Neo-Dyn Models 122P, 123P, 130P, 131P, 132P, 181P, 231P, 232P Adjustable Pressure Switches; Model 125P and 225P Factory Set Pressure Switches; Enclosure 6N for Explosive Atmospheres: Installation and Operation Manual, pages 1 to 10

Pages 1 to 10 of 19

The original document is the PDF (432 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the ITT Controls 125P1S473

Page 1

NEO-DYN MODELS 122P, 123P, 130P, 131P, 132P, 181P, 231P, 232P ADJUSTABLE PRESSURE SWITCHES; MODEL 125P AND 225P FACTORY SET PRESSURE SWITCHES;

ENCLOSURE 6N FOR EXPLOSIVE ATMOSPHERES

INSTALLATION AND OPERATION MANUAL

PN 610-0009 Rev K

Page 2

Manual No. 610-0009 REV K Neo-Dyn® 28150 Industry Drive Valencia, CA 91355 Tel: (661) 295-4000 Fax: (661) 294-1750 World Wide Web: www.neodyn.com ©Copyright 2002 ITT Industries

Important Information The product warranty applicable to this ITT Neo-Dyn® instrument is as stated on the last page of this manual. Should any after-delivery problems arise, please contact ITT Neo-Dyn’s Customer Service using the information above. Our normal business hours are weekdays, 7:00 am to 3:30 PM, Pacific Time. Before installing this Pressure Switch, become familiar with the installation and adjustment instructions in Chapters 2 and 3 WARNING

Indicates a hazard which can cause severe personal injury, death, or substantial property damage if the warning is ignored.

CAUTION

Indicates a hazard which will or can cause minor personal injury or property damage if the caution is ignored.

SPECIAL CONDITIONS FOR SAFE USE The electrical snap switch assemblies shall be installed such that the equipment wiring is protected from mechanical damage by the use of metal conduit or a method providing equivalent protection. The equipment wiring must not be subjected to tension or torque. If it is to be terminated within a potentially explosive atmosphere, a suitably certified termination facility must be used.

NOTE

Indicates additional information about a particular item necessary to the operation of the unit. This document contains proprietary information, which is the property of Neo-Dyn®, a unit of ITT industries. This document may not be reproduced, either in part or in full, without the consent of ITT industries.

Enclosure 6N Pressure Switches Page i

Page 3

TABLE OF CONTENTS CHAPTER 1 INTRODUCTION ............................................................................................................ 1 CUSTOMER SERVICE .................................................................................................................... 2 OTHER CONFIGURATIONS .......................................................................................................... 2 CHAPTER 2 INSTALLATION ............................................................................................................. 3 MOUNTING ..................................................................................................................................... 3 PROCESS CONNECTIONS............................................................................................................. 4 PROCESS MEDIA ............................................................................................................................ 4 POTENTIALLY EXPLOSIVE ATMOSPHERES (HAZARDOUS LOCATIONS) ...................... 5 ELECTRICAL CONNECTIONS...................................................................................................... 5 CHAPTER 3 ADJUSTMENTS AFTER INSTALLATION .................................................................. 6 SETPOINT ADJUSTMENT ............................................................................................................. 6 CHAPTER 4 TROUBLESHOOTING ................................................................................................... 8 CHAPTER 5 SPECIFICATIONS .......................................................................................................... 9 WARRANTY INFORMATION .......................................................................................................... 16

