Manual · ITT Controls
Neo-Dyn Models 122P, 123P, 130P, 131P, 132P, 181P, 231P, 232P Adjustable Pressure Switches; Model 125P and 225P Factory Set Pressure Switches; Enclosure 6N for Explosive Atmospheres: Installation and Operation Manual
Manual19 pagesPDF 432 KB
Installation and operation manual for ITT Neo-Dyn Enclosure 6N explosion-proof pressure switches, including the factory-set Model 125P.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
The ITT Neo-Dyn installation and operation manual for Enclosure 6N weather and explosion-proof pressure switches: adjustable Models 122P, 123P, 130P, 131P, 132P, 181P (vacuum), 231P and 232P, and factory-set tamperproof Models 125P and 225P. It covers mounting, process connections and media, use in potentially explosive atmospheres, electrical connections, setpoint adjustment, troubleshooting, full specifications and warranty information.
Its parts
- Introduction
- Installation
- Adjustments After Installation
- Troubleshooting
- Specifications
- Warranty Information
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Neo-Dyn installation and operation manual (PN 610-0009 Rev K) for Enclosure 6N pressure switches for explosive atmospheres: adjustable models 122P, 123P, 130P, 131P, 132P, 181P, 231P and 232P, and factory-set models 125P and 225P. It does not print the number 125P1S473. It explains mounting, process and electrical connections, setpoint adjustment, troubleshooting, part numbers and specifications.
- Device
- 125P: factory-set tamperproof pressure switch with no setpoint adjustment p. 4
- Electrical rating
- Standard switch: up to 11 amp at 125 or 250 VAC, 5 amp resistive at 28 VDC, or 0.5 amp resistive at 125 VDC p. 4
- Pressure port
- 125P: ¼-18 NPT female p. 7
- Weight
- Approximately 20 ounces (0.6 kg) with an aluminum alloy body p. 12
- Leads
- 18 AWG free leads 18 in (46 cm) long, green wire grounded to the case, factory sealed; 72 inch (183 cm) leads as R Option p. 8
- Approvals
- The manual states Zone 1, Ex db IIC, and Division 1; Class 1, Groups A, B, C and D; Class II, Groups E, F and G p. 8
- Enclosure
- The manual states IP66 and NEMA type 3, 3R, 3S, 4, 4X, 13 p. 17
- Form C6N rating
- SPDT: 11 amp @ 125 or 250 VAC to +70 °C (+158 °F) max, T5, or to +60 °C (+140 °F) max, T6 p. 17
- Form CC6N rating
- DPDT: 11 amp @ 125 or 250 VAC to +65 °C (+149 °F) max, T4A, or to +45 °C (+113 °F) max, T6 p. 17
- M Option contacts
- Gold contacts rated to one amp for milliampere and microampere currents; 1 amp @ 125 VAC to +70 °C max, T6 p. 4, 17
- Wetted materials
- 125P: option 1 aluminum alloy port or option 4 UNS S31600 CRES port, with teflon-coated polyimide diaphragm and nitrile O-ring p. 13
- Panel mounting
- 125P: .190 in. (no. 10) or M5 fasteners through mounting holes 1.125 in. (28.6 mm) apart p. 6
- Media temperature
- Standard nitrile O-rings: -40°C (-40°F) to +121°C (+250°F); B Option Viton O-rings: -26°C (-15°F) to +121°C (+250°F) p. 17
- Minimum ambient
- -40 °C (-40 °F); -26°C (-15°F) with B Option or Kalrez O-rings p. 17
What this manual walks you through
- Mounting the switch on the process line or a wall or panel p. 6
- Making the process connections p. 7
- Wiring the free leads in conduit p. 8
- Adjusting and checking setpoints on the adjustable models p. 9, 10
- Troubleshooting leaks, failure to switch and calibration shifts p. 11
- Decoding the part number and wetted material codes p. 13, 14
- Looking up pressure ratings by model and range p. 14, 15, 16
- Choosing options such as gold contacts and long leads p. 18
Good to know
- Models 125P and 225P have no setpoint adjustment; the pressure and electrical limits marked on the unit apply. p. 5
- The switches must be installed by a qualified electrician under local and national electrical codes. p. 6
- The switch must not be removed while under pressure. p. 6
- The marked maximum operating pressure is not to be exceeded; relief valves are set below the marked proof pressure. p. 7
- Wiring must be protected by metal conduit or equivalent and not put under tension or torque. p. 2
Questions this manual answers
Can the setpoint of a Neo-Dyn 125P be adjusted?
No. The 125P is a tamperproof factory-set unit with no provision for setpoint adjustment. p. 5
What thread is the 125P pressure port?
¼-18 NPT female is standard on the 125P. p. 7
What lead wires come on the Enclosure 6N 125P?
18 AWG free leads 18 in (46 cm) long with a green wire grounded to the case; 72 inch (183 cm) leads are the R Option. p. 8
How do I check a Neo-Dyn pressure switch for a leak?
Isolate the switch and a calibrated gauge at normal system pressure for at least one minute and watch for a drop; return a leaking unit for repair. p. 11
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file