Page 279

Appendix D: Logic Variables Description of Logic Variables

The DX-9100 contains logic variables, representing the individual bits in status Items. They are listed for use as logical status connections and PLC parameters in the configuration of the DX-9100. Logic variables are referred to by a byte address with a label (corresponding to the label of the equivalent Status Item in the Item List), and a bit position. When using the GX Tool for the DX-9100, the user will refer to module tags and numbers and logic variable tags. Absolute addresses (byte address and bit position) are normally not required. Note: When an address number is used for a connection inside the DX-9100, the microprocessor will automatically select between the Item List and the Logic Variables, depending on whether the connection is for an analog type or for a logic type.

Configuration Guides - DX-9100 Configuration Guide

279

Page 280

Logic Variable Tables

Table 64: Logic Variable Tables Byte No. Hex

Dec

Tag

Description

00H

00

System Clock X8 X7 X6 X5

01H

01

X2 = 1

Clock

0.5 sec.

X3 = 1

Clock

1 sec.

X4 = 1

Clock

2 sec.

X5 = 1

Clock

4 sec.

X6 = 1

Clock

8 sec.

X7 = 1

Clock

16 sec.

X8 = 1

Clock

32 sec.

MNT

Maintenance Control

02H

02

DIAG

Diagnostic LOW BYTE

03H

03

DIAG

Diagnostic HIGH BYTE

04H

04

DICT

Digital Input Counters

05H

05

TOS

TRIAC Output Status

06H

06

DIS

Digital Input Status

07H

07

AIS

Analog Input Status LOW BYTE

08H

08

AIS

Analog Input Status HIGH BYTE

09H

09

LRST1

Logic Results LOW BYTE

0AH

10

LRST1

Logic Results HIGH BYTE

0BH

11

LRST2

Logic Results LOW BYTE

0CH

12

LRST2

Logic Results HIGH BYTE

0DH

13

LCOS1

Logic Constants LOW BYTE

0EH

14

LCOS1

Logic Constants HIGH BYTE

10H

15

LCOS2

Logic Constants LOW BYTE

10H

16

LCOS2

Logic Constants HIGH BYTE

11H

17

SUP

Supervisory Control LOW BYTE

12H

18

SUP

Supervisory Control HIGH BYTE

13H

19

LRST3

Logic Results LOW BYTE (Version 1.1 or Later)

14H

20

LRST3

Logic Results HIGH BYTE (Version 1.1 or Later)

15H

21

LRST4

Logic Results LOW BYTE (Version 1.1 or Later) Logic Results HIGH BYTE (Version 1.1 or Later)

16H

22

LRST4

17H

23

Spare

Continued on next page . . .

