 240V 50/60 Hz 400V class: 380 to 460V 50/60 Hz

Ground Insulation

Adequate resistance

✔

Digital volt meter, GND to terminals

5 Meg. Ohms or greater

Mounting

No loose screws

✔

Torque wrench

M3: 0.5 – 0.6 Nm M4: 0.98 – 1.3 Nm M5: 1.5 – 2.0 Nm

Components

Overheating

✔

Thermal trip events

No trip events

Housing

Dirt, dust

✔

Visual

Vacuum dust and dirt

✔

Visual

No abnormalities

Visual

No abnormalities

Overall

Main circuit

Year

Inspection Method

Terminal block Secure connections ✔

Smoothing capacitor

Leaking, swelling

Relay(s)

Chattering

✔

Aural

Single click when switching ON or OFF

Resistors

Cracks or discoloring

✔

Visual

Use Ohm meter to check braking resistors

Cooling fan

Noise

✔

Power down, manually rotate

Rotation must be smooth

Dust

✔

Visual

Vacuum to clean

Visual

No abnormalities

✔

Overall

No odor, discoloring, corrosion

Capacitor

No leaks or deformation

✔

Visual

Undistorted appearance

Legibility

✔

Visual

All LED segments work

Display LEDs

Note 1: Note 2:

The life of a capacitor is affected by the ambient temperature. See “Capacitor Life Curve” on page 6–11. The inverter must be cleaned periodically. If dust accumulates on the fan and heat sink, it can cause overheating of the inverter.

Troubleshooting and Maintenance

Maintenance and Inspection

Page 161

6–10

Maintenance and Inspection

Troubleshooting and Maintenance

Megger Test The megger is a piece of test equipment that uses a high voltage to determine if an insulation degradation has occurred. For inverters, it is important that the power terminals be isolated from the Earth GND terminal via the proper amount of insulation. The circuit diagram below shows the inverter wiring for performing the megger test. Just follow the steps to perform the test: 1. Remove power from the inverter and wait at least 5 minutes before proceeding. 2. Open the front housing panel to access the power wiring. 3. Remove all wires to terminals [R, S, T, +1, +, –, U, V, and W]. Most importantly, the input power and motor wires will be disconnected from the inverter. 4. Use a bare wire and short terminals [R, S, T, +1, +, –, U, V, and W] together as shown in the diagram. 5. Connect the megger to the inverter Earth GND and to the shorted power terminals as shown. Then perform the megger test at 500 VDC and verify 5MΩ or greater resistance. Add test jumper wire Disconnect power source

Disconnect motor wires

L100 R

U

S

V

T

W +1

Motor

Megger, 500VDC

+ – Earth GND

6. After completing the test, disconnect the megger from the inverter. 7. Reconnect the original wires to terminals [R, S, T, +1, +, –, U, V, and W]. CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter. CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground.

Page 162

L100 Inverter

6–11

Spare parts

Quantity Part description

Symbol

Notes Used

Spare

Cooling fan

FAN

1

1

022NF, 037LF, 015HF to 075HF

Case

CV

1

1

• Front case • Key cover • Case • Bottom cover

Capacitor Life Curve The DC bus inside the inverter uses a large capacitor as shown in the diagram below. The capacitor handles high voltage and current as it smooths the power for use by the inverter. So, any degradation of the capacitor will affect the performance of the inverter. Power Input

Variable-frequency Drive Converter

L1 L2

Internal DC Bus

Inverter

Motor

+

+

Rectifier

U/T1 V/T2

L3

W/T3 –

Capacitor

Capacitor life is reduced in higher ambient temperatures, as the graph below demonstrates. Be sure to keep the ambient temperature at acceptable levels, and perform maintenance inspections on the fan, heat sink, and other components. If the inverter is installed on a cabinet, the ambient temperature is the temperature inside the cabinet. Capacitor Life Curve

40 Ambient temperature, °C

Operation for 12 hours/day

30 20 10 0 -10 1

2

3

4

5

6

7

8

9

10

Years

Troubleshooting and Maintenance

We recommend that you stock spare parts to reduce down time, including these parts:

Page 163

6–12

Maintenance and Inspection

Troubleshooting and Maintenance

General Inverter Electrical Measurements The following table specifies how to measure key system electrical parameters. The diagrams on the next page show inverter-motor systems and the location of measurement points for these parameters. Parameter

Circuit location of measurement

Measuring instrument

Notes

Reference Value

Supply voltage E1

ER – across L1 and L2 ES – across L2 and L3 ET – across L3 and L1

Fundamental Moving-coil type voltmeter or wave effective value rectifier type voltmeter

Supply current I1

Ir – L1, Is – L2, It – L3

Total effective value, Supply power W1

W11 – across L1 and L2 W12 – across L2 and L3

Total effective value, Supply power factor Pf1

Commercial supply voltage (200V class) 200– 240V, 50/60 Hz 400V class 380– 460V, 50/60 Hz, W1 Pf 1 = ----------------------------- × 100% 3 × E1 × I1

Output voltage E0

EU – across U and V EV – across V and W EW – across W and U

Rectifier type voltmeter

Total effective value, Output current Io

IU – U IV – V IW – W

Moving-coil ammeter

Total effective value, Output power Wo

W01 – across U and V W02 – across V and W

Electronic type wattmeter

Total effective value, Output power factor Pfo

Calculate the output power factor from the output voltage E, output current I, and output power W., W0 Pf 0 = ----------------------------- × 100% 3 × E0 × I0 Note 1: Note 2:

Note 3:

Use a meter indicating a fundamental wave effective value for voltage, and meters indicating total effective values for current and power. The inverter output has a distorted waveform, and low frequencies may cause erroneous readings. However, the measuring instruments and methods listed above provide comparably accurate results. A general-purpose digital volt meter (DVM) is not usually suitable to measure a distorted waveform (not pure sinusoid).

