Page 1 of Neo-Dyn Models 122P, 123P, 130P, 131P, 132P, 181P, 231P, 232P Adjustable Pressure Switches; Model 125P and 225P Factory Set Pressure Switches; Enclosure 6N for Explosive Atmospheres: Installation and Operation Manual

Manual · ITT Controls

Neo-Dyn Models 122P, 123P, 130P, 131P, 132P, 181P, 231P, 232P Adjustable Pressure Switches; Model 125P and 225P Factory Set Pressure Switches; Enclosure 6N for Explosive Atmospheres: Installation and Operation Manual

Manual19 pagesPDF 432 KB

Installation and operation manual for ITT Neo-Dyn Enclosure 6N explosion-proof pressure switches, including the factory-set Model 125P.

Download the PDF432 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

The ITT Neo-Dyn installation and operation manual for Enclosure 6N weather and explosion-proof pressure switches: adjustable Models 122P, 123P, 130P, 131P, 132P, 181P (vacuum), 231P and 232P, and factory-set tamperproof Models 125P and 225P. It covers mounting, process connections and media, use in potentially explosive atmospheres, electrical connections, setpoint adjustment, troubleshooting, full specifications and warranty information.

Its parts

  1. Introduction
  2. Installation
  3. Adjustments After Installation
  4. Troubleshooting
  5. Specifications
  6. Warranty Information

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Neo-Dyn installation and operation manual (PN 610-0009 Rev K) for Enclosure 6N pressure switches for explosive atmospheres: adjustable models 122P, 123P, 130P, 131P, 132P, 181P, 231P and 232P, and factory-set models 125P and 225P. It does not print the number 125P1S473. It explains mounting, process and electrical connections, setpoint adjustment, troubleshooting, part numbers and specifications.

Device
125P: factory-set tamperproof pressure switch with no setpoint adjustment p. 4
Electrical rating
Standard switch: up to 11 amp at 125 or 250 VAC, 5 amp resistive at 28 VDC, or 0.5 amp resistive at 125 VDC p. 4
Pressure port
125P: ¼-18 NPT female p. 7
Weight
Approximately 20 ounces (0.6 kg) with an aluminum alloy body p. 12
Leads
18 AWG free leads 18 in (46 cm) long, green wire grounded to the case, factory sealed; 72 inch (183 cm) leads as R Option p. 8
Approvals
The manual states Zone 1, Ex db IIC, and Division 1; Class 1, Groups A, B, C and D; Class II, Groups E, F and G p. 8
Enclosure
The manual states IP66 and NEMA type 3, 3R, 3S, 4, 4X, 13 p. 17
Form C6N rating
SPDT: 11 amp @ 125 or 250 VAC to +70 °C (+158 °F) max, T5, or to +60 °C (+140 °F) max, T6 p. 17
Form CC6N rating
DPDT: 11 amp @ 125 or 250 VAC to +65 °C (+149 °F) max, T4A, or to +45 °C (+113 °F) max, T6 p. 17
M Option contacts
Gold contacts rated to one amp for milliampere and microampere currents; 1 amp @ 125 VAC to +70 °C max, T6 p. 4, 17
Wetted materials
125P: option 1 aluminum alloy port or option 4 UNS S31600 CRES port, with teflon-coated polyimide diaphragm and nitrile O-ring p. 13
Panel mounting
125P: .190 in. (no. 10) or M5 fasteners through mounting holes 1.125 in. (28.6 mm) apart p. 6
Media temperature
Standard nitrile O-rings: -40°C (-40°F) to +121°C (+250°F); B Option Viton O-rings: -26°C (-15°F) to +121°C (+250°F) p. 17
Minimum ambient
-40 °C (-40 °F); -26°C (-15°F) with B Option or Kalrez O-rings p. 17

What this manual walks you through

  • Mounting the switch on the process line or a wall or panel p. 6
  • Making the process connections p. 7
  • Wiring the free leads in conduit p. 8
  • Adjusting and checking setpoints on the adjustable models p. 9, 10
  • Troubleshooting leaks, failure to switch and calibration shifts p. 11
  • Decoding the part number and wetted material codes p. 13, 14
  • Looking up pressure ratings by model and range p. 14, 15, 16
  • Choosing options such as gold contacts and long leads p. 18

Good to know

  • Models 125P and 225P have no setpoint adjustment; the pressure and electrical limits marked on the unit apply. p. 5
  • The switches must be installed by a qualified electrician under local and national electrical codes. p. 6
  • The switch must not be removed while under pressure. p. 6
  • The marked maximum operating pressure is not to be exceeded; relief valves are set below the marked proof pressure. p. 7
  • Wiring must be protected by metal conduit or equivalent and not put under tension or torque. p. 2

Questions this manual answers

Can the setpoint of a Neo-Dyn 125P be adjusted?

No. The 125P is a tamperproof factory-set unit with no provision for setpoint adjustment. p. 5

What thread is the 125P pressure port?

¼-18 NPT female is standard on the 125P. p. 7

What lead wires come on the Enclosure 6N 125P?

18 AWG free leads 18 in (46 cm) long with a green wire grounded to the case; 72 inch (183 cm) leads are the R Option. p. 8

How do I check a Neo-Dyn pressure switch for a leak?

Isolate the switch and a calibrated gauge at normal system pressure for at least one minute and watch for a drop; return a leaking unit for repair. p. 11

How is a 125P mounted to a wall or panel?

With .190 in. (no. 10) or M5 fasteners through its two mounting holes, spaced 1.125 in. (28.6 mm) apart. p. 5, 6

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 1911-19

The file

Revision and size

RevisionPN 610-0009 Rev K, copyright 2002
PublisherITT Industries (Neo-Dyn)
Pages19