Page 45
Inverter Mounting and Installation In This Chapter....
2 page, Orientation to Inverter Features ...................... 2, Basic System Description ............................... 5, Step-by-Step Basic Installation........................ 6, Powerup Test ................................................ 19, Using the Front Panel Keypad ...................... 21
Page 46
2–2
Orientation to Inverter Features
Orientation to Inverter Features Unpacking and Inspection Please take a few moments to unpack your new L100 inverter and perform these steps: 1. Look for any damage that may have occurred during shipping. 2. Verify the contents of the box include: a. One L100 inverter
Inverter Mounting and Installation b. One Instruction Manual with self-adhesive label for the inverter c. One L100 Quick Reference Guide d. One packet of desiccant - discard (not for human consumption) 3. Inspect the specifications label on the side of the inverter. Make sure it matches the product part number you ordered.
Main Physical Features The L100 Series inverters vary in size according to the current output rating and motor size for each model number. All feature the same basic keypad and connector interface for consistent ease of use. The inverter construction has a heat sink at the back of the housing. The larger models include a fan(s) to enhance heat sink performance. The mounting holes are pre-drilled in the heat sink for your convenience. Never touch the heat sink during or just after operation; it can be very hot. The electronics housing and front panel are built onto the front of the heat sink. The front panel has three levels of physical access designed for convenience and safety: • First-level access – for basic use of inverter and editing parameters (power ON) • Second-level access – for editing parameters and wiring control signals (power ON) • Third-level access – for wiring the inverter power supply or motor (power OFF) 1. First-level Access - View the unit just as it came from the box as shown. The four-digit display can show a variety of performance parameters. LEDs indicate whether the display units are Hertz or Amperes. Other LEDs indicate Power (external), and Run/ Stop Mode and Program/Monitor Mode status. Membrane keys Run and Stop/Reset, and a Min/Max frequency control knob control motor operation. These controls and indicators are usually the only ones needed after the inverter installation is complete. You can also access the modular jack for connecting a programming or monitoring device such as a PC (see Chapter 3). And, you can access the two chassis GND screws on the metal tab at the bottom of the inverter.
Page 47
L100 Inverter
2–3
2. Second-level access - Locate the lift tab at the right lower corner of the front panel near the safety warning message. Lift the corner to swing the half-door around to the left. This exposes four more control buttons and some connectors. The FUNC., 1 , 2 , and STR keys allow an operator to access and change the inverter’s functions and parameter values. The 7 and 8-position connectors provide the interface for logic-level control signals. These signals are generally low-voltage in nature and are appropriate for second-level access.
Lift tab for opening door
Control signal connectors
Locate the label sheet that came with the manual. This is a good moment to apply the self-sticking labels as shown below. Adhere the larger label for monitor codes and basic functions to the rear of the half-door panel. Then adhere the remaining trip code label to the area beside the connectors. Be careful not to cover the screw access on models like the one shown.
Inverter Mounting and Installation
Controls for mode and parameter changes
Page 48
Inverter Mounting and Installation
2–4
Orientation to Inverter Features 3. Third-level access - First, ensure no power source of any kind is connected to the inverter. If power has been connected, wait five minutes after powerdown and verify the Power LED is OFF to proceed. Then locate the recessed retention screw on the left side main front panel (it is along the left hinge area on some models, or behind the first access door on others). Use a small screwdriver (Regular or Phillips) to loosen the screw. Swing the door around to the right to reveal the internal components of the drive. The two-level tiered 12-position terminal block accepts wires for the power input and wires to the motor. Notice the housing partition that lifts out to allow full access to the terminals for wiring as shown. Never operate the inverter drive with the partition removed or the full access door opened. The alarm circuit connections are accessible on the 3-position connector near the modular connector on the rear of the main panel door. The nearby relay provides both normallyopen and normally-closed logic for interface to an external alarm. The alarm circuit may carry hazardous live voltages even when the main power to the inverter is OFF. So, never directly touch any terminal or circuit component. A notch in the removable partition serves as the exit path for alarm circuit wiring.
Retention screw
Alarm connector Housing partition
The following sections will describe the system design and guide you through a step-by-step installation process. After the section on wiring, this chapter will show how to use the front panel keys to access functions and edit parameters.
Power and motor connector terminals
Page 49
L100 Inverter
2–5
Basic System Description A motor control system will obviously include a motor and inverter, as well as a breaker or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now. But a system can also have a variety of additional components. Some can be for noise suppression, while others may enhance the inverter’s braking performance. The figure and table below show a system with all the optional components you may need in your finished application. From power supply Function
Breaker / disconnect
A molded-case circuit breaker (MCCB), ground fault interrupter (GFI), or a fused disconnect device. NOTE: The installer must refer to the NEC and local codes to ensure safety and compliance.
Input-side AC Reactor
This is useful in suppressing harmonics induced on the power supply lines and for improving the power factor. WARNING: Some applications must use an inputside AC reactor to prevent inverter damage. See Warning on next page.
Radio noise filter Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on output).
L1
L2
L3 +1
EMI filter (for CE applications, see Appendix D)
Reduces the conducted noise on the power supply wiring between the inverter and the power distribution system. Connect to the inverter primary (input side).
+
Radio noise filter (use in non-CE applications)
This capacitive filter reduces radiated noise from the main power wires in the inverter input side.
DC link choke
Suppresses harmonics generated by the inverter. However, it will not protect the input diode bridge rectifier.
Braking resistor
This is useful for increasing the inverter’s control torque for high duty-cycle (ON-OFF) applications, and improving the decelerating capability.
