The text of a manual · part 19 of 23
L100 Series Inverter Instruction Manual: Troubleshooting and Maintenance, pages 160 to 167
Pages 160 to 167 of 193, from L100 Series Inverter Instruction Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi L100-040HFU
Page 160
L100 Inverter
6–9
Monthly and Yearly Inspection Chart Inspection Cycle
Item Inspected
Check for... Month
Control circuit
Criteria
Ambient environment
Extreme temperatures & humidity
✔
Thermometer, hygrometer
Ambient temperature between -10 to 40°C, non-condensing
Major devices
Abnormal noise & vib.
✔
Visual and aural
Stable environment for electronic controls
Power supply voltage
Voltage tolerance
✔
Digital volt meter, measure between inverter terminals [L1], [L2], [L3]
200V class: 200 to 240V 50/60 Hz 400V class: 380 to 460V 50/60 Hz
Ground Insulation
Adequate resistance
✔
Digital volt meter, GND to terminals
5 Meg. Ohms or greater
Mounting
No loose screws
✔
Torque wrench
M3: 0.5 – 0.6 Nm M4: 0.98 – 1.3 Nm M5: 1.5 – 2.0 Nm
Components
Overheating
✔
Thermal trip events
No trip events
Housing
Dirt, dust
✔
Visual
Vacuum dust and dirt
✔
Visual
No abnormalities
Visual
No abnormalities
Overall
Main circuit
Year
Inspection Method
Terminal block Secure connections ✔
Smoothing capacitor
Leaking, swelling
Relay(s)
Chattering
✔
Aural
Single click when switching ON or OFF
Resistors
Cracks or discoloring
✔
Visual
Use Ohm meter to check braking resistors
Cooling fan
Noise
✔
Power down, manually rotate
Rotation must be smooth
Dust
✔
Visual
Vacuum to clean
Visual
No abnormalities
✔
Overall
No odor, discoloring, corrosion
Capacitor
No leaks or deformation
✔
Visual
Undistorted appearance
Legibility
✔
Visual
All LED segments work
Display LEDs
Note 1: Note 2:
The life of a capacitor is affected by the ambient temperature. See “Capacitor Life Curve” on page 6–11. The inverter must be cleaned periodically. If dust accumulates on the fan and heat sink, it can cause overheating of the inverter.
Troubleshooting and Maintenance
Maintenance and Inspection
Page 161
6–10
Maintenance and Inspection
Troubleshooting and Maintenance
Megger Test The megger is a piece of test equipment that uses a high voltage to determine if an insulation degradation has occurred. For inverters, it is important that the power terminals be isolated from the Earth GND terminal via the proper amount of insulation. The circuit diagram below shows the inverter wiring for performing the megger test. Just follow the steps to perform the test: 1. Remove power from the inverter and wait at least 5 minutes before proceeding. 2. Open the front housing panel to access the power wiring. 3. Remove all wires to terminals [R, S, T, +1, +, –, U, V, and W]. Most importantly, the input power and motor wires will be disconnected from the inverter. 4. Use a bare wire and short terminals [R, S, T, +1, +, –, U, V, and W] together as shown in the diagram. 5. Connect the megger to the inverter Earth GND and to the shorted power terminals as shown. Then perform the megger test at 500 VDC and verify 5MΩ or greater resistance. Add test jumper wire Disconnect power source
Disconnect motor wires
L100 R
U
S
V
T
W +1
Motor
Megger, 500VDC
+ – Earth GND
6. After completing the test, disconnect the megger from the inverter. 7. Reconnect the original wires to terminals [R, S, T, +1, +, –, U, V, and W]. CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter. CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground.