Page 164

L100 Inverter

6–13

Single-phase Measurement Diagram Inverter L1

L1

I1

U

T1

I1 EU-V

E1

W1

V

T2

I1 EU-V

N

N

W

W01 Motor

W02 T3

I1 EU-V

Three-phase Measurement Diagram Inverter L1

R

I1 E1

L2

L3

EU-V S

E1

V

T2

EU-V W

W01

I1

W02 T

I3

T1

I1

W01

I2 E1

U

W02 T3

I1 EU-V

Motor

Troubleshooting and Maintenance

The figures below show measurement locations for voltage, current, and power measurements listed in the table on the previous page. The voltage to be measured is the fundamental wave effective voltage. The power to be measured is the total effective power.

Page 165

6–14

Maintenance and Inspection

Troubleshooting and Maintenance

Inverter Output Voltage Measurement Techniques Taking voltage measurements around drives equipment requires the right equipment and a safe approach. You are working with high voltages and high-frequency switching waveforms that are not pure sinusoids. Digital voltmeters will not usually produce reliable readings for these waveforms. And, it is usually risky to connect high voltage signals to oscilloscopes. The inverter output semiconductors have some leakage, and no-load measurements produce misleading results. So, we highly recommend using the following circuits to measure voltage for performing the equipment inspections. Voltage measurement with load

L2/S

Inverter

L3/T

U/T1

L1/R

U/T1

L1/R

Voltage measurement without load

V/T2

L2/S

W/T3

L3/T

Inverter

V/T2 W/T3

Additional resistor

220 kΩ 2W

220 kΩ 2W

+

V Class

Diode Bridge

5 kΩ 30W

–

+

Voltmeter

V Class

200V Class

600V 0.01A min. 300V range

200V Class

600V 0.01A min. 300V range

400V Class

100V 0.1A min.

400V Class

100V 0.1A min.

600V range

Diode Bridge

–

Voltmeter

600V range

HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working with the inverters and taking measurements. Be sure to place the measurement circuitry components above in an insulated housing before using them.

Page 166

6–15

L100 Inverter

IGBT Test Method 1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and W]. 2. Disconnect any wires from terminals [+] and [–] for regenerative braking. 3. Use a Digital Volt Meter (DVM) and set it for 1Ω resistance range. You can check the status of the charging state of terminals [R, S, T, U, V, W, +, and –] of the inverter and the probe of the DVM by measuring the charging state. D1

D2

[+1] [+] D3

[R]

TR1

TR2

TR3

[U]

+

[S]

[V]

[T]

[W]

D4

D5

TR4

D6

TR5

TR6

[–]

Table Legend – Almost infinite resistance: ≅ ∞ Ω Almost zero resistance: ≅ 0 Ω DVM Part D1

D2

D3

D4

DVM

Measured Value

Part D5

+

–

[R]

+1

≅∞Ω

+1

[R]

≅0Ω

[S]

+1

≅∞Ω

+1

[S]

≅0Ω

[T]

+1

≅∞Ω

+1

[T]

≅0Ω

[R]

[N]

≅0Ω

[N]

[R]

≅∞Ω

D6

TR1

TR2

TR3

DVM

Measured Value

Part TR4

+

–

[S]

[N]

≅0Ω

[N]

[S]

≅∞Ω

[T]

[N]

≅0Ω

[N]

[T]

≅∞Ω

[U]

[+]

≅∞Ω

[+]

[U]

≅0Ω

[V]

[+]

≅∞Ω

[+]

[V]

[W] [+]

Measured Value

+

–

[U]

[–]

≅0Ω

[–]

[U]

≅∞Ω

[V]

[–]

≅0Ω

[–]

[V]

≅∞Ω

[W]

[–]

≅0Ω

[–]

[W]

≅∞Ω

[RB]

[+]

≅0Ω

≅0Ω

[+]

[RB]

≅∞Ω

[+]

≅∞Ω

[RB]

[–]

≅0Ω

[W]

≅0Ω

[–]

[RB]

≅0Ω

TR5

TR6

TR7

NOTE: The resistance values for the diodes or the transistors will not be exactly the same, but they will be close. If you find a significance difference, a problem may exist. NOTE: Before measuring the voltage between [+] and [–] with the DC current range, confirm that the smoothing capacitor is discharged fully, then execute the tests.

Troubleshooting and Maintenance

The following procedure will check the inverter transistors (IGBTs) and diodes:

Page 167

Troubleshooting and Maintenance

6–16

Warranty

Warranty Warranty Terms The warranty period under normal installation and handling conditions shall be two (2) years from the date of manufacture (“DATE” on product nameplate), or one (1) year from the date of installation, whichever occurs first. The warranty shall cover the repair or replacement, at Hitachi's sole discretion, of ONLY the inverter that was installed. 1. Service in the following cases, even within the warranty period, shall be charged to the purchaser: a. Malfunction or damage caused by mis-operation or modification or improper repair b. Malfunction or damage caused by a drop after purchase and transportation c. Malfunction or damage caused by fire, earthquake, flood, lightening, abnormal input voltage, contamination, or other natural disasters 2. When service is required for the product at your work site, all expenses associated with field repair shall be charged to the purchaser. 3. Always keep this manual handy; please do not loose it. Please contact your Hitachi distributor to purchase replacement or additional manuals.