For the Keyence FS-V33CP

Page 1

96M11292

Input Circuit Diagram FS-V33/34 3.3 VDC Sensor main circuit

DIGITAL FIBER SENSOR 2-OUTPUT TYPE

FS-V33(P)/V34(P)/V33C(P)/V34C(P)

•

0V

12 to 24 VDC Brown* Sensor main circuit

•

PLC, etc. Blue*

FS-V33P/34P

Read this manual before using the product in order to achieve maximum performance. Keep this manual in a safe place after reading it so that it can be used at any time.

Warning

(Short-circuit current 1 mA or less)

* FS-V33 only

Instruction Manual •

Pink (input)

This product is just intended to detect the object(s). Do not use this product for the purpose to protect a human body or a part of human body. This product is not intended for use as explosion-proof product. Do not use this product in a hazardous location and/or potentially explosive atmosphere. This product is a sensor of DC power supply type. Do not apply AC power. The product may explode or burn if an AC voltage is applied.

PLC, etc.

Pink (input) (Short-circuit current 2 mA or less)

* FS-V33P only

Socket Cable (Sold Separately for FS-V33C (P)/V34C (P)) Precautions on Regulations and Standards

„ Connecting the Socket Cable

„ UL Certificate

Pin and wire color table

1 Connect the socket to the pin on the

This product is an UL/C-UL Listed product. • UL File No. E301717 • Category NRKH,NRKH7 • Enclosure Type 1 (Based on UL50)

amplifier.

Be sure to consider the following specifications when using this product as an UL/ C-UL Listed Product. • Use the power supply with Class 2 output defined in NFPA70 (NEC: National Electrical Code). • Power supply/ Control input/ Control output circuits shall be connected to a single Class 2 source only. • Use with the over current protection device which is rated 24V or more and not more than 2A.

4 3

2 1

Connected pin Core wire No. cover color (1)

Brown

(2)

White

(3)

Blue

(4)

Black

2 Turn the fixing ring on the socket clockwise to fix the socket.

Option (Sold Separately) Mounting bracket (main unit)

End unit

Socket cable Dedicated for FS-V33C(P)/34C(P)

Mounting Unit „ Mounting on a DIN Rail

1 Align the claw at the bottom of the main body with the OP-73880

OP-26751 (a set of two)

OP-73864 (cable length: 2 m) OP-73865 (cable length: 10 m)

DIN rail. While pushing the main body in the direction of the arrow 1, slant it in the direction of the arrow 2.

2 To dismount the sensor, raise the main body in

Part Names the direction of the arrow 3 while pushing the main body in the direction of the arrow 1.

Fiber lock lever

„ Installation on a Wall (Main Unit Only) Attach the unit to the optional mounting bracket (OP-73880), mount them together, and secure them with two M3 screws as shown in the illustration.

DSC

DSC

(

1 2

1 2

Operation status indicators (output 1) Operation status indicators (output 2) Setting value SET button (SET) (Displayed in green) DSC indicator Digital monitor Current value Manual button (Displayed in red) )

OP-73880

1

1

Expansion protective cover Expansion connector

2

2

Channel selection MODE button (MODE) Output selector (L/D ON)

Connecting Multiple Amplifiers Up to 16 sub units can be connected to one main unit.

1 Remove the protection cover on the side of

* Dust cover the main unit.

* FS-V33 (P)/34(P) is a cable, and FS-V33C(P)/34C(P) is a M8 connector.

Output Circuit Diagram

2 Install the amplifier one by one on the DIN rail.

FS-V33(C)/34(C) 12 to 24 VDC

Overcurrent protection circuit

Sensor main circuit

Brown* Black/white Load

Black: control output 1 White: control output 2

0V

FS-V33 (C)P/V34(C)P

4 3

(1) 12-24 VDC (FS-V33C/V33CP only)

recesses on the main unit side until you hear a click sound.

(2) Control output 2 Brown 12 to 24 VDC

Overcurrent protection circuit

2 1

3 Engage the two claws of the child unit with the

Blue

*FS-V33 only

Sensor main circuit

Pin assignment of the connector type

(3) 0 V (FS-V33C/V33CP only)

4 Attach the end units (option: OP-26751) to the

(4) Control output 1 Black/white Load both ends of the connected amplifiers in the same way as in step (2).

