L100 Series Inverter Instruction Manual: Inverter Mounting and Installation, pages 54 to 62

Pages 54 to 62 of 193, from L100 Series Inverter Instruction Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi L100-040HFU

Page 54

2–10

Step-by-Step Basic Installation

Dimensional drawings, continued... 98(3.86)

External Dimensions MODEL -004HFE -004HFU -005NFE -007NFE -007NFU

130(5.12)

118(4.65)

L100

Inverter Mounting and Installation

5(0.20)

4(0.16)

Ground Terminal

7(0.28)

110(4.33)

2.5(0.10) 129(5.08)

10(0.39)

5(0.20)

98(3.86) Air

MODEL -007HFE(No fan) -007HFU(No fan)

130(5.12)

-015HFE -015HFU

118(4.65)

5(0.20)

5(0.20) 4(0.16)

156(6.14)

7(0.28)

110(4.33)

Ground Terminal

FAN

6(0.24)

L100

Air

Page 55

L100 Inverter

2–11

Dimensional drawings, continued... 140(5.51) 128(5.04)

180(7.09)

168(6.61)

L100 -011NFE -015NFE -015NFU

7(0.28)

Ground Terminal

3.5(0.14) 153(6.02)

10(0.39)

5(0.20)

140(5.51) 128(5.04)

L100 -022NFE -022NFU

Air

5(0.20)

164(6.46)

5(0.20)

7(0.28)

-040HFE -040HFU

168(6.61)

-030HFE -037LFU

180(7.08)

-022HFE -022HFU

FAN

6(0.24)

Ground Terminal

Air

Inverter Mounting and Installation

5(0.20)

Page 56

2–12

Step-by-Step Basic Installation

Dimensional drawings, continued... L100 -055LFU -075LFU -055HFU -075HFU -055HFE -075HFE 182(7.17) 160(6.30)

257(10.12)

236(9.29)

7(0.28)

Air Ground Terminal

170(6.69)

7(0.28)

7(0.28)

6(0.24)

Inverter Mounting and Installation

1

Air

NOTE: Model L100-075LFU has (2) fans. All other models in this housing have (1) fan.

Page 57

L100 Inverter

2–13

Prepare for Wiring 5

Step 5: It is very important to perform the wiring steps carefully and correctly. Before proceeding, please study the caution and warning messages below. WARNING: “Use 60/75°C Cu wire only” or equivalent.

WARNING: “Open Type Equipment.”

WARNING: “Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H. HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric shock and/or fire. HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Otherwise, there is a danger of electric shock and/or fire. HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Otherwise, you may incur electric shock and/or fire. HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is not mounted according the instructions given in this manual. Otherwise, there is a danger of electric shock and/or injury to personnel.

Inverter Mounting and Installation

WARNING: “Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes, 240 V maximum.” For models with suffix N or L.

Page 58

2–14

Step-by-Step Basic Installation

Determining Wire and Fuse Sizes The maximum motor currents in your application determines the recommended wire size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other component shown in the “Basic System Description” on page 2–5. The “Signal Lines” column applies to any wire connecting to the two green 7 and 8position connectors just inside the front panel half-door.

Inverter Mounting and Installation

Motor Output (kW/HP)

Applicable equipment

Wiring Inverter Model kW

HP

Power Lines

0.2

1/4

L100-002NFE/NFU

0.4

1/2

L100-004NFE/NFU

0.55

3/4

L100-005NFE

0.75

1

L100-007NFE/NFU

1.1

1 1/2

1.5

2

2.2

Signal Lines

Fuse (UL-rated, class J, 600V)

AWG16 / 1.3 mm2

10A (single ph.) 7A (three ph.)

AWG14 / 2.1 mm2

15A (single ph.) 10A (three ph.)

L100-015NFE/NFU

AWG12 / 3.3 mm2

20A (single ph.) 15A (three ph.)

3

L100-022NFE/NFU

AWG10 / 5.3 mm2

30A (single ph.) 20A (three ph.)

3.7

5

L100-037LFU

AWG12 / 3.3 mm2

5.5

7 1/2

L100-055LFU

AWG10 / 5.3 mm2

7.5

10

L100-075LFU

AWG8 / 8.4 mm2

0.4

1/2

L100-004HFE/HFU

0.75

1

L100-007HFE/HFU

1.5

2

L100-015HFE/HFU

2.2

3

L100-022HFE/HFU

3.0

4

L100-030HFE

4.0

5

L100-040HFE/HFU

5.5

7 1/2

L100-055HFE/HFU

7.5

10

L100-075HFE/HFU

Note 1:

Note 2: Note 3: Note 4:

L100-011NFE

18 to 28 AWG / 0.14 to 0.75 mm2 shielded wire (see Note 4)

30A 40A 50A 3A

AWG16 / 1.3 mm2

6A 10A

AWG14 / 2.1 mm2 AWG12 / 3.3 mm2

15A 20A 25A

Field wiring must be made by a UL-listed and CSA-certified closed-loop terminal connector sized for the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector manufacturer. Be sure to consider the capacity of the circuit breaker to be used. Be sure to use a larger wire gauge if power line length exceeds 66 ft. (20m). Use 18 AWG / 0.75 mm2 wire for the alarm signal wire ([AL0], [AL1], [AL2] terminals).

Page 59

L100 Inverter

2–15

Terminal Dimensions and Torque Specs The terminal screw dimensions for all L100 inverters are listed in table below. This information is useful in sizing spade lug or ring lug connectors for wire terminations. CAUTION: Fasten the screws with the specified fastening torque in the table below. Check for any loosening of screws. Otherwise, there is the danger of fire.

