Page 279
Appendix D: Logic Variables Description of Logic Variables
The DX-9100 contains logic variables, representing the individual bits in status Items. They are listed for use as logical status connections and PLC parameters in the configuration of the DX-9100. Logic variables are referred to by a byte address with a label (corresponding to the label of the equivalent Status Item in the Item List), and a bit position. When using the GX Tool for the DX-9100, the user will refer to module tags and numbers and logic variable tags. Absolute addresses (byte address and bit position) are normally not required. Note: When an address number is used for a connection inside the DX-9100, the microprocessor will automatically select between the Item List and the Logic Variables, depending on whether the connection is for an analog type or for a logic type.
Configuration Guides - DX-9100 Configuration Guide
279
Page 280
Logic Variable Tables
Table 64: Logic Variable Tables Byte No. Hex
Dec
Tag
Description
00H
00
System Clock X8 X7 X6 X5
01H
01
X2 = 1
Clock
0.5 sec.
X3 = 1
Clock
1 sec.
X4 = 1
Clock
2 sec.
X5 = 1
Clock
4 sec.
X6 = 1
Clock
8 sec.
X7 = 1
Clock
16 sec.
X8 = 1
Clock
32 sec.
MNT
Maintenance Control
02H
02
DIAG
Diagnostic LOW BYTE
03H
03
DIAG
Diagnostic HIGH BYTE
04H
04
DICT
Digital Input Counters
05H
05
TOS
TRIAC Output Status
06H
06
DIS
Digital Input Status
07H
07
AIS
Analog Input Status LOW BYTE
08H
08
AIS
Analog Input Status HIGH BYTE
09H
09
LRST1
Logic Results LOW BYTE
0AH
10
LRST1
Logic Results HIGH BYTE
0BH
11
LRST2
Logic Results LOW BYTE
0CH
12
LRST2
Logic Results HIGH BYTE
0DH
13
LCOS1
Logic Constants LOW BYTE
0EH
14
LCOS1
Logic Constants HIGH BYTE
10H
15
LCOS2
Logic Constants LOW BYTE
10H
16
LCOS2
Logic Constants HIGH BYTE
11H
17
SUP
Supervisory Control LOW BYTE
12H
18
SUP
Supervisory Control HIGH BYTE
13H
19
LRST3
Logic Results LOW BYTE (Version 1.1 or Later)
14H
20
LRST3
Logic Results HIGH BYTE (Version 1.1 or Later)
15H
21
LRST4
Logic Results LOW BYTE (Version 1.1 or Later) Logic Results HIGH BYTE (Version 1.1 or Later)
16H
22
LRST4
17H
23
Spare
Continued on next page . . .
280
X2 0
Configuration Guides - DX-9100 Configuration Guide
Page 281
Byte No. (Cont.) Hex Dec
Tag
Description
18H
24
PM1HDC
Hold Control
Programmable Function Module 1
19H
25
PM1DO
Logic Outputs
Programmable Function Module 1
1AH
26
PM1ST
Status LOW BYTE
Programmable Function Module 1
1BH
27
PM1ST
Status HIGH BYTE Programmable Function Module 1
1CH
28
PM2HDC
Hold Control
Programmable Function Module 2
1DH
29
PM2DO
Logic Outputs
Programmable Function Module 2
1EH
30
PM2ST
Status LOW BYTE
Programmable Function Module 2
1FH
31
PM2ST
Status HIGH BYTE Programmable Function Module 2
20H
32
PM3HDC
Hold Control
Programmable Function Module 3
21H
33
PM3DO
Logic Outputs
Programmable Function Module 3
22H
34
PM3ST
Status LOW BYTE
Programmable Function Module 3
23H
35
PM3ST
Status HIGH BYTE Programmable Function Module 3
24H
36
PM4HDC
Hold Control
Programmable Function Module 4
25H
37
PM4DO
Logic Outputs
Programmable Function Module 4
26H
38
PM4ST
Status LOW BYTE
Programmable Function Module 4
27H
39
PM4ST
Status HIGH BYTE Programmable Function Module 4
28H
40
PM5HDC
Hold Control
Programmable Function Module 5
29H
41
PM5DO
Logic Outputs
Programmable Function Module 5