Black: control output 1 White: control output 2

5 Sandwich the amplifiers between the end units.

0V Blue*

*FS-V33P only

Tighten the screws at the top (two screws x two units) with a Phillips screwdriver to fix the end units.

1

OP-26751 (a set of two)

Page 2

Connecting Fiber Unit

Making Sensitivity Settings „ Two-point Calibration

1 Open the dust cover in the direction shown by arrow 1.

In this mode, the setting value used will be the mean value of two sensing values obtained with and without a workpiece.

2 Move down the fiber lock lever in the

1 Press the SET button without any workpiece placed in front of the fiber unit.

direction shown by arrow 2.

3 Insert a fiber unit into the fiber insertion holes DSC to a length of the fiber insertion sign (i.e., approximately 14 mm).

1 2

4 Move down the fiber lock lever in the

2 Place a workpiece placed in front of the fiber unit, and press the SET button.

Fiber insertion sign direction shown by arrow 4.

Note

Cable outer dia.

Adapter

φ1.3

Adapter A (OP-26500)

φ1.0

Adapter B (OP-26501)

Workpiece

If a thin fiber unit is used, an adapter provided with the thin fiber unit will be required. Unless the right adapter is connected, the thin fiber unit will not detect targets correctly. (The adapter is supplied with the fiber unit.)

DSC

1 2

When the setting is completed, the setting value is displayed.

Appearance

If the sensitivity difference does not have enough room, flashes for about two seconds after the calibration is complete. The set value is stored in memory even in that case.

„ Maximum Sensitivity Setting Set the sensitivity without a workpiece in the case of the reflective model, and with a workpiece in the case of the through-beam or retro-reflective model.

• To connect the coaxial reflective type fiber unit to the amplifier, connect the single-core fiber to the transmitter side, and connect the multiple-core fiber to the receiver side.

Reflective DSC

1 2

Thrubeam 3 sec or longer

Single-core fiber

Transmitter

Press the SET button for three seconds in the state as shown in the above figure. (Release the button when SET flashes.) The setting value is set slightly higher than the received light intensity at the time of setting the sensitivity.

Receiver

„ Full Auto Calibration

Multi-core fiber

In this mode, the setting value will be set to the mean value of the maximum and minimum incident values obtained within a certain period. Use this mode to detect moving workpieces.

External Input

1 Signals can be input externally by selecting an external input function (page 5, No. 5). 2 The signal can be accepted by short-circuiting the pink wire for 2 ms or more as

1 Press the set button for a minimum of three seconds while the target workpiece is passing the sensing area of the fiber unit. • While the set button is pressed, the sensitivity of the sensor will be set according to the incident values.

shown below for each model (20 ms for OFF). FS-V33P/V34P

Brown *

Brown *

+V

+V Workpiece

FS-V33/V34

Pink

Blue *

0V

Pink

Blue *

DSC

1 2

When the setting is completed, the setting value is displayed.

0V

* FS-V33/V33P only. * Setting using an external input is up to 1 million times. * No inputs are accepted while setting each mode.

• After the setting is completed, the setting value is displayed on the digital monitor.

„ Positioning Calibration

When external calibration is selected, the operation is the same as with the SET button.

1 Press the SET button without any workpiece placed in front of the fiber unit. Workpiece

„ Special Function By performing the following operation, both sensitivity setting and scaling can be performed using external input.Select external calibration (page 5, No. 5) and display scaling (page 6, No. 7).The following is the example when using the % calibration. % calibration

DSC

1 2

Display scaling

Input ON

2 Place a workpiece on the position where you want to perform positioning.

Input OFF

% calibration

Workpiece

3 seconds or less

DSC

1 2

% calibration

Input ON

Edge When the setting is completed, the setting value is displayed.

Input OFF 3 seconds or more

Press the SET button for 3 seconds or longer until the display flashes.

Fine-adjusting Sensitivity The setting value can be directly changed by pressing the manual button.