280

X2 0

Configuration Guides - DX-9100 Configuration Guide

Page 281

Byte No. (Cont.) Hex Dec

Tag

Description

18H

24

PM1HDC

Hold Control

Programmable Function Module 1

19H

25

PM1DO

Logic Outputs

Programmable Function Module 1

1AH

26

PM1ST

Status LOW BYTE

Programmable Function Module 1

1BH

27

PM1ST

Status HIGH BYTE Programmable Function Module 1

1CH

28

PM2HDC

Hold Control

Programmable Function Module 2

1DH

29

PM2DO

Logic Outputs

Programmable Function Module 2

1EH

30

PM2ST

Status LOW BYTE

Programmable Function Module 2

1FH

31

PM2ST

Status HIGH BYTE Programmable Function Module 2

20H

32

PM3HDC

Hold Control

Programmable Function Module 3

21H

33

PM3DO

Logic Outputs

Programmable Function Module 3

22H

34

PM3ST

Status LOW BYTE

Programmable Function Module 3

23H

35

PM3ST

Status HIGH BYTE Programmable Function Module 3

24H

36

PM4HDC

Hold Control

Programmable Function Module 4

25H

37

PM4DO

Logic Outputs

Programmable Function Module 4

26H

38

PM4ST

Status LOW BYTE

Programmable Function Module 4

27H

39

PM4ST

Status HIGH BYTE Programmable Function Module 4

28H

40

PM5HDC

Hold Control

Programmable Function Module 5

29H

41

PM5DO

Logic Outputs

Programmable Function Module 5

2AH

42

PM5ST

Status LOW BYTE

Programmable Function Module 5

2BH

43

PM5ST

Status HIGH BYTE Programmable Function Module 5

2CH

44

PM6HDC

Hold Control

Programmable Function Module 6

2DH

45

PM6DO

Logic Outputs

Programmable Function Module 6 Programmable Function Module 6

2EH

46

PM6ST

Status LOW BYTE

2FH

47

PM6ST

Status HIGH BYTE Programmable Function Module 6

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

281

Page 282

Byte No. (Cont.) Hex Dec

Tag

Description

30H

48

PM7HDC

Hold Control

Programmable Function Module 7

31H

49

PM7DO

Logic Outputs

Programmable Function Module 7 Programmable Function Module 7

32H

50

PM7ST

Status LOW BYTE

33H

51

PM7ST

Status HIGH BYTE Programmable Function Module 7

34H

52

PM8HDC

Hold Control

Programmable Function Module 8

35H

53

PM8DO

Logic Outputs

Programmable Function Module 8

36H

54

PM8ST

Status LOW BYTE

Programmable Function Module 8

37H

55

PM8ST

Status HIGH BYTE Programmable Function Module 8

38H

56

PM9HDC

Hold Control

Programmable Function Module 9

39H

57

PM9DO

Logic Outputs

Programmable Function Module 9

3AH

58

PM9ST

Status LOW BYTE

Programmable Function Module 9

3BH

59

PM9ST

Status HIGH BYTE Programmable Function Module 9

3CH

60

PM10HDC

Hold Control

Programmable Function Module 10

3DH

61

PM10DO

Logic Outputs

Programmable Function Module 10

3EH

62

PM10ST

Status LOW BYTE

Programmable Function Module 10

3FH

63

PM10ST

Status HIGH BYTE Programmable Function Module 10

40H

64

PM11HDC

Hold Control

Programmable Function Module 11

41H

65

PM11DO

Logic Outputs

Programmable Function Module 11 Programmable Function Module 11

42H

66

PM11ST

Status LOW BYTE

43H

67

PM11ST

Status HIGH BYTE Programmable Function Module 11

Continued on next page . . .

282

Configuration Guides - DX-9100 Configuration Guide

Page 283

Byte No. (Cont.) Hex Dec

Tag

Description

44H 68 PM12HDC 45H 69 PM12DO 46H 70 PM12ST 47H 71 PM12ST 48H 72 AIST1 49H 73 AIST2 4AH 74 AIST3 4BH 75 AIST4 4CH 76 AIST5 4DH 77 AIST6 4EH 78 AIST7 4FH 79 AIST8 50H 80 AOC1 51H 81 AOC2 52H 82 DOC3 53H 83 DOC4 54H 84 DOC5 55H 85 DOC6 56H 86 DOC7 57H 87 DOC8 58H 88 XT1AIS 59H 89 XT1AIS 5AH 90 XT1HDC 5BH 91 XT1DO 5CH 92 XT1DI 5DH 93 XT1ST 5EH 94 XT2AIS 5FH 95 XT2AIS 60H 96 XT2HDC 61H 97 XT2DO 62H 98 XT2DI 63H 99 XT2ST Continued on next page . . .

Hold Control Programmable Function Module 12 Logic Outputs Programmable Function Module 12 Status LOW BYTE Programmable Function Module 12 Status HIGH BYTE Programmable Function Module 12 Analog Input 1 Status Analog Input 2 Status Analog Input 3 Status Analog Input 4 Status Analog Input 5 Status Analog Input 6 Status Analog Input 7 Status Analog Input 8 Status Analog Output 1 Control and Status Analog Output 2 Control and Status Digital Output 3 Control and Status Digital Output 4 Control and Status Digital Output 5 Control and Status Digital Output 6 Control and Status Digital Output 7 Control and Status Digital Output 8 Control and Status Alarms LOW BYTE - Extension Module 1 Alarms HIGH BYTE - Extension Module 1 Hold Control - Extension Module 1 Output Control - Extension Module 1 Input Status - Extension Module 1 Error Status - Extension Module 1 Alarms LOW BYTE - Extension Module 2 Alarms HIGH BYTE - Extension Module 2 Hold Control - Extension Module 2 Output Control - Extension Module 2 Input Status - Extension Module 2 Error Status - Extension Module 2