2AH
42
PM5ST
Status LOW BYTE
Programmable Function Module 5
2BH
43
PM5ST
Status HIGH BYTE Programmable Function Module 5
2CH
44
PM6HDC
Hold Control
Programmable Function Module 6
2DH
45
PM6DO
Logic Outputs
Programmable Function Module 6 Programmable Function Module 6
2EH
46
PM6ST
Status LOW BYTE
2FH
47
PM6ST
Status HIGH BYTE Programmable Function Module 6
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
281
Page 282
Byte No. (Cont.) Hex Dec
Tag
Description
30H
48
PM7HDC
Hold Control
Programmable Function Module 7
31H
49
PM7DO
Logic Outputs
Programmable Function Module 7 Programmable Function Module 7
32H
50
PM7ST
Status LOW BYTE
33H
51
PM7ST
Status HIGH BYTE Programmable Function Module 7
34H
52
PM8HDC
Hold Control
Programmable Function Module 8
35H
53
PM8DO
Logic Outputs
Programmable Function Module 8
36H
54
PM8ST
Status LOW BYTE
Programmable Function Module 8
37H
55
PM8ST
Status HIGH BYTE Programmable Function Module 8
38H
56
PM9HDC
Hold Control
Programmable Function Module 9
39H
57
PM9DO
Logic Outputs
Programmable Function Module 9
3AH
58
PM9ST
Status LOW BYTE
Programmable Function Module 9
3BH
59
PM9ST
Status HIGH BYTE Programmable Function Module 9
3CH
60
PM10HDC
Hold Control
Programmable Function Module 10
3DH
61
PM10DO
Logic Outputs
Programmable Function Module 10
3EH
62
PM10ST
Status LOW BYTE
Programmable Function Module 10
3FH
63
PM10ST
Status HIGH BYTE Programmable Function Module 10
40H
64
PM11HDC
Hold Control
Programmable Function Module 11
41H
65
PM11DO
Logic Outputs
Programmable Function Module 11 Programmable Function Module 11
42H
66
PM11ST
Status LOW BYTE
43H
67
PM11ST
Status HIGH BYTE Programmable Function Module 11
Continued on next page . . .
282
Configuration Guides - DX-9100 Configuration Guide
Page 283
Byte No. (Cont.) Hex Dec
Tag
Description
44H 68 PM12HDC 45H 69 PM12DO 46H 70 PM12ST 47H 71 PM12ST 48H 72 AIST1 49H 73 AIST2 4AH 74 AIST3 4BH 75 AIST4 4CH 76 AIST5 4DH 77 AIST6 4EH 78 AIST7 4FH 79 AIST8 50H 80 AOC1 51H 81 AOC2 52H 82 DOC3 53H 83 DOC4 54H 84 DOC5 55H 85 DOC6 56H 86 DOC7 57H 87 DOC8 58H 88 XT1AIS 59H 89 XT1AIS 5AH 90 XT1HDC 5BH 91 XT1DO 5CH 92 XT1DI 5DH 93 XT1ST 5EH 94 XT2AIS 5FH 95 XT2AIS 60H 96 XT2HDC 61H 97 XT2DO 62H 98 XT2DI 63H 99 XT2ST Continued on next page . . .
Hold Control Programmable Function Module 12 Logic Outputs Programmable Function Module 12 Status LOW BYTE Programmable Function Module 12 Status HIGH BYTE Programmable Function Module 12 Analog Input 1 Status Analog Input 2 Status Analog Input 3 Status Analog Input 4 Status Analog Input 5 Status Analog Input 6 Status Analog Input 7 Status Analog Input 8 Status Analog Output 1 Control and Status Analog Output 2 Control and Status Digital Output 3 Control and Status Digital Output 4 Control and Status Digital Output 5 Control and Status Digital Output 6 Control and Status Digital Output 7 Control and Status Digital Output 8 Control and Status Alarms LOW BYTE - Extension Module 1 Alarms HIGH BYTE - Extension Module 1 Hold Control - Extension Module 1 Output Control - Extension Module 1 Input Status - Extension Module 1 Error Status - Extension Module 1 Alarms LOW BYTE - Extension Module 2 Alarms HIGH BYTE - Extension Module 2 Hold Control - Extension Module 2 Output Control - Extension Module 2 Input Status - Extension Module 2 Error Status - Extension Module 2