DSC

1 2

1

2

When extended display (page 6, No. 9) is set for the number of digits to be displayed for the received light intensity

1 Press the manual button quickly once, and check that the setting value flashes. 2 While the setting value is flashing, change the setting value with the Manual button. 2

Page 3

Percentage Calibration

Area Detection Mode This mode is suited to detecting the received light intensity only of a certain range. To set this mode, select the area detection mode at Detection mode selection (page 5, No.4). Received light intensity

This is a calibration method that can set the setting value by percentage with reference to the received light intensity at the time of sensitivity setting. For example, if the target value is set to -10P, the setting value is determined 10% lower than the received light intensity when the SET button is pressed.

1 When selecting the sensitivity setting method (page 5, No. 2), select the % calibration, and set the target value of calibration.

OFF

HI: Upper limit setting value

2 Taking the desired light intensity as a reference (normally without a

ON workpiece), press the SET button.

LO: Lower limit setting value OFF

Set the value so that the upper limit setting value is larger than the lower limit setting value. The unit does not respond when the upper limit setting value is less than or equal to the lower limit setting value.

DSC

1 2

1

2

* While the % calibration is in use, other calibrations (sensitivity setting) cannot be used.

Even when the above condition is satisfied, the unit may not respond when the HI and LO values are close to each other because of hysteresis. Be sure to operate the unit to check whether the values are valid.

Output Selection Either light-ON mode or dark-ON mode is selectable.

„ How to Switch the Upper Limit Setting Value (HI) and the Lower Limit Setting Value (LO)

(1) Press

When the button is pressed, HI or LO and the setting value alternately flash. When the MODE button is pressed while the display alternately flashes, the HI or LO display changes. How to configure the sensitivity setting is the same as when in the normal detection mode.

DSC

1 2

1

2

(2) When Area, Limit setting, Counter, or Alarm is selected, the selection options are NO and NC.

Press (2) within 5 seconds after pressing (1).

Setting the Display Scaling This is the function to adjust the current received light intensity to the ìscaling target value.

Dynamic Sensitivity Correction (DSC) Function

1 When selecting a display value correction function (page 6, No. 7), select the

DSC automatically corrects the setting value according to the changes in the received light intensity when there is no workpiece (output OFF). This function is effective when the light intensity difference is small when judging whether or not there is a workpiece. At Detection mode selection (page 5, No.4), select “Dynamic sensitivity correction mode” beforehand.* How to set the sensitivity is the same as in the normal mode.

display scaling function, and set the target value. (The explanation here deals with the case where the target value is set to 2000.)

2 During the normal display, press the SET button while pressing the MODE button. (Scaling is performed for the current light intensity at this time.)

The DSC indicator illuminates when the DSC function is set. DSC

1 2

DSC indicator

* *

2

The display changes as follows, and the target value (which is 2000) to be set as a scale is displayed.

DSC

1 2

*

1

1

2 DSC

When Light ON is selected, the upper limit of the correctable range is twice as much as the initial setting value. The value is stored in memory even after the power is turned off. The DSC indicator flashes when the light intensity during output OFF greatly fluctuates or the L/D ON selection is inappropriate. In such a case, check the setting again.

1 2

1

2

Ø The scaled value is displayed. DSC

1 2

1

2

Edge Detection Mode The reference light intensity can be set in the following range in reference with the currently received light intensity:

This mode detects the change in the received light intensity during a given period of time. (Set at page 5, No. 4) Rising edge detection

Detects the increase (rising edge) of the received light intensity

Falling edge detection

Detects the decrease (falling edge) of the received light intensity

„ Filter Setting Basically, leave this setting as its initial value. If the passage interval of workpieces is too short for the unit to respond, strengthen the level and try again. The selectable filter level differs depending on the power modes. Filter level

HSP*

FINE

TURBO

SUPER

ULTRA

Default state

5

8

9

9

9

9

Setting range

1 to 5

4 to 8

5 to 9

6 to 9

8 to 9

9 only

Power mode

Minimum value

Maximum value

HIGH SPEED

Approx. 1/20 times

Approx. 16 times

FINE

Approx. 1/20 times

Approx. 16 times

TURBO

Approx. 1/20 times

Approx. 16 times

SUPER

Approx. 1/40 times

Approx. 8 times

ULTRA

Approx. 1/160 times

Approx. 2 times

MEGA

Approx. 1/320 times

Approx. 1 time

If the value exceeds the range, 'TT is displayed and scaling is performed up to the possible range.