Number of Screw Terminals

Models 005NF– 022NF, 037LF, 004HF–040HF

Models 055LF–075LF, 055HF–075HF

Screw Diameter

Width (mm)

Screw Diameter

Width (mm)

Screw Diameter

Width (mm)

Power Terminals

12

M3.5

7.1

M4

9

M5

13

Control Signal

15

M2, M2, M2, Alarm Signal

3

M3, M3, M3, Ground Terminals

2

M4, M4, M4, When connecting wiring, use the tightening torque listed in the following table to safely attach wiring to the connectors. Screw

Tightening Torque

Screw

Tightening Torque

Screw

Tightening Torque

M2

0.2 N•m (max. 0.25 N•m) M3.5

0.8 N•m (max. 0.9 N•m)

M5

2.0 N•m (max. 2.2 N•m)

M3

0.5 N•m (max. 0.6 N•m)

1.2 N•m (max. 1.3 N•m), - M4

Wire the Inverter Input to a Supply 6

Step 6: In this step, you will connect wiring to the input of the inverter. First, you must determine whether the inverter model you have requires three-phase power only, or if it can accept either single-phase or three-phase power. All models have the same power connector terminals [L1], [L2], and [N/L3]. So, you must refer to the specifications label (on the side of the inverter) for the acceptable power source types! For inverters that can accept singlephase power and are connected that way, terminal [L2] will remain unconnected. The wiring example to the right shows an L100 inverter wired for 3-phase input. Note the use of ring lug connectors for a secure connection.

Inverter Mounting and Installation

Connector

Models 002NF, 004NF

Page 60

2–16

Step-by-Step Basic Installation Please use the terminal arrangement below corresponding to your inverter model. –002NFE/NFU, –004NFE/NFU, –005NFE Jumper

(/) L1

+1 + – L2 N/L3 U/T1 V/T2 W/T3

Inverter Mounting and Installation

Chassis Ground

–007 to 022NFE/NFU, –037LFU, 004 to 040HFE/HFU Jumper

(/)

+1 L1

+ – L2 N/L3 U/T1 V/T2 W/T3 Chassis Ground

–055LFU, –075LFU, 055HFE/HFU, 075HFE/HFU Jumper

(/) +1 + – L1 L2 N/L3 U/T1 V/T2 W/T3 Chassis Ground

NOTE: An inverter powered by a portable power generator may receive a distorted power waveform, overheating the generator. In general, the generator capacity should be five times that of the inverter (kVA). CAUTION: Be sure that the input voltage matches the inverter specifications: • Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) • Three phase 200 to 230V 50/60Hz (above 2.2kW) • Three phase 380 to 460 V 50/60Hz CAUTION: Be sure not to power a three-phase-only inverter with single phase power. Otherwise, there is the possibility of damage to the inverter and the danger of fire.

Page 61

L100 Inverter

2–17

CAUTION: Be sure not to connect an AC power supply to the output terminals. Otherwise, there is the possibility of damage to the inverter and the danger of injury and/or fire. Power Input

Power Output

(L)

T1 T2 T3

(N)

L1 L2 N/L3 U

V W

NOTE: L, N: Single-phase 200 to 240V 50/60 Hz L1, L2, L3: Three-phase 200 to 230V 50/60 Hz Three-phase 380 to 460V 50/60 Hz

CAUTION: Be sure to install a fuse for each phase of the main power supply to the inverter. Otherwise, there is the danger of fire. CAUTION: For motor leads, ground fault interrupter breakers and electromagnetic contactors, be sure to size these components properly (each must have the capacity for rated current and voltage). Otherwise, there is the danger of fire.

Inverter Mounting and Installation

CAUTION: Remarks for using ground fault interrupter breakers in the main power supply: Adjustable frequency inverters with CE-filters (RFI-filter) and shielded (screened) motor cables have a higher leakage current toward Earth GND. Especially at the moment of switching ON this can cause an inadvertent trip of ground fault interrupters. Because of the rectifier on the input side of the inverter there is the possibility to stall the switch-off function through small amounts of DC current. Please observe the following: • Use only short time-invariant and pulse current-sensitive ground fault interrupters with higher trigger current. • Other components should be secured with separate ground fault interrupters. • Ground fault interrupters in the power input wiring of an inverter are not an absolute protection against electric shock.

Page 62

2–18

Step-by-Step Basic Installation

Wire the Inverter Output to Motor 7

Step 7: The process of motor selection is beyond the scope of this manual. However, it must be an AC induction motor with three phases. It should also come with a chassis ground lug. If the motor does not have three power input leads, stop the installation and verify the motor type. Other guidelines for wiring the motor include: • Use an inverter-grade motor for maximum motor life (1600V insulation).

Inverter Mounting and Installation

• For standard motors, use the AC reactor accessory if the wiring between the inverter and motor exceeds 10 meters in length. Simply connect the motor to the terminals [U/T1], [V/T2], and [W/T3] as shown to the right. This is a good time to connect the chassis ground lug on the drive as well. The motor chassis ground must also connect to the same point. Use a star ground (singlepoint) arrangement, and never daisy-chain the grounds (point-to-point). Use the same wire gauge on the motor and chassis ground wiring as you used on the power input wiring in the previous step. After completing the wiring: • Check the mechanical integrity of each wire crimp and terminal connection. • Replace the housing partition that covers access to the power connections.

To Power Supply

To Motor

To Chassis Ground

• Close the main door and secure the retention screw firmly.

Logic Control Wiring After completing the initial installation and powerup test in this chapter, you may need to wire the logic signal connector for your application. For new inverter users/applications, we highly recommend that you first complete the powerup test in this chapter without adding any logic control wiring. Then you will be ready to set the required parameters for logic control as covered in Chapter 4, Operations and Monitoring.