For the Holjeron BBK-DNT128

Page 1

BusBlock Digital I/O Module for DeviceNet™ BBK-4045-1

TECHNICAL DATA

0204

Description The Holjeron BusBlock I/O Module is designed to handle small amounts of I/O in a limited amount of space. The BusBlock I/O Module comes in two versions: twelve inputs/eight outputs and eight inputs/six relay outputs. All I/O is optically isolated from the bus. Field terminations are captive screw terminals. Each input and output has its own LED indication for immediate verification of I/O states.

Specifications Warranty/Remedy

Part Numbers

Seller warrants its products to be free from defects in design, material and workmanship under normal use and service. Seller will repair or replace without charge any such products it finds to be so defective on its return to Seller within 18 months after date of shipment by Seller. The foregoing is in lieu of all other expressed or implied warranties (except title), including those of merchantability and fitness for a particular purpose. The foregoing is also purchaser’s sole remedy and is in lieu of all other guarantees, obligations, or liabilities or any consequences incidental, or punitive damages attributable to negligence or strict liability, all by way of example.

Electrical

While Holjeron provides application assistance, personally and through our literature, it is up to the customer to determine the suitability of the product in the application. All information contained herein, including illustrations, specifications and dimensions, is believed to be reliable as of the date of publication, but is subject to change without notice.

Inputs

Outputs -DNT128

-DNT086

Environmental

Physical

12 Input/8 Output 8 Input/6 Relays DeviceNet™ Voltage Range Current Consumption Data Rates Type Number BBK-DNT128 BBK-DNT086 Voltage Range Maximum Current Isolation Type Number Voltage Range Maximum Current Isolation Type Number Voltage Range Maximum Current Isolation Temperature Storage Operating Humidity Vibration Shock Dimensions Weight Color Case Material Mounting Terminations Indication Power Error Activity I/O

BBK-DNT128 BBK-DNT086 11-25 VDC 60 mA 125, 250, and 500 kbps Current Sinking (Sourcing load) Twelve (12) Eight (8) 10-28 VDC 20 mA per input 1500 Vrms Current Sinking Eight (8) 10-28 VDC 200 mA 1500 Vrms Relay Six (6) 10-125 VDC, 24-240 VAC 2 Amps @ 115 VAC 1500 Vrms -30° to 70° C (-22° to 158° F) 0° to 60° C (32° to 140° F) 5-95% RH, non-condensing 2G at 10 to 500 Hz 10G 5.50" H x 3.48" W x 1.00" D 12 oz Bone Gray Polycarbonate DIN Rail or foot mount Captive Screw Terminal Green Red Green Green th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 2

BusBlock Digital I/O Module for DeviceNet™ BBK-4045-1

TECHNICAL DATA

Page 2

Dimensions

Wiring BBK-DNT128 TOP VIEW

10-30 VDC

0

1

2

3

4

5

6

Out3 LOAD

Out1

Out0

Out2 LOAD

LOAD

LOAD

Out7

Out6 4

LOAD

2 3

LOAD

Out4

Bus-

DC-

Bus+

In11

DC+

In9

LOAD

Act. Error

LOAD

Power

In10

In8

BUS CONNECTOR

Out5

OUTPUT WIRING 5.50

7

Er ro r

0

1

5

6

7

DC+ DC- Bus+ Bus-

Out0 Out1 Out2 Out3

In8

In9

In10 In11

Out4 Out5 Out6 Out7

In4

In5

In6

In7

COM COM COM COM

In0

In1

In2

In3

COM COM COM COM

3.47"

0

8

9

10

2 3

4

5

6 7

8

1 1 9 0 1

11

In3

7

In2

6

In1

5

In0

4

In7

3

In6

2

In5

1

In4

0

1

INPUT WIRING

END VIEW BBK-DNT086 3.53

10-30 VDC 1.77"

Bus-

DC-

Bus+

DC+

BUS CONNECTOR

Er ro r

0

1

2 3

4

5

6

7

2.27" V-

V-

V+

V+

In4

In5

In6

In7

Out0 Out1 Out2 Out3

In0

In1

In2

In3

INPUT WIRING

1

2 3

4

5

6 7

8

1 1 9 0 1

OUTPUT WIRING (Typical of 6)

LOAD

In3

In2

In1

In0

In7

In6

In5

0

In4

Out4 Out5

DC+ DC- Bus+ BusCOM COM COM COM

10-125 VDC 24-240 VAC th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 3

BusBlock Digital I/O Module for DeviceNet™ TECHNICAL DATA

BBK-4045-1

Page 3

Configuration

Quick Start

Operation

A BusBlock module can be configured using several tools. Please consult the documentation for the specific tool for details.