• No value can be set when the Edge detection mode is selected. • The value is stored in memory even after the power is turned off. • External input can be used when using FS-V33(P)/34(P) (page 5, No.5).

MEGA

Zero-shift Function

*HSP: HIGH SPEED As the number becomes smaller, the filter becomes stronger, which makes the unit difficult to respond to gradual changes in light intensity.

The Zero-shift function is used to forcibly set the current light intensity to zero.

1 At Display value correction function selection (page 6, No.7), select “Zero-shift function”. 2 When the SET button is pressed while the MODE button is pressed, the current

„ Making Sensitivity Settings light intensity is forcibly set to zero.

The sensitivity is set to maximum when the SET button is pressed quickly once. When the setting value is too low and the unit detects objects other than the workpiece, fine-adjust the setting value to a higher number.

DSC

„ Operation When Switching Outputs Setting

1 2

L-ON

Normally OFF. Turns ON only when the light intensity changes.

D-ON

Normally ON. Turns OFF only when the light intensity changes.

1

2

• This function cannot be used when the Dynamic sensitivity correction (DSC) or Edge detection mode is selected. • The value is stored in memory even after the power is turned off. • External input can be used when using FS-V33(P)/34(P) (page 5, No.5).

Operation

3

Page 4

Display Selection

Key Lock Function

The factory default value is “1” only. Other items can be displayed only after being selected at Display customization selection (page 6, No. 8).

The key lock function disables the operation of all keys.

1 While pressing the MODE button, press the

(1)

Press

DSC

Parameter

DSC

Current received light intensity

MODE

DSC

1 2

MODE

Press

(2)

) button for at least three

(7)

Power mode

Current received light intensity

( seconds.

MODE

Press

1

2

The same steps can be taken to deactivate key lock.

DSC

(6)

By selecting the key lock (page 6, No.12) level (1-3), key operations to be disabled can be changed. (The default value is level 1.)

DSC

Extension display (received light intensity) *1

DSC

MODE

Press

Excess gain (%) Hold value *4

(3) DSC

Bar display *2

Current received light intensity

Bar display *2

(5) DSC

DSC

Excess gain (%) *3

Received light Received light intensity intensity Hold value *4 Hold value *4

*1 When ULTRA/MEGA mode is selected, the current received light intensity can be displayed up to 5 digits. The setting value flashes when the button is pressed once. The setting can be changed by pressing the button while flashing. *2 The excess gain is displayed in a 5% increment from 85 to 115%. *3 The current light intensity for the setting value is displayed in percentage. *4 Holds and displays the peak value and the bottom value.

2

3

° c c c c

Channel selection (p.1)

Channel selection switch c c c

Output selection (p.2)

L/D ON

°

°

°

Menu selection (p.5)

Press and hold MODE

°

°

Level Advanced Operations

2

3

L/D ON + press and hold SET

°

°

°

Display scaling (p.4)

MODE + quickly press SET

° c c

Zero shift (p.4)

MODE + quickly press SET

° c c

Direct access menu (p.7)

Press and hold

°

°

Display OFF/ON (p.6)

L/D.ON + press and hold MODE c c c: °: :

„ User-friendly Functions (Direct Access Menu)

Button 1

Initialization (p.2)

How to reset peak or bottom value (with the (5)/(6) display) The value can be reset by pressing the SET button for 3 seconds or more while pressing the MODE button. With FS-V33(P)/34(P), the value can be reset externally by selecting Reset at External input function selection (page 5, No.5).The peak/bottom value is also reset after the power is turned off.

The hold display (5/6) can be set in detail by pressing the onds or longer.

SET

1

Sensitivity fine-adjustment (p.3)

MODE

Press

Button

Sensitivity Setting (p.3)

MODE

MODE

DSC

Basic Operations

Press

Press (4)

Level

Excess gain (%) Hold value *4 c

Normal operation is possible. Operation is not possible. The settings can be checked but cannot be changed.

PIN Number Key Lock Function button for 2 sec-

The unit can be locked using a PIN number to ensure securer locking effect.

1 While pressing the MODE button, press the

(

) button 10 times.

