For the KB Electronics KBMG-212D

Page 10

D. Field – For Shunt Wound motors only. Do not use F+ and F– terminals for any other motor type. Connect motor shunt field to terminals F+ and F– for 90VDC motors with 100VDC fields and 180VDC motors with 200VDC fields. For motors with half voltage fields, 90VDC motors with 50VDC fields and 180VDC motors with 100VDC fields, connect field to terminals F+ and L1. See table 7, p. 18 for summary of field connections.

FIG. 10A – FULL VOLTAGE FIELD

CAUTION – Shunt-Wound motors may be damaged due to overheating if field remains powered without motor rotating for an extended period of time. FIG. 10B – HALF VOLTAGE FIELD

17

TABLE 7 – FIELD CONNECTIONS (Shunt Wound Motors Only) AC Line Voltage (VAC)

Motor Voltage

Field Voltage (VDC)

Field Connection

115

90

100

F+, F–

115

90

50

F+, L1

230

180

200

F+, F–

230

180

100

F+, L1

230

90*

100

F+, L1

*Step Down operation (see sec. III C, p. 9).

E. Main Speed Potentiometer – The main speed potentiometer can be connected in several ways using terminals “COM,” “+15,” “SIG” and “–15.” A 5K ohm potentiometer is supplied with control. (A 10K potentiometer can also be used.) (Warning! Terminals “COM,” “+15,” “SIG” and “–15" are not isolated from AC line.) Note: Jumper J4 must be in the “15V” position. i. Unidirectional operation only – Connect potentiometer to terminals “COM,” “+15,” “SIG" for forward direction. To operate in reverse direction, connect to “COM,” “SIG,” and “–15.” See fig. 11, p. 19. ii. Bidirectional operation only – Connect to terminals “COM,” “+15,” “SIG,” and “–15" when using reversing contacts. To operate with a potentiometer, connect to “+15," “SIG,” and “–15." See fig. 11.

18

Page 11

FIG. 11 – MAIN SPEED POTENTIOMETER CONNECTIONS A) Forward

B) Reverse

C) Bidirectional with Reversing Contact

D) Bidirectional with Speed Pot

*Note: A jumper must be wired to EN and COM in order for control to operate. 19

FIG. 12 – CONTROL LAYOUT (Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings)

Notch denotes position.

TRIMPOT

20

Page 12

FIG. 13 – MECHANICAL SPECIFICATIONS (INCHES / [mm])

21

F.

Voltage Following – An isolated FIG. 14 – VOLTAGE analog voltage can be used in lieu FOLLOWING CONNECTION of main speed potentiometer. Connect signal to terminals “SIG" and “COM.” Note: Terminal “COM" is common. A positive signal to terminal “SIG” will produce a positive output to motor. A negative signal to terminal “SIG" will produce a negative output. A 0 to ±10VDC is required to operate control from 0 ± full output. Note: Jumper J4 must be in the “10V” position. Note: An isolated signal voltage must be used or catastrophic failure can result. (A bipolar signal isolator, model SIMG [KB P/N 8832], is available as an option from your distributor.)

G. Enable Start/Stop Circuits – The KBMG-212D contains a 2-wire stop circuit (Enable), which is used to electronically bring the motor to a “stop.” An isolated single contact closure is required. If an isolated contact is not available, it may be necessary to use an isolation relay. *Note: If 2-wire start/stop circuit is not used, a jumper must be wired to EN and COM or control will not operate. WARNING! Do not use Start/Stop or Enable functions as a safety disconnect. Use only an AC line disconnect for that purpose. 22

Page 13

i. Regen to a stop using terminals EN and COM on terminal block TB1 – When a contact is opened between terminals “EN” and “COM,” with jumper J6 in the “RTS” position, the motor will regeneratively brake to a rapid stop. Application note (See fig. 15): If controlled regen to stop is required, a contact can be installed in series with the signal “SIG” connection. The braking time will be equal to the REV ACCEL setting when the motor is in the forward direction, and equal to the FWD ACCEL setting when the motor is in the reverse direction. Note: J4 must be in the “15V” position. (See fig. 11D, p. 19.) ii. Coast to a stop using terminals “EN” and “COM” on terminal block TB1 – If coast to stop operation is required, move jumper J6 to the coast to stop (CTS) position. When the contact is opened between “EN” and “COM,” the motor will coast to a stop. See fig. 16. FIG. 15 – REGENERATE TO STOP

FIG. 16 – COAST TO STOP

ENABLE

ENABLE

OPEN TO REGENERATE TO STOP

OPEN TO COAST TO STOP

*FWD Accel and REV Accel do not affect the stopping time when the enable circuit is opened.