Configuration Guides - DX-9100 Configuration Guide

283

Page 284

Byte No. (Cont.) Hex Dec

Tag

Description

64H

100

XT3AIS

Alarms LOW BYTE

- Extension Module 3

65H

101

XT3AIS

Alarms HIGH BYTE

- Extension Module 3

66H

102

XT3HDC

Hold Control

- Extension Module 3

67H

103

XT3DO

Output Control

- Extension Module 3 - Extension Module 3

68H

104

XT3DI

Input Status

69H

105

XT3ST

Error Status

- Extension Module 3

6AH

106

XT4AIS

Alarms LOW BYTE

- Extension Module 4

6BH

107

XT4AIS

Alarms HIGH BYTE

- Extension Module 4

6CH

108

XT4HDC

Hold Control

- Extension Module 4

6DH

109

XT4DO

Output Control

- Extension Module 4

6EH

110

XT4DI

Input Status

- Extension Module 4

6FH

111

XT4ST

Error Status

- Extension Module 4

70H

112

XT5AIS

Alarms LOW BYTE

- Extension Module 5

71H

113

XT5AIS

Alarms HIGH BYTE

- Extension Module 5

72H

114

XT5HDC

Hold Control

- Extension Module 5

73H

115

XT5DO

Output Control

- Extension Module 5

74H

116

XT5DI

Input Status

- Extension Module 5

75H

117

XT5ST

Error Status

- Extension Module 5

76H

118

XT6AIS

Alarms LOW BYTE

- Extension Module 6

77H

119

XT6AIS

Alarms HIGH BYTE

- Extension Module 6

78H

120

XT6HDC

Hold Control

- Extension Module 6

79H

121

XT6DO

Output Control

- Extension Module 6

7AH

122

XT6DI

Input Status

- Extension Module 6

7BH

123

XT6ST

Error Status

- Extension Module 6

7CH

124

XT7AIS

Alarms LOW BYTE

- Extension Module 7

7DH

125

XT7AIS

Alarms HIGH BYTE

- Extension Module 7

7EH

126

XT7HDC

Hold Control

- Extension Module 7

7FH

127

XT7DO

Output Control

- Extension Module 7

80H

128

XT7DI

Input Status

- Extension Module 7

81H

129

XT7ST

Error Status

- Extension Module 7

Continued on next page . . .