Enclosure 6N Pressure Switches Page ii

Page 4

CHAPTER 1 INTRODUCTION The Neo-Dyn® Enclosure 6N Switches described in this manual are weather and explosion-proof, electromechanical sensing devices designed for a wide range of applications in pneumatic and hydraulic systems up to 10,000 psig, and for use in Zone 1 Potentially Explosive Atmospheres (Division 1 hazardous locations). 122P, 123P, 125P, 130P, 131P, 132P, 225P, 231P, and 232P are gauge pressure switches, and Model 181P is a vacuum switch. The most common wetted materials of the pressure and vacuum switches include a polyimide (Kapton) sensing diaphragm, nitrile O-ring, and aluminum alloy or corrosion resistant steel (CRES) pressure port. CRES diaphragms and all-welded constructions are also available in some models for corrosive pressure media. Setpoints of Model 130P are easily adjusted by turning an adjustment screw located inside the pressure port, while the other adjustable models have an adjustment nut that is accessed by removing the unit’s front cover. Models 131P, 181P, and 231P also include a selectable deadband, which can be factory-set. Models 125P, and 225P are factory-set tamperproof units. The standard configuration of these switches will switch up to 11 amp at 125 or 250 VAC, 5 amp resistive at 28 VDC, or 0.5 amp resistive at 125 VDC. When ordered with M Option, the switch is rated for currents to one amp, but its bifurcated gold contacts will reliably switch currents in the milliampere and microampere ranges. These switches have CE Mark, and they also have weatherproof enclosures with IP 66 ingress protection, and that meet the requirements of NEMA 3. 3R, 3S, 4, 4X and 13. The electrical subassemblies are listed by UL, FM Approvals, CSA, INMETRO, ATEX, and IECEx.

Enclosure 6N Pressure Switches Page 1

Page 5

2X 1.50 in (38.1 mm)

5.40 in Max (137.2 mm)

18 in (46 cm) FREE LEADS 18 AWG STD

PROCESS CONNECTION 2 MOUNTING HOLES, MODELS 125P, 132P, 225P, 232P ONLY

1/2 in NPT CONDUIT FITTING

ADJUSTMENT COVER, ALL MODELS EXCEPT 125P, 130P, AND 225P

Figure 1. Enclosure 6N Adjustable Pressure Switches

The standard process connection for each model is described in Chapter 2, and Chapter 4 on page 10 contains complete specifications.

CUSTOMER SERVICE If you have any questions about these Pressure and Temperature Switches that are not covered in this manual, you can contact Neo-Dyn® or our representatives in several ways. The Neo-Dyn® customer service phone number is (661) 295-4000. Our customer service department is open from 7:00 am to 3:30 p.m. Pacific Time. Our Internet site is www.neodyn.com; it includes lists of sales representatives and distributors.

OTHER CONFIGURATIONS WARNING

The models described in this manual are also available in special and factory-set configurations. For these units, follow the installation and operating instructions herein, except adhere to the pressure and electrical limits marked on the units.

WARNING

Models 125P and 225P are tamperproof factory-set units that are installed and operated like models 132P and 232P, but with no provision for setpoint adjustment. Again, adhere to the pressure and electrical limits marked on the units. Enclosure 6N Pressure Switches Page 2

Page 6

CHAPTER 2 INSTALLATION Installation of these Neo-Dyn® Enclosure 6N pressure switches is straightforward. However, they must be installed by a qualified electrician, in compliance with all local and national electrical codes. WARNING

Electrical hazard

WARNING

Do not make electrical connections while power is on.

WARNING

Always check for multiple circuits.

WARNING

Always make sure grounding is adequate.

WARNING

Do not remove switch while under pressure.

MOUNTING The pressure switch can be mounted directly to the process connection if there is no significant vibration and the fluid lines are capable of supporting the weight; in addition, Models 125P, 132P, 225P, and 232P can also be attached to a flat surface, such as a wall or panel, using .190 in. diameter (no. 10) or M5 fasteners through the mounting holes that are spaced 1.125 in. (28.6 mm) apart. The fastener length should include 1.50 inch (38.1 mm) above the mounting surface.

Enclosure 6N Pressure Switches Page 3

Page 7

PROCESS CONNECTIONS The process connections are: Model 130P port: ¼” - 18 NPT male standard. Model 131P, 181P, and 231P: combined ¼” - 18 NPT female and ½” - 14 NPT male standard. Models 132P and 232P: ¼” - 18 NPT female standard; ½ ” - 14 NPT female (G Option) and 7/16-20 SAE (E Option) are available. Models 125P and 225P: ¼” - 18 NPT female standard When installing the Pressure Switch, always:

Make sure that the unit and your system have matching threads.

Use the wrench flats provided.

Seal all joints with pipe joint sealing compound.