23

H. Tach-generator Feedback – The KBMG212D is factory set for armature feedback, which provides good load regulation for most applications. For superior load regulation, analog tach-generator feedback can be used.

FIG. 17 – TACH-GENERATOR FEEDBACK

Wire the tach-generator so that the polarity of the tach-generator is the same with respect to the input signal polarity (see fig. 17). Note: If tach-generator is wired with reverse polarity, the motor will run at full speed. Note: Jumper J3 must be set to the proper position for tach feedback. See sec III, C, p. 9 and fig. 2 on page 10. Note: Check tach voltage polarity with respect to input signal if polarity does not match reverse tach leads. Be sure AC line is disconnected when rewiring tach-generator. VI. FUSING. Armature Fuse – It is recommended that the correct size armature fuse be installed, depending on the rating of the motor and form factor (RMS/AVG current). Fuse type should be Littelfuse 326 ceramic or Buss ABC, or equivalent. A fuse chart is presented below which suggests appropriate armature fuse ratings. However, the specific application may require larger fuse ratings based on ambient temperature, CL set point and duty cycle of operation (see table 8, p. 25). Fuses may be purchased from your distributor. Wire fuse in series with armature lead. 24

Page 14

TABLE 8 – ARMATURE FUSE CHART

90VDC

180VDC

Approx. DC Motor Current Amps

1/8

1/4

1.3

2

1/6

1/3

1.7

2

1/4

1/2

2.5

4

1/3

3/4

3.3

5

1/2

1

5.0

8

3/4

1

7.5

12

1

2

10.0

20

Motor Horsepower

Fuse Rating (AC Amps)

VII. TRIMPOT ADJUSTMENTS. The KBMG-212D contains trimpots that have been factory adjusted for most applications. See specifications for factory settings. (Note: Fig. 12, p. 20, presents the various trimpots with their location. They are shown in the approximate factory position.) Some applications may require readjustment of trimpots in order to tailor control to exact requirements. Readjust trimpots as follows:

25

A. Forward Acceleration (FWD ACCEL) and Reverse Acceleration (REV ACCEL) – The FWD ACCEL trimpot determines the amount of time it takes the control voltage to reach full output in the forward direction. It also determines the amount of time it takes for the control voltage, in the reverse direction, to reach zero output. (FWD ACCEL is the Reverse Decel.)

FIG. 18 – ACCEL TRIMPOT ADJUSTMENT ACCEL TRIMPOT SETTING 7.5

1.0

14.0

0.1

15.0 SECONDS

The REV ACCEL trimpot determines the amount of time it takes the control voltage to reach full output in the reverse direction and the time it takes for the control voltage, in the forward direction, to reach zero output. (REV ACCEL is the Forward Decel.) The FWD and REV ACCEL trimpots are factory adjusted to approximately 1 second. The acceleration times are adjustable over a range of 0.1 to 15 seconds. See fig. 18 for graphical representation of ACCEL. Note: The FWD and REV CL trimpots may override the rapid accel and decel settings. 26

Page 15

Note: A 4-quadrant ACCEL/DECEL accessory module (KB P/N 8834) is available as an option. It provides separate control of FORWARD acceleration and deceleration and REVERSE acceleration and deceleration.