Configuration Guides - DX-9100 Configuration Guide
283
Page 284
Byte No. (Cont.) Hex Dec
Tag
Description
64H
100
XT3AIS
Alarms LOW BYTE
- Extension Module 3
65H
101
XT3AIS
Alarms HIGH BYTE
- Extension Module 3
66H
102
XT3HDC
Hold Control
- Extension Module 3
67H
103
XT3DO
Output Control
- Extension Module 3 - Extension Module 3
68H
104
XT3DI
Input Status
69H
105
XT3ST
Error Status
- Extension Module 3
6AH
106
XT4AIS
Alarms LOW BYTE
- Extension Module 4
6BH
107
XT4AIS
Alarms HIGH BYTE
- Extension Module 4
6CH
108
XT4HDC
Hold Control
- Extension Module 4
6DH
109
XT4DO
Output Control
- Extension Module 4
6EH
110
XT4DI
Input Status
- Extension Module 4
6FH
111
XT4ST
Error Status
- Extension Module 4
70H
112
XT5AIS
Alarms LOW BYTE
- Extension Module 5
71H
113
XT5AIS
Alarms HIGH BYTE
- Extension Module 5
72H
114
XT5HDC
Hold Control
- Extension Module 5
73H
115
XT5DO
Output Control
- Extension Module 5
74H
116
XT5DI
Input Status
- Extension Module 5
75H
117
XT5ST
Error Status
- Extension Module 5
76H
118
XT6AIS
Alarms LOW BYTE
- Extension Module 6
77H
119
XT6AIS
Alarms HIGH BYTE
- Extension Module 6
78H
120
XT6HDC
Hold Control
- Extension Module 6
79H
121
XT6DO
Output Control
- Extension Module 6
7AH
122
XT6DI
Input Status
- Extension Module 6
7BH
123
XT6ST
Error Status
- Extension Module 6
7CH
124
XT7AIS
Alarms LOW BYTE
- Extension Module 7
7DH
125
XT7AIS
Alarms HIGH BYTE
- Extension Module 7
7EH
126
XT7HDC
Hold Control
- Extension Module 7
7FH
127
XT7DO
Output Control
- Extension Module 7
80H
128
XT7DI
Input Status
- Extension Module 7
81H
129
XT7ST
Error Status
- Extension Module 7
Continued on next page . . .
284
Configuration Guides - DX-9100 Configuration Guide
Page 285
Byte No. (Cont.) Hex Dec
Tag
Description
82H
130
XT8AIS
Alarms LOW BYTE
- Extension Module 8
83H
131
XT8AIS
Alarms HIGH BYTE
- Extension Module 8
84H
132
XT8HDC
Hold Control
- Extension Module 8
85H
133
XT8DO
Output Control
- Extension Module 8 - Extension Module 8
86H
134
XT8DI
Input Status
87H
135
XT8ST
Error Status
- Extension Module 8
88H
136
TS1STA
Status and Control
- Time Schedule 1
89H
137
TS2STA
Status and Control
- Time Schedule 2
8AH
138
TS3STA
Status and Control
- Time Schedule 3
8BH
139
TS4STA
Status and Control
- Time Schedule 4
8CH
140
TS5STA
Status and Control
- Time Schedule 5
8DH
141
TS6STA
Status and Control
- Time Schedule 6
8EH
142
TS7STA
Status and Control
- Time Schedule 7
8FH
143
TS8STA
Status and Control
- Time Schedule 8
90H
144
OS1STA
Status and Control
- Optimal Start/Stop 1
91H
145
OS2STA
Status and Control
- Optimal Start/Stop 2
92H
146
AOC9
Status and Control
- Analog Output 9
93H
147
AOC10
Status and Control
- Analog Output 10
94H
148
AOC11
Status and Control
- Analog Output 11
95H
149
AOC12
Status and Control
- Analog Output 12
96H
150
AOC13
Status and Control
- Analog Output 13
97H
151
AOC14
Status and Control
- Analog Output 14
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
285
Page 286
Byte No. (Cont.) Hex Dec
Tag
Description
98H
152
NDI1
LOW BYTE
Network Digital Input Module 1
99H
153
NDI1
HIGH BYTE
Network Digital Input Module 1
9AH
154
NDI2
LOW BYTE
Network Digital Input Module 2
9BH
155
NDI2
HIGH BYTE
Network Digital Input Module 2
9CH
156
NDI3
LOW BYTE