Page 162
L100 Inverter
6–11
Spare parts
Quantity Part description
Symbol
Notes Used
Spare
Cooling fan
FAN
1
1
022NF, 037LF, 015HF to 075HF
Case
CV
1
1
• Front case • Key cover • Case • Bottom cover
Capacitor Life Curve The DC bus inside the inverter uses a large capacitor as shown in the diagram below. The capacitor handles high voltage and current as it smooths the power for use by the inverter. So, any degradation of the capacitor will affect the performance of the inverter. Power Input
Variable-frequency Drive Converter
L1 L2
Internal DC Bus
Inverter
Motor
+
+
Rectifier
U/T1 V/T2
L3
W/T3 –
Capacitor
Capacitor life is reduced in higher ambient temperatures, as the graph below demonstrates. Be sure to keep the ambient temperature at acceptable levels, and perform maintenance inspections on the fan, heat sink, and other components. If the inverter is installed on a cabinet, the ambient temperature is the temperature inside the cabinet. Capacitor Life Curve
40 Ambient temperature, °C
Operation for 12 hours/day
30 20 10 0 -10 1
2
3
4
5
6
7
8
9
10
Years
Troubleshooting and Maintenance
We recommend that you stock spare parts to reduce down time, including these parts:
Page 163
6–12
Maintenance and Inspection
Troubleshooting and Maintenance
General Inverter Electrical Measurements The following table specifies how to measure key system electrical parameters. The diagrams on the next page show inverter-motor systems and the location of measurement points for these parameters. Parameter
Circuit location of measurement
Measuring instrument
Notes
Reference Value
Supply voltage E1
ER – across L1 and L2 ES – across L2 and L3 ET – across L3 and L1
Fundamental Moving-coil type voltmeter or wave effective value rectifier type voltmeter
Supply current I1
Ir – L1, Is – L2, It – L3
Total effective value, Supply power W1
W11 – across L1 and L2 W12 – across L2 and L3
Total effective value, Supply power factor Pf1
Commercial supply voltage (200V class) 200– 240V, 50/60 Hz 400V class 380– 460V, 50/60 Hz, W1 Pf 1 = ----------------------------- × 100% 3 × E1 × I1
Output voltage E0
EU – across U and V EV – across V and W EW – across W and U
Rectifier type voltmeter
Total effective value, Output current Io
IU – U IV – V IW – W
Moving-coil ammeter
Total effective value, Output power Wo
W01 – across U and V W02 – across V and W
Electronic type wattmeter
Total effective value, Output power factor Pfo
Calculate the output power factor from the output voltage E, output current I, and output power W., W0 Pf 0 = ----------------------------- × 100% 3 × E0 × I0 Note 1: Note 2:
Note 3:
Use a meter indicating a fundamental wave effective value for voltage, and meters indicating total effective values for current and power. The inverter output has a distorted waveform, and low frequencies may cause erroneous readings. However, the measuring instruments and methods listed above provide comparably accurate results. A general-purpose digital volt meter (DVM) is not usually suitable to measure a distorted waveform (not pure sinusoid).
Page 164
L100 Inverter
6–13
Single-phase Measurement Diagram Inverter L1
L1
I1
U
T1
I1 EU-V
E1
W1
V
T2
I1 EU-V
N
N
W
W01 Motor
W02 T3
I1 EU-V
Three-phase Measurement Diagram Inverter L1
R
I1 E1
L2
L3
EU-V S
E1
V
T2
EU-V W
W01
I1
W02 T
I3
T1
I1
W01
I2 E1
U
W02 T3
I1 EU-V
Motor
Troubleshooting and Maintenance
The figures below show measurement locations for voltage, current, and power measurements listed in the table on the previous page. The voltage to be measured is the fundamental wave effective voltage. The power to be measured is the total effective power.
Page 165
6–14
Maintenance and Inspection
Troubleshooting and Maintenance
Inverter Output Voltage Measurement Techniques Taking voltage measurements around drives equipment requires the right equipment and a safe approach. You are working with high voltages and high-frequency switching waveforms that are not pure sinusoids. Digital voltmeters will not usually produce reliable readings for these waveforms. And, it is usually risky to connect high voltage signals to oscilloscopes. The inverter output semiconductors have some leakage, and no-load measurements produce misleading results. So, we highly recommend using the following circuits to measure voltage for performing the equipment inspections. Voltage measurement with load
L2/S
Inverter
L3/T
U/T1
L1/R
U/T1
L1/R
Voltage measurement without load
V/T2
L2/S
W/T3
L3/T
Inverter
V/T2 W/T3
Additional resistor
220 kΩ 2W
220 kΩ 2W
+
V Class
Diode Bridge
5 kΩ 30W
–
+
Voltmeter
V Class
200V Class
600V 0.01A min. 300V range
200V Class
600V 0.01A min. 300V range
400V Class
100V 0.1A min.