DSC

Press for 2 seconds or longer. DSC

MODE

Press

Hold display selection Select the setting by pressing the button. . Updates every time the current light intensity is less (or more) than the specified peak and bottom values. . Displays the maximum and minimum peak values since the power is turned on (total number). . Displays the maximum and minimum bottom values since the power is turned on (total number). . Displays the minimum peak value and the maximum bottom value since the power is turned on (total number). . Displays the maximum peak value and the minimum bottom value since the power is turned on (total number).

DSC

1 2

Follow the same step to disable the key lock. Use the same PIN number used for locking.

Note Write down the PIN number in case it is forgotten. The key lock cannot be disabled unless the correct PIN number is used.

DSC for 2 seconds or longer.

DSC

Press to select (see page 5, No. 1).

Press to select (see page 5, No. 5).

2

2 Select a PIN number between 0 and 9999 using the button. 3 Press the MODE button to activate key lock.

The power mode and emission power for the power mode display (7) can be switched by pressing the button for 2 seconds or longer.

Press

1

MODE

Press DSC

MODE

Press

4

Page 5

Operation Configuration

Detection Setting Menu

Normally, this unit can be used in the basic settings. Set other functions as necessary. Pressing

MODE

From the basic menu for 3 seconds or longer displays the basic menu.

Select a function with the button, and press

MODE

DSC to confirm.

MODE

The setting for each item is confirmed when selecting END and pressing

MODE

Press

.

DSC

3

1. Power mode selection 2. Sensitivity setting method selection

Basic setting menu

Press

When VQ(( is selected

When other than VQ(( is selected

3. Timer mode selection 4. Detection mode selection 5. Light emission power selection

Detection setting menu

Timer mode selection Select the setting by pressing the button. Timer OFF OFF-delay ON-delay One-shot ON-delay OFF-delay *1 ON-delay One-shot *1

MODE

DSC

Timer setting Configure setting by pressing the button. Can be set between 0.1 and 9999 ms. When 1 is selected, ON-delay timer is set.

MODE

Press

6. Display value correction function selection 7. Display reverse selection 8. Display customization selection

Display setting menu a b

At Timer mode selection, * other than 1 is selected * 1 is selected b a

DSC

Timer setting 2

9. APC function setting 10. Power save mode setting 11. Key lock level setting 12. Interference prevention function setting

System setting menu

Sets the time of OFF-delay (One-shot).

or

Configure setting by pressing the button. Can be set between 0.1 and 9999 ms.

DSC

MODE

Press

4 Detection mode selection DSC

Basic Setting Menu

MODE

Press

Set the channel selection switch to "1".

1

2

When dSc is selected

When Std or ArEA is selected

Channel selection switch MODE

Press for 3 seconds or longer

Select the setting by pressing the button. . Normal (light intensity) detection mode . Dynamic sensitivity correction mode (see page 3) . Area detection mode (see page 3) . Detects the rising edge of the received light intensity (Edge detection mode) (see page 3) . Detects the falling edge of the received light intensity (Edge detection mode) (see page 3)

DSC

Detection operation selection Select the setting by pressing the button. . Mainly reflective [Light intensity with workpiece > Light intensity without workpiece] (The output is ON when the light enters.) . Mainly thrubeam [Light intensity with workpiece < Light intensity without workpiece] (The output is ON when the light is blocked.)

MODE DSC

Press

1 Power mode (response time) selection Select the setting by pressing the button. . HIGH SPEED: 33 µs . FINE: 250 µs . TURBO: 500 µs . SUPER: 1 ms . ULTRA: 4 ms . MEGA: 16 ms (Can be switched when the power selection switch is set to SEL.)

MODE

Press

DSC

DSC

Correction speed selection Select the setting by pressing the button. 1 to 3 The correction is made faster as the number becomes larger. (Select 1 in normal cases.)

MODE

2 Sensitivity setting method selection

Press

Select the setting by pressing the button. Normal sensitivity setting (see page 2) % calibration (see page 2)

. .

MODE

Press

Power mode

When SEtP is selected

When Std is selected

Level 1 Level 2 Level 3 hSP

7.34s 114.7ms 1.8ms

FinE

52.43s 819.2ms 12.8ms

Turb/SuPr/Ultr/MEGA 104.86s 1.64s

DSC

A

MODE

Press

Percentage calibration target value setting Select the setting by pressing the button. Can be set between –99 and +99%.