FIG. 19 – DEAD BAND TRIMPOT ADJUSTMENT

B. Dead Band Trimpot (DB) – The DB trimpot sets the amount of main speed potentiometer rotation or analog voltage input required to initiate control voltage output. It is factory adjusted to approximately 25% of rotation. The DB trimpot also determines the amount of delay that will occur before regeneration starts. Regeneration occurs when the applied load torque is in the same direction as the motor rotation. To readjust the DB to factory setting: i. Set Main Speed pot to zero speed position. ii. Set DB trimpot to full CCW position. 27 iii. Adjust DB trimpot CW until motor hum is eliminated. (See fig. 19, p. 27 for graphic illustration of the DB trimpot.) Note: If the dead band trimpot is set too low (CCW direction), the motor may oscillate between forward and reverse. Adjust dead band trimpot CW until the instability disappears. (Oscillation may also occur due to RESP and IR COMP trimpot settings. See sec. VII, D & F on page 29.) C. Forward Current Limit (FWD CL) and Reverse Current Limit (REV CL) Trimpots – These trimpots are used to set the maximum amount of DC current that the motor can draw in both the forward and reverse directions. The amount of DC current determines the amount of maximum motor torque. They are factory set at 150% of the current established by the jumper J2 setting. Readjust the CL trimpot as follows: i. Turn CL trimpot to MIN (CCW) position. Be sure jumper J3 is in the proper position approximately equal to the motor DC ampere rating. ii. Wire in a DC ammeter in series with armature lead. Lock shaft of motor. iii. Apply power. Rotate CL trimpot quickly until desired CL setting is reached (factory setting is 1.5 times rated motor current). Be sure control is in forward direction for FWD CL trimpot adjustment and likewise with REV CL. Warning! To prevent motor damage, do not leave motor shaft locked for more than 2 – 3 seconds. Caution! Adjusting the CL above 150% of motor rating can cause overheating and demagnetization of some PM motors. Consult motor manufacturer. 28

Page 16

D. IR Compensation (IR Comp) – The IR Comp is used to stabilize motor speed under varying loads. Readjust the IR Comp trimpot as follows: i. Initially set trimpot to factory position (approximately 10 o’clock). ii. Run motor at approximately 30 – 50% of rated speed under no load and measure actual speed. iii. Load motor to rated current. Rotate IR Comp trimpot so that loaded speed is the same as the unloaded speed measured in the previous step. Control is now compensated so that minimal speed change will occur over a wide range of motor load. Note: Excessive IR Comp will cause unstable (oscillatory) operation. E. Maximum Speed (MAX) – The MAX trimpot is used to set the maximum output voltage of the control which, in turn, sets the maximum speed of the motor. Adjust the MAX trimpot as follows: i. Rotate Main Speed potentiometer to full speed (CW). ii. Adjust MAX trimpot to desired maximum motor speed. Note: Do not exceed maximum rated RPM of motor since unstable operation may result. F.

Response Trimpot (RESP) – This trimpot determines the dynamic response of the control. The factory setting is approximately 50% of full rotation. The setting may be increased if a faster response is required. Note: If response is set too fast, unstable operation may result.

29

VIII. FUNCTION INDICATOR LAMPS. A. Power On (PWR ON) – Indicates that the drive is energized with the AC line. B. Overload (OL) – Indicates the control has reached the current limit set point which has been established by the position of jumper J2 and the FWD CL and REV CL trimpot settings. In transient load applications, it is normal for this light to blink. IX. KBMG-212D ACCESSORIES

30

•

Model SIMG Bipolar Signal Isolator (P/N 8832) – Allows a non-isolated signal source to be used.

•

Multi Speed Board (P/N 8833) – Provides discrete preset speeds which can be controlled from a PLC.

•

4-Quadrant Accel/Decel (P/N 8834) – Provides independent settings of forward accel, forward decel, reverse accel and reverse decel.

•

DIN Rail Mounting Kit (P/N 9995) – Converts control to standard DIN Rail Mounting.

Page 17

– NOTES –

X – LIMITED WARRANTY For a period of 18 months from date of original purchase, KB will repair or replace without charge devices which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. The foregoing is in lieu of any other warranty or guarantee, expressed or implied, and we are not responsible for any expense, including installation and removal, inconvenience, or consequential damage, including injury to any person, caused by items of our manufacture or sale. Some states do not allow certain exclusions or limitations found in this warranty so that they may not apply to you. In any event, KB's total liability, under all circumstances, shall not exceed the full purchase price of this unit. (rev 4/88)