400V Class
100V 0.1A min.
600V range
Diode Bridge
–
Voltmeter
600V range
HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working with the inverters and taking measurements. Be sure to place the measurement circuitry components above in an insulated housing before using them.
Page 166
6–15
L100 Inverter
IGBT Test Method 1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and W]. 2. Disconnect any wires from terminals [+] and [–] for regenerative braking. 3. Use a Digital Volt Meter (DVM) and set it for 1Ω resistance range. You can check the status of the charging state of terminals [R, S, T, U, V, W, +, and –] of the inverter and the probe of the DVM by measuring the charging state. D1
D2
[+1] [+] D3
[R]
TR1
TR2
TR3
[U]
+
[S]
[V]
[T]
[W]
D4
D5
TR4
D6
TR5
TR6
[–]
Table Legend – Almost infinite resistance: ≅ ∞ Ω Almost zero resistance: ≅ 0 Ω DVM Part D1
D2
D3
D4
DVM
Measured Value
Part D5
+
–
[R]
+1
≅∞Ω
+1
[R]
≅0Ω
[S]
+1
≅∞Ω
+1
[S]
≅0Ω
[T]
+1
≅∞Ω
+1
[T]
≅0Ω
[R]
[N]
≅0Ω
[N]
[R]
≅∞Ω
D6
TR1
TR2
TR3
DVM
Measured Value
Part TR4
+
–
[S]
[N]
≅0Ω
[N]
[S]
≅∞Ω
[T]
[N]
≅0Ω
[N]
[T]
≅∞Ω
[U]
[+]
≅∞Ω
[+]
[U]
≅0Ω
[V]
[+]
≅∞Ω
[+]
[V]
[W] [+]
Measured Value
+
–
[U]
[–]
≅0Ω
[–]
[U]
≅∞Ω
[V]
[–]
≅0Ω
[–]
[V]
≅∞Ω
[W]
[–]
≅0Ω
[–]
[W]
≅∞Ω
[RB]
[+]
≅0Ω
≅0Ω
[+]
[RB]
≅∞Ω
[+]
≅∞Ω
[RB]
[–]
≅0Ω
[W]
≅0Ω
[–]
[RB]
≅0Ω
TR5
TR6
TR7
NOTE: The resistance values for the diodes or the transistors will not be exactly the same, but they will be close. If you find a significance difference, a problem may exist. NOTE: Before measuring the voltage between [+] and [–] with the DC current range, confirm that the smoothing capacitor is discharged fully, then execute the tests.
Troubleshooting and Maintenance
The following procedure will check the inverter transistors (IGBTs) and diodes:
Page 167
Troubleshooting and Maintenance
6–16
Warranty
Warranty Warranty Terms The warranty period under normal installation and handling conditions shall be two (2) years from the date of manufacture (“DATE” on product nameplate), or one (1) year from the date of installation, whichever occurs first. The warranty shall cover the repair or replacement, at Hitachi's sole discretion, of ONLY the inverter that was installed. 1. Service in the following cases, even within the warranty period, shall be charged to the purchaser: a. Malfunction or damage caused by mis-operation or modification or improper repair b. Malfunction or damage caused by a drop after purchase and transportation c. Malfunction or damage caused by fire, earthquake, flood, lightening, abnormal input voltage, contamination, or other natural disasters 2. When service is required for the product at your work site, all expenses associated with field repair shall be charged to the purchaser. 3. Always keep this manual handy; please do not loose it. Please contact your Hitachi distributor to purchase replacement or additional manuals.