Network Digital Input Module 3
9DH
157
NDI3
HIGH BYTE
Network Digital Input Module 3
9EH
158
NDI4
LOW BYTE
Network Digital Input Module 4
9FH
159
NDI4
HIGH BYTE
Network Digital Input Module 4
A0H
160
NDI5
LOW BYTE
Network Digital Input Module 5
A1H
161
NDI5
HIGH BYTE
Network Digital Input Module 5
A2H
162
NDI6
LOW BYTE
Network Digital Input Module 6
A3H
163
NDI6
HIGH BYTE
Network Digital Input Module 6
A4H
164
NDI7
LOW BYTE
Network Digital Input Module 7
A5H
165
NDI7
HIGH BYTE
Network Digital Input Module 7
A6H
166
NDI8
LOW BYTE
Network Digital Input Module 8
A7H
167
NDI8
HIGH BYTE
Network Digital Input Module 8
A8H
168
NDISTA
LOW BYTE
Network Digital Input Reliability Status
A9H
169
NDISTA
HIGH BYTE (not used)
Network Digital Input Reliability Status
AAH
170
NAISTA
LOW BYTE
Network Analog Input Reliability Status
ABH
171
NAISTA
HIGH BYTE
Network Analog Input Reliability Status
ACH
172 •
Spare for future expansion
•
Spare for future expansion
•
Local Variables used for PLC partial results to AFH
175
B0H
176 to BFH
191
C0H
192 to FFH
286
255
Configuration Guides - DX-9100 Configuration Guide
Page 287
Appendix E: Analog Items and Logic Variables for the Trend Log Module Table 65: Analog Items and Logic Variables For Point History
For DX LCD Display
DX Versions 1.4, 2.3, and Later:
DX Versions 2.3, 3.3, and Later:
Analog Items: AI1 to AI8 OUT1 to OUT8 ACO1 to ACO8 XtnAI1 to XtnAI8* XtnAO1 to XtnAO8*
Analog Items: AI1 to AI8 OUT1 to OUT14 ACO1 to ACO8 XTnAI1 to XTnAI8 XTnAO1 to XTnAO8 PMnK1 to PMnK34 PMnOU1 to PMnOU8 PMnAX1, PMnAX2
Logic Variables: DIS (DI1..8) LRST1 Low Byte (LRS1..8) LRST1 High Byte (LRS9..16) LRST2 Low Byte (LRS17..24) LRST2 High Byte (LRS25..32) XtnDI (XtnDI1..8)*
Logic Variables: DIS (DI1..8) LRST1 Low Byte (LRS1..8) LRST1 High Byte (LRS9..16) LRST2 Low Byte (LRS17..24) LRST2 High Byte (LRS25..32) LRST3 Low Byte (LRS33..40) LRST3 High Byte (LRS41..48) LRST4 Low Byte (LRS49..56) LRST4 High Byte (LRS57..64) TOS (DO3..8) LCOS1 Low Byte (DCO1..8) LCOS1 High Byte (DCO9..16) LCOS2 Low Byte (DCO17..24) LCOS2 High Byte (DCO25..32) XTnDI (XTnDI1..8) XTnDO (XTnDO1..8) AIS Low Byte (AIH/L1..4) AIS High Byte (AIH/L5..8) XTnAIS Low Byte (XTnAIH/L1..4) XTnAIS High Byte (XTnAIH/L5..8) PMnDO (PMnDO1..8)
* Available in Metasys Release 11.00. Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
287
Page 288
For Point History (Cont.)
For DX LCD Display
DX Version 2.3 and later only:
DX Version 3.3 and later only:
Analog Items: OUT9 to OUT14
Analog Items: NAI1 to NAI16 Logic Variables: NDI1 Low Byte (NDI1-1..8) NDI1 High Byte (NDI1-9..16) NDI2 Low Byte (NDI2-1..8) NDI2 High Byte (NDI2-9..16) NDI3 Low Byte (NDI3-1..8) NDI3 High Byte (NDI3-9..16) NDI4 Low Byte (NDI4-1..8) NDI4 High Byte (NDI4-9..16) NDI5 Low Byte (NDI5-1..8) NDI5 High Byte (NDI5-9..16) NDI6 Low Byte (NDI6-1..8) NDI6 High Byte (NDI6-9..16) NDI7 Low Byte (NDI7-1..8) NDI7 High Byte (NDI7-9..16) NDI8 Low Byte (NDI8-1..8) NDI8 High Byte (NDI8-9..16)
Note:
Since a logic variable byte is recorded when any one of its variables changes state, you are recommended to assign LRS logic variable bytes to trend log and to connect the source variables (the ones that you wish to trend) to the individual LRS variables in a PLC module.
Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201
288