25.6ms

When Edge detection is selected DSC

Filter time selection Select the setting by pressing the button. Select larger number (initial state) in normal cases. The selectable level depends on the power modes. (see page 3)

DSC

MODE

Press When StG-Func is selected

Detection When StG-diSP is selected

Display When StG-SYS When End is is selected selected System

Menu end/continue selection Select the setting by pressing the button. . Ends the menu. . Configures detection settings. (Timer, DSC, etc.) . Configures display settings. (Scaling, inversion, etc.) . Configures system settings. (APC, Power Save, etc.)

MODE

Press

When using FS-V33(P)/ 34(P)

When using FS-V33C(P)/ 34C(P) DSC

5 External input function selection MODE

Press

When other than SCAL is selected

End of basic menu display

When SCAL is selected

Select the setting by pressing the button. • Does not use external input. • External calibration • Display scaling Zero-shift • • Reset • Emission stop

DSC

MODE

Press

DSC

Display scaling target value setting Select the setting by pressing the button. The value can be set between 100 and 10000 in the unit of 100. 10000 is displayed as FuLL.

DSC

MODE

Press

6 Light emission power selection Select the setting by pressing the button.

Power mode Display hSP

FinE

Turb/SuPr/ uLtr/MEGA

Normal Approx. 15% of the normal time

A

5

Approx. 11% of the normal time

Approx. 3% of the normal time

Approx. 1.5% of the normal time

Page 6

Display Setting Menu

System Setting Menu

From the basic menu

From the basic menu

DSC

MODE

MODE

Press

Press

DSC

DSC

7 Display value correction function selection MODE

Press When oFF or ShFt is selected

9 S-APC setting

Select the setting by pressing the button. . Not to be used. . Uses the display scaling function. . Uses the zero-shift function.

Configure setting by pressing the . APC is enabled. . APC is disabled.

When SCAL is selected

About APC (Auto Power Control) In normal cases, use the sensor with APC disabled. When APC is enabled, the light intensity is monitored and corrected in order to maintain regular light transmission. If the environment is sufficiently clean, a highly accurate detection can constantly be performed. Note: Long-term use of APC imposes heavier load on the LED than when disabled.

MODE

Press

DSC

MODE

Press

DSC

Display scaling target value setting Configure setting by pressing the button. The value can be set between 100 and 10000 in unit of 100. 10000 is displayed as FuLL.

8 Display reverse selection

DSC

10 Power save mode setting

Select the setting by pressing the button. . Normal display Reverses the display. . Even when the display is reversed, the green light indicates setting values, and the red light indicates received light intensity.

MODE

Press

Configure setting by pressing the button. . Saves power (Turns off the display). While the power save mode is activated, only one segment on the digital monitor remains displayed. . Normal display MODE

To turn all the displays OFF (both digital monitor and operation status indicators) ALL can be selected when is pressed for 3 seconds or longer while “on” is selected. To restore the display from Display OFF, press MODE and L/D ON buttons simultaneously for 3 seconds or longer.

Press

9 Display customization selection

DSC

Select the setting by pressing the button. . Does not customize the display. . Customizes the display.

MODE

Press When no is selected

When no is selected

DSC

11 Key lock level setting (see page 6) Select the setting by pressing the Level 1 Level 2 Level 3

DSC

(1)

. . .

MODE

Normal

Press

MODE

Press (2)

button.

DSC

DSC

Expansion

MODE

Press DSC

(3)

Extension bar

MODE

Press

DSC

(4)

Excess gain (%)

Selectable display setting The items shown left are displayed in order every time the MODE button is pressed. (see page 3) Select the setting by pressing the button. . Adds the item to the selectable display. . Deletes the item from the selectable display.

12 Selecting the number of units of interference prevention Select the setting by pressing the button. . Normal . The number of units of interference prevention is twice as many as in the normal time. (The response time is also twice as long as in the normal time. The detection distance is the same as in the normal time.)

MODE

Press

Back to A of the basic setting.

MODE

Press

Initializing, Saving and Loading the Settings

DSC

(5)

HOLD

„ Initializing the settings

MODE

Press (6)

button.