The following steps are the minimum steps to configure BusBlock module. Default values are shown in bold typeface.

The BusBlock I/O Module is a general purpose discrete I/O device functioning as a “Group 2 Only Server”. In addition to explicit messaging, polled I/O and change-of-state/cyclic I/O is supported for the transfer of input and output information. Once a polled connection is established, the module expects a poll at least every 10 seconds, otherwise the module will time out and take action as specified in the watchdog timeout action attribute. The connection timeout can be altered by changing the Expected Packet Rate (EPR) for the polled connection, which is contained in Object 5, Instances 1, attribute 9.

Set MAC ID Using one of the tools described above, change the device address from the default. All units are shipped from the factory as MAC ID 63.

Note Set the address before attaching any component to a complete bus. This will help prevent duplicate MAC IDs on a bus.

The BusBlock I/O Module also supports Offline Connection Set messaging.

th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 4

BusBlock Digital I/O Module for DeviceNet™ BBK-4045-1

Page 4

TECHNICAL DATA

Input Variable The Input Variable is contained in the Assembly Object (Object 4, Instance 4) and is a collection of discrete inputs. The Input Variable gets passed to the host controller as an array of 2 bytes in the BBK-DNT128 and as a single byte in the BBK-DNT086. The inputs can be configured using the Discrete Input Object (Object 8, Instances 1-n).

Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Name Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Input 9 Input 10 Input 11 Reserved Reserved Reserved Reserved

Notes

Discrete Input Object Input State Attribute 3 The current state of the input. This attribute maps to bits 0-7 in the input variable of the BBK-DNT086 and bits 0-11 in the input variable of the BBK-DNT128.

Input NO/NC Attribute 100 When the Input NO/NC is set to a value of 1 the state of the input reported in the input variable will be inverted from the physical input state.

BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only BBK-DNT128 Only th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 5

BusBlock Digital I/O Module for DeviceNet™ BBK-4045-1

TECHNICAL DATA

Page 5

Output Variable The Output Variable is contained in the Assembly Object (Object 4, Instance 34) and is a collection of discrete outputs as defined by the Discrete Output Object (Object 9, Instance 1-4).

Discrete Output Object

Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

This attribute maps to bits 0-5 in the output variable of the BBK-DNT086 and 0-7 in the BBK-DNT128.

Name Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Flasher 0 Flasher 1 Flasher 2 Flasher 3 Flasher 4 Flasher 5 Flasher 6 Flasher 7

Notes

BBK-DNT128 Only BBK-DNT128 Only

BBK-DNT128 Only BBK-DNT128 Only

Output State Attribute 3 The current state of the output.

Fault Action Attribute 5 If the Fault Action is set to 0 when a fault occurs, the output will be set to the state defined in the Fault Value. When set to 1, the outputs will be held at their last state.

Flasher Enable Attribute 10 When the Flasher Enable is set to a value of 1 the associated output will flash when turned on. This attribute maps to bits 8-15 in the output variable.

Flasher Rate Attribute 11 The Flasher Rate is the frequency which the output will flash when enabled and on. The rate is Hertz (cycles per second).

Fault Value Attribute 6 The value for the output when a fault occurs and the Fault Action is set to 0.

Idle Action Attribute 7 When the BusBlock I/O Module is in an idle state (unallocated) and the Idle Action is set to a value of 0, the associated output will be set to the state defined in the Idle Value. If set to a value of 1 the output will be held in its last state.

Idle Value Attribute 8 The value for the output when idle and the Idle Action is enabled.

th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 6

BusBlock Digital I/O Module for DeviceNet™ BBK-4045-1

Common Services Common Services are explicit messaging services for DeviceNet™ with request/response parameters and a defined behavior. Not all Common Services are supported by every object.

TECHNICAL DATA

Page 6

Service Code

Service Name

Description

1 (01hex)

Get_Attributes_All

Returns a pre-defined listing of attributes within an object. Request data includes the object and instance.

