Manual · KB Electronics
Installation and Operating Instructions, Regenerative Drive Model KBMG-212D
Manual17 pagesPDF 948 KB
Installation and operating instructions for the KB Electronics KBMG-212D 4-quadrant regenerative SCR drive for PM and shunt wound DC motors.
Covers · 1 model
The models it covers
Summary
What is in it
KB Electronics instructions for the KBMG-212D, a full-wave, 4-quadrant regenerative variable speed SCR control for permanent magnet and shunt wound DC motors. It gives simplified setup steps, safety warnings, electrical ratings and performance specifications, jumper settings for line voltage, motor current, armature voltage, input signal, speed or torque mode and stop mode, then mounting, wiring, fusing, trimpot adjustments, indicator lamps and accessories.
Its parts
- Simplified Setup and Operating Instructions
- Safety Warning
- General Information
- Operation
- Setting Selectable Jumpers
- Mounting
- Wiring
- Fusing
- Trimpot Adjustments
- Function Indicator Lamps
- KBMG-212D Accessories
- Limited Warranty
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Installation and operating instructions for the KB Electronics KBMG-212D regenerative drive (KB part 8831), a full-wave, 4-quadrant SCR control for permanent magnet and shunt wound DC motors. It gives the ratings and walks through jumper settings, mounting, wiring, fusing and trimpot adjustment. It also explains the indicator lamps and lists the optional accessories.
- Device
- Full-wave, 4-quadrant regenerative SCR drive for PM and shunt wound DC motors, KB Part No. 8831 p. 1, 3
- AC line input
- 115 or 230 VAC ±10%, 50/60 Hz, chosen with jumpers J1A and J1B p. 2, 4
- Motor voltage
- 90 VDC motors on a 115 or 230 VAC line; 180 VDC motors on a 230 VAC line only p. 2
- Ratings
- 8.0 A DC: 0.75 HP at 90 VDC, 1.5 HP at 180 VDC; with auxiliary heatsink KB P/N 9861, 11.0 A DC: 1 HP or 2 HP p. 4
- Armature current
- Jumper J2: 1.7, 2.5, 5.0, 7.5 or 10 A; factory 7.5 A; 10 A needs auxiliary heatsink KB P/N 9861 p. 2, 5
- Current limit
- Factory set at 150% of the J2 setting, adjustable with the FWD CL and REV CL trimpots p. 5
- Control mode
- Speed (SPD, factory setting) or torque (TRQ), chosen with jumper J5 p. 2
- Speed input
- 5K ohm potentiometer supplied (10K usable), or an isolated 0 to ±10 VDC signal with J4 at 10V p. 10, 12
- Stopping
- Opening the EN-COM enable circuit stops the motor; jumper J6 picks regenerate to stop (RTS, factory) or coast to stop (CTS) p. 7
- Feedback
- Armature feedback (factory); optional tach-generator, 7 V or 50 V per 1000 RPM p. 6, 13
- Acceleration
- Forward and reverse accel 0.1 to 15 seconds, factory about 1 second p. 14
- Fusing
- Armature fuse Littelfuse 326 ceramic or Buss ABC; 20 amp normal-blow fuse or breaker on each ungrounded AC line p. 9, 13
- Accessories
- SIMG signal isolator P/N 8832, Multi Speed Board P/N 8833, 4-quadrant accel/decel P/N 8834, DIN rail kit P/N 9995 p. 16
- Indicator lamps
- PWR ON (AC line applied) and OL (current limit reached) p. 16
What this manual walks you through
- Quick setup: connections, motor current, enable and mode p. 2
- Setting the selectable jumpers before first use p. 5, 6, 7
- Mounting the drive and sizing an enclosure p. 9
- Wiring the AC line, ground and motor armature p. 9
- Connecting full or half voltage shunt fields p. 10
- Connecting the speed potentiometer for one or both directions p. 10, 11
- Wiring tach-generator feedback p. 13
- Choosing the armature fuse p. 13, 14
- Adjusting the accel, dead band, current limit, IR comp, max speed and response trimpots p. 14, 15, 16
Good to know
- The start/stop and enable circuits are not safety disconnects; use an AC line disconnect. p. 12
- The potentiometer, start/stop and enable inputs are not isolated from the AC line. p. 3
- A voltage-following signal must be isolated, or catastrophic failure can result. p. 12
- Regenerative drives heat the motor more than standard SCR controls, especially at low speed. p. 3
- The manual states a CE approved RFI filter (KBRF-200A, KB P/N 9945C or equivalent) is required for CE installations. p. 3
Questions this manual answers
How do I set the KBMG-212D for 115 or 230 VAC?
Set both jumpers J1A and J1B to the position matching the AC line voltage, 115 or 230. p. 2
Can a 90 VDC motor run on a 230 VAC line with the KBMG-212D?
Yes, with J3 in the A90 position, but speed range may be reduced and the motor may need derating. p. 6
Why will my KBMG-212D not run?
The control will not run unless a jumper or closed contact connects the EN and COM terminals. p. 7
What does the OL lamp on the KBMG-212D mean?
The control has reached its current limit set point; blinking is normal with transient loads. p. 16
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.