1 While pressing , press for 5 seconds or longer. 2 Select “T5V“with the button, and press . 3 Select with the button, and press to initialize. L/D ON

DSC

SET

MODE

HOLD Excess gain (%)

MODE

MODE

Press

Default setting Power mode: FAIN Detection mode: Normal Setting value: 50 Output selection: L ON

DSC

(7)

Power mode

MODE

Press

Back to A of the basic setting.

„ Saving the Settings

1 While pressing , press for 5 seconds or longer. 2 Select “5#X'” with the button, and press . 3 Select “;'5” with the button, and press to save. L/D ON

MODE

Reference

When setting each mode, the display returns normal by pressing the button for 3 seconds or longer.

SET

MODE

MODE

„ Loading the setting

1 While pressing , press for 5 seconds or longer. 2 Select “T5V” with the button, and press . 3 Select “=X5V” with the button, and press to load. L/D ON

SET

MODE

MODE

6

Page 7

Channel Selection Switch 2

Special Functions of Channel 2 „ Limit Setting

1

To set channel 2, set the channel selection switch to "2".

2

This function issues a prediction alarm when the light intensity difference is small when judging whether or not there is a workpiece. Two types of limit setting function are available:

Channel selection switch

DSC

Peak limit setting Samples the peak values of setting value while the received light intensity is higher than the output 1 setting value, and issues an alarm when the minimum peak value is lower than the output 2 setting value.

MODE

Press for 3 seconds or longer

DSC

Bottom limit setting Samples the bottom values of setting value while the received light intensity is lower than the output 1 setting value, and issues an alarm when the maximum bottom value is higher than the output 2 setting value.

Output 2 function selection Select the setting by pressing the button. • Normal (light intensity) detection • Used as limit setting output. • Used as counter output. • Used as alarm output.

Peak hold minimum value When Std is selected

When LiMt is selected

Setting value when PEAk is selected 1ch value Setting value when botm is selected

DSC

Limit function setting Select the setting by pressing the button. • Sets the peak value. • Sets the bottom value.

MODE

Press

Bottom hold maximum value

1ch output

DSC

(Instantaneous display)

2ch output (PEAk setting value) 2ch output (botm setting value) DSC

(Normal display)

Channel 2 normal display when using the limit setting function DSC

When Cnt is selected

Alternate display

DSC

Counter function setting Select the setting by pressing the • Over count mode 1 • Over count mode 2 • Auto reset mode

MODE

Press When ovr1/ovr2 is selected

When Auto is selected button.

DSC

Setting value Peak/bottom value

How to reset the peak/bottom value The value can be reset by pressing the SET button for 3 seconds or more while pressing the MODE button. With FS-V33(P)/34(P), the value can be reset externally by selecting Reset at External input function selection (page 5, No.5). The peak/bottom value is also reset after the power is turned off.

DSC

One-shot time setting Select the setting by pressing the button. The value can be set between 0.1 and 9999 ms.

MODE

Press

Pressing the button can adjust the setting value.

„ Counter Function

DSC

(Instantaneous display)

This mode counts the output (edge of OFF to ON) of output 1, and compares it with the setting value. The following three count modes are available:

DSC

(Normal display)

Over counter 1

Q7T

When AlrM is selected

Over counter 2

The output turns ON with the value higher than the setting value.The counter value increases until it is reset. The output turns ON only when the value is the same as the setting value.The count value increases until it is reset.

DSC

#XVQ

(Instantaneous display)

One-shot output is performed when the value is the same as the setting value, and the count value is automatically reset.

Auto reset

DSC

(Normal display)

Channel 2 normal display when using the counter function DSC

DSC

(Instantaneous display)

Alternate display DSC

DSC

(Normal display)

Setting value

Count value

Pressing the button can adjust the setting value. The setting value can be displayed up to 65.535 on the Extension display (page 6, No. 9).

How to reset the count value The value can be reset by pressing the SET button for 3 seconds or more while pressing the MODE button. With FS-V33(P)/34(P), the value can be reset externally by selecting Reset at External input function selection (page 5, No.5). The count value is also reset after the power is turned off.

„ Alarm Output Function When using the APC function, the alarm output is issued when the load on the LED is too large.The alarm output is also issued when the DSC indicator is flashing (refer to Dynamic Sensitivity Correction (DSC) Function on page 4). Channel 2 normal display when using the alarm output function

Normal DSC

7

When the load on the LED is greater DSC