5 (05hex)

Reset

Invokes the reset service for the device. Request data includes the object, instance and a single parameter.

14 (0Ehex)

Get_Attribute_Single

Returns the value of a specific attribute within an object. Request data includes the object, instance and attribute number.

16 (10hex)

Set_Attribute_Single

Modifies the value of an attribute within an object that is defined with GET/SET access. Request data includes the object, instance, attribute number and the new value.

17 (11hex)

Find_Next_Object_Instance

Returns a list of all instance ID’s for existing instances of a specific object.

24 (18hex)

Get_Member

Returns the contents of a specific member within an attribute.

th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 7

BusBlock Digital I/O Module for DeviceNet™ TECHNICAL DATA

BBK-4045-1

Page 7

Identity Object

Attributes

Class 1, Instance 1

Attribute Description

1 2 3 4 5 6 7

The Identity Object provides status and general information about a device. The Identity Object is required in all DeviceNet™ products.

Vendor ID Device Type Product Code Revision Status Serial Number Product Name

Data Type

Access

Default Value

UINT UINT UINT USINT [2] WORD UDINT STRING

Get Get Get Get Get Get Get

693

1,1 See table below BusBlock I/O Module

Attribute 5 - Status

Message Router Object

Bit

Name

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Owned Reserved Configured Reserved Reserved Reserved Reserved Reserved Minor Recoverable Fault Minor Unrecoverable Fault Major Recoverable Fault Major Unrecoverable Fault Reserved Reserved Reserved Reserved

Bit Meaning 0 1 Not Owned Allocated

No Fault No Fault No Fault No Fault

Fault Fault Fault Fault

There are no defined attributes for the Message Router Object in the BusBlock I/O Module, nor are there any Common Services.

Class 2, Instance 1

DeviceNet Object

Attributes

Class 3, Instance 1

Attribute Description

1 2 3 4 5

MAC ID (0-63) Baud Rate BOI Bus-Off Counter Allocation Information

Data Type

Access

Default Value

USINT USINT BOOLEAN BYTE BYTE [2]

Get/Set Get/Set Get/Set Get/Set Get

63 0 (125K) 1

Attributes

Assembly Object Class 4, Instance 4 (Inputs) Class 4, Instance 34 (Outputs)

Attribute Description

3

Input Variable

3

Output Variable

Data Type

See the section on Input Variable for mapping and configuration. See the section on Output Variable for mapping and configuration.

th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com

Page 8

BusBlock Digital I/O Module for DeviceNet™ TECHNICAL DATA

BBK-4045-1

Page 8

Connection Object

Attributes

Class 4, Class 5, Instances 1, 2 and 4

Attribute Description

1 2 3 4 5 6 7 8 9 12 13 14 15 16 17

Data Type

State BYTE Instance Type BYTE Transport Class Trigger BYTE Produced Connection ID BYTE Consumed Connection ID BYTE Initial Communications BYTE Characteristics Produced Connection Size INTEGER Consumed Connection Size INTEGER Expected Packet Rate INTEGER Watchdog Timeout Action BYTE Produced Connection Path UINT Length Produced Connection Path Consumed Connection Path UINT Length Consumed Connection Path Production Inhibit Time UINT

Access

Default Value

Get Get Get Get Get Get

01h 01h 82h

Get Get Get/Set Get/Set Get

FFFFh 01h

00 00

Get Get Get Get/Set

00

Discrete Input Object

Attributes

Class 8, Instances 1-8 (BBK-DNT086) Class 8, Instances 1-12 (BBK-DNT128)

Attribute Description

Data Type

Access

Default Value

3 100

BOOLEAN BOOLEAN

Get Get/Set

0 [disabled]

Data Type

Access

Default Value

BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BYTE

Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set

0 [Fault Value attribute] 0 0 [Idle Value attribute] 0 0 [disabled]

Input State Input NO/NC

Discrete Output Object

Attributes

Class 9, Instances 1-6 (BBK-DNT086) Class 9, Instances 1-8 (BBK-DNT128)

Attribute Description

3 5 6 7 8 10 11

Output State Fault Action Fault Value Idle Action Idle Value Enable Flash Flash Rate (Hertz)

th Holjeron • 25599 SW 95 Avenue, Suite E • Wilsonville, OR 97070 • 503.582-0820 • Fax 503.582-9166 • www.holjeron.com