284

Configuration Guides - DX-9100 Configuration Guide

Page 285

Byte No. (Cont.) Hex Dec

Tag

Description

82H

130

XT8AIS

Alarms LOW BYTE

- Extension Module 8

83H

131

XT8AIS

Alarms HIGH BYTE

- Extension Module 8

84H

132

XT8HDC

Hold Control

- Extension Module 8

85H

133

XT8DO

Output Control

- Extension Module 8 - Extension Module 8

86H

134

XT8DI

Input Status

87H

135

XT8ST

Error Status

- Extension Module 8

88H

136

TS1STA

Status and Control

- Time Schedule 1

89H

137

TS2STA

Status and Control

- Time Schedule 2

8AH

138

TS3STA

Status and Control

- Time Schedule 3

8BH

139

TS4STA

Status and Control

- Time Schedule 4

8CH

140

TS5STA

Status and Control

- Time Schedule 5

8DH

141

TS6STA

Status and Control

- Time Schedule 6

8EH

142

TS7STA

Status and Control

- Time Schedule 7

8FH

143

TS8STA

Status and Control

- Time Schedule 8

90H

144

OS1STA

Status and Control

- Optimal Start/Stop 1

91H

145

OS2STA

Status and Control

- Optimal Start/Stop 2

92H

146

AOC9

Status and Control

- Analog Output 9

93H

147

AOC10

Status and Control

- Analog Output 10

94H

148

AOC11

Status and Control

- Analog Output 11

95H

149

AOC12

Status and Control

- Analog Output 12

96H

150

AOC13

Status and Control

- Analog Output 13

97H

151

AOC14

Status and Control

- Analog Output 14

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

285

Page 286

Byte No. (Cont.) Hex Dec

Tag

Description

98H

152

NDI1

LOW BYTE

Network Digital Input Module 1

99H

153

NDI1

HIGH BYTE

Network Digital Input Module 1

9AH

154

NDI2

LOW BYTE

Network Digital Input Module 2

9BH

155

NDI2

HIGH BYTE

Network Digital Input Module 2

9CH

156

NDI3

LOW BYTE

Network Digital Input Module 3

9DH

157

NDI3

HIGH BYTE

Network Digital Input Module 3

9EH

158

NDI4

LOW BYTE

Network Digital Input Module 4

9FH

159

NDI4

HIGH BYTE

Network Digital Input Module 4

A0H

160

NDI5

LOW BYTE

Network Digital Input Module 5

A1H

161

NDI5

HIGH BYTE

Network Digital Input Module 5

A2H

162

NDI6

LOW BYTE

Network Digital Input Module 6

A3H

163

NDI6

HIGH BYTE

Network Digital Input Module 6

A4H

164

NDI7

LOW BYTE

Network Digital Input Module 7

A5H

165

NDI7

HIGH BYTE

Network Digital Input Module 7

A6H

166

NDI8

LOW BYTE

Network Digital Input Module 8

A7H

167

NDI8

HIGH BYTE

Network Digital Input Module 8

A8H

168

NDISTA

LOW BYTE

Network Digital Input Reliability Status

A9H

169

NDISTA

HIGH BYTE (not used)

Network Digital Input Reliability Status

AAH

170

NAISTA

LOW BYTE

Network Analog Input Reliability Status

ABH

171

NAISTA

HIGH BYTE

Network Analog Input Reliability Status

ACH

172 •

Spare for future expansion

•

Spare for future expansion

•

Local Variables used for PLC partial results to AFH

175

B0H

176 to BFH

191

C0H

192 to FFH

286

255

Configuration Guides - DX-9100 Configuration Guide

Page 287

Appendix E: Analog Items and Logic Variables for the Trend Log Module Table 65: Analog Items and Logic Variables For Point History

For DX LCD Display

DX Versions 1.4, 2.3, and Later:

DX Versions 2.3, 3.3, and Later:

Analog Items: AI1 to AI8 OUT1 to OUT8 ACO1 to ACO8 XtnAI1 to XtnAI8* XtnAO1 to XtnAO8*

Analog Items: AI1 to AI8 OUT1 to OUT14 ACO1 to ACO8 XTnAI1 to XTnAI8 XTnAO1 to XTnAO8 PMnK1 to PMnK34 PMnOU1 to PMnOU8 PMnAX1, PMnAX2

Logic Variables: DIS (DI1..8) LRST1 Low Byte (LRS1..8) LRST1 High Byte (LRS9..16) LRST2 Low Byte (LRS17..24) LRST2 High Byte (LRS25..32) XtnDI (XtnDI1..8)*

Logic Variables: DIS (DI1..8) LRST1 Low Byte (LRS1..8) LRST1 High Byte (LRS9..16) LRST2 Low Byte (LRS17..24) LRST2 High Byte (LRS25..32) LRST3 Low Byte (LRS33..40) LRST3 High Byte (LRS41..48) LRST4 Low Byte (LRS49..56) LRST4 High Byte (LRS57..64) TOS (DO3..8) LCOS1 Low Byte (DCO1..8) LCOS1 High Byte (DCO9..16) LCOS2 Low Byte (DCO17..24) LCOS2 High Byte (DCO25..32) XTnDI (XTnDI1..8) XTnDO (XTnDO1..8) AIS Low Byte (AIH/L1..4) AIS High Byte (AIH/L5..8) XTnAIS Low Byte (XTnAIH/L1..4) XTnAIS High Byte (XTnAIH/L5..8) PMnDO (PMnDO1..8)

* Available in Metasys Release 11.00. Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

287

Page 288

For Point History (Cont.)

For DX LCD Display

DX Version 2.3 and later only:

DX Version 3.3 and later only:

Analog Items: OUT9 to OUT14

Analog Items: NAI1 to NAI16 Logic Variables: NDI1 Low Byte (NDI1-1..8) NDI1 High Byte (NDI1-9..16) NDI2 Low Byte (NDI2-1..8) NDI2 High Byte (NDI2-9..16) NDI3 Low Byte (NDI3-1..8) NDI3 High Byte (NDI3-9..16) NDI4 Low Byte (NDI4-1..8) NDI4 High Byte (NDI4-9..16) NDI5 Low Byte (NDI5-1..8) NDI5 High Byte (NDI5-9..16) NDI6 Low Byte (NDI6-1..8) NDI6 High Byte (NDI6-9..16) NDI7 Low Byte (NDI7-1..8) NDI7 High Byte (NDI7-9..16) NDI8 Low Byte (NDI8-1..8) NDI8 High Byte (NDI8-9..16)

Note:

Since a logic variable byte is recorded when any one of its variables changes state, you are recommended to assign LRS logic variable bytes to trend log and to connect the source variables (the ones that you wish to trend) to the individual LRS variables in a PLC module.

Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201

288