Inverter RB
T1
GND T2 T3
Radio noise filter Electrical noise interference may occur on nearby equipment such as a radio receiver. This magnetic choke filter helps reduce radiated noise (can also be used on input). Output-side AC reactor
This reactor reduces the vibrations in the motor caused by the inverter’s switching waveforms, by smoothing the waveform to approximate commercial power quality. It is also useful to reduce harmonics when wiring from the inverter to the motor is more than 10m in length.
LCR filter
Sine wave shaping filter for output side.
Motor Thermal switch
NOTE: Note that some components are required for regulatory agency compliance (see Chapter 5 and Appendix C).
Inverter Mounting and Installation
Breaker, MCCB or GFI
Name
Page 50
2–6
Step-by-Step Basic Installation
Inverter Mounting and Installation
WARNING: In the cases below involving a general-purpose inverter, a large peak current can flow on the power supply side, sometimes destroying the converter module: 1.The unbalance factor of the power supply is 3% or higher. 2.The power supply capacity is at least 10 times greater than the inverter capacity (or the power supply capacity is 500 kVA or more). 3.Abrupt power supply changes are expected, due to conditions such as: a. Several inverters are interconnected with a short bus. b. A thyristor converter and an inverter are interconnected with a short bus. c. An installed phase advance capacitor opens and closes. Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightning strike are possible, install a lightning conductor.
Step-by-Step Basic Installation This section will guide you through the following basic steps of installation: 1. Study the warnings associated with mounting the inverter. 2. Select a suitable mounting location. NOTE: If the installation is in an EU country, study the EMC installation guidelines in Appendix C. 3. Place covers over the inverter’s ventilation openings to prevent debris from entering. 4. Check the inverter mounting dimensions for footprint and mounting hole locations. 5. Study the caution and warning messages associated with wiring the inverter. 6. Connect wiring for the inverter power input. 7. Connect wiring to the motor. 8. Remove any covers applied in Step 3 from the inverter’s ventilation openings. CAUTION: The inverter is shipped with a plastic cover over the top vent grill. REMOVE this cover after the installation is complete. Operation with this cover in place will not allow proper cooling, and damage to the inverter may result. 9. Perform a powerup test. 10. Make observations and check your installation.
Page 51
L100 Inverter
2–7
Choosing a Mounting Location 1
Step 1: Study the following caution messages associated with mounting the inverter. This is the time when mistakes are most likely to occur that will result in expensive rework, equipment damage, or personal injury. CAUTION: Be sure to install the unit on flame-resistant material such as a steel plate. Otherwise, there is the danger of fire. CAUTION: Be sure not to place any flammable materials near the inverter. Otherwise, there is the danger of fire.
CAUTION: Be sure to install the inverter in a place that can bear the weight according to the specifications in the text (Chapter 1, Specifications Tables). Otherwise, it may fall and cause injury to personnel. CAUTION: Be sure to install the unit on a perpendicular wall that is not subject to vibration. Otherwise, it may fall and cause injury to personnel. CAUTION: Be sure not to install or operate an inverter that is damaged or has missing parts. Otherwise, it may cause injury to personnel. CAUTION: Be sure to install the inverter in a well-ventilated room that does not have direct exposure to sunlight, a tendency for high temperature, high humidity or dew condensation, high levels of dust, corrosive gas, explosive gas, inflammable gas, grinding-fluid mist, salt damage, etc. Otherwise, there is the danger of fire.
Inverter Mounting and Installation
CAUTION: Be sure not to let the foreign matter enter vent openings in the inverter housing, such as wire clippings, spatter from welding, metal shavings, dust, etc. Otherwise, there is the danger of fire.
Page 52
2–8
Step-by-Step Basic Installation
Ensure Adequate Ventilation 2
Step 2: To summarize the caution messages - you will need to find a solid, non-flammable, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, maintain the specified clearance around the inverter specified in the diagram.
Inverter Mounting and Installation
Clear area
8 cm (3.15”) minimum
10 cm (3.94”) minimum
L100
Air flow
12 cm (4.72”) minimum
10 cm (3.94”) minimum
CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.
Keep Debris Out of Inverter Vents 3
Step 3: Before proceeding to the wiring section, it’s a good time to temporarily cover the inverter’s ventilation openings. Paper and masking tape are all that is needed. This will prevent harmful debris such as wire clippings and metal shavings from entering the inverter during installation. The inverter housing comes from the factory with a snap-in cover on the top of its housing. Ensure it is in place at this time (also to be removed later, unless the installation must have a NEMA rating). Please observe this checklist while mounting the inverter:
Top cover installed
Ventilation holes (both sides)
1. The ambient temperature must be in the range of -10 to 40°C. If the range will be up to 50°C, you will need to set the carrier frequency to 2.1 kHz or less and derate the output current to 80% or less. Chapter 3 covers how to change parameters such as the carrier frequency. Remember to remove the top cover (unless the installation is to have a NEMA rating)! 2. Keep any other heat-producing equipment as far away from the inverter as possible.
Page 53
L100 Inverter
2–9
3. When installing the inverter in an enclosure, maintain the clearance around the inverter and verify that its ambient temperature is within specification when the enclosure door is closed. 4. Do not open the main front panel door at any time during operation.
Check Inverter Dimensions Step 4: Locate the applicable drawing on the following pages for your inverter. Dimensions are given in millimeters (inches) format.
-002NFU -004NFE -004NFU
5(0.20)
4(0.16)
2.5(0.10)
80(3.15)
7(0.28)
107 (4.21) 107 (4.21) 107 (4.21) 107 (4.21)
H= (see H chart)
-002NFE
120(4.72)
H mm (in.) 110(4.33)
L100
MODEL
Inverter Mounting and Installation
67(2.64)
External Dimensions
10(0.39)
4
NOTE: Some inverter housings require two mounting screws, while others require four. Be sure to use lock washers or other means to ensure screws do not loosen due to vibration.