CAUTION

Avoid excessive torque on all threaded connections.

WARNING

Do not exceed the marked maximum operating pressure in normal operation. The marked Proof Pressure is provided to give the maximum allowable pressure without causing permanent damage to the pressure switch in the event of an over-pressure condition. Set pressure relief/safety valves below this setting.

PROCESS MEDIA Process media must be compatible with the wetted materials listed in Chapter 5 starting on page 13. Compatibility is defined by an “A” rating in the Chemical Resistance Guide for Metals and Alloys, the Chemical Resistance Guide for Plastics, and the Chemical Resistance Guide for Elastomers, all published by Compass Publications, and available from the National Association of Corrosion Engineers (NACE), Houston, Texas; telephone 281 228 6200.

Enclosure 6N Pressure Switches Page 4

Page 8

POTENTIALLY EXPLOSIVE ATMOSPHERES (HAZARDOUS LOCATIONS) Suitable for Zone 1, Ex db IIC explosive atmospheres, in accordance with Potentially Explosive Atmospheres Directive 2014/68/EU (ATEX) Suitable for Division 1; Class 1, Groups A, B, C and D; Class II, Groups E, F and G hazardous locations, in accordance with the National Electric Code (NEC), and applicable UL, CSA, FM, INMETRO specifications.

ELECTRICAL CONNECTIONS 18 AWG free leads 18 in (46 cm) long are standard, with a green wire grounded to the case. 72 inch (183 cm) leads are available as R Option, and other lead lengths may be ordered as special configurations. The leads are intended for installation in conduit capable of withstanding possible explosion pressures, and the leads are factory sealed. WARNING

All field wiring must comply with requirements of the NEC or applicable local or national electrical codes, including wire gauges and insulation temperature ratings. Conduit seals may be required.

Figure 2. Form C and CC Schematics Shown Below the Decreasing Setpoint NOTE

The direction of increasing pressure shown above represents the direction of increasing vacuum on model 181P.

Enclosure 6N Pressure Switches Page 5

Page 9

CHAPTER 3 ADJUSTMENTS AFTER INSTALLATION The factory-set setpoint or adjustable setpoint range is marked on the nameplate of the switch. This section describes the adjustments needed after an Adjustable Pressure Switch has been properly installed. Models 125P, and 225P are not adjustable.

SETPOINT ADJUSTMENT WARNING

Do not remove switch while under pressure. 1. Disconnect the electrical power. Check for multiple circuits. 2. On Model 130P, remove the pressure connection to allow access to the adjustment nut inside the pressure port. On the other models, loosen the screws on the access cover, and swing it to the side. 3. To change the setpoint on Model 130P, use an Allen wrench to rotate the adjustment nut counterclockwise to increase the setpoint, and clockwise to decrease it. It takes approximately 3 to 5 turns to move from one end of the adjustable range to the other (the higher range units require more turns than the lower range units). Check the setpoints per paragraphs 5 and 0 below for precise adjustments. 4. On the other models, the adjustment nut can be rotated by hand or with a smallshafted screwdriver or similar tool inserted into a slot. The range scale is intended to be used only as an approximate guide; it indicates the increasing setpoint on Models 122P, 123P, 132P, and 232P, and decreasing setpoint on Models 131P, 181P, and 231P. 5. To check the increasing setpoint, connect a pressure source and a calibrated pressure gauge or transducer to the pressure port and slowly apply increasing pressure (or vacuum on Model 181P) until the switch actuates. Actuation can be noted by listening to the audible snap of the Belleville spring, or with an ohmmeter across the appropriate free leads.

Enclosure 6N Pressure Switches Page 6

Page 10

6. If you want to check the decreasing setpoint, slowly decrease the pressure or vacuum after the switch has actuated and note the value at which the audible snap or an ohmmeter indicates deactuation. Deadband may be calculated if desired by subtracting the decreasing setpoint reading from the increasing setpoint reading. 7. On all models except 130P, replace the cover by swinging it back into position over the adjustment window and tightening the screws until the cover is snug against its gasket. Do not overtighten, as this could damage the gasket

Enclosure 6N Pressure Switches Page 7