The text of a manual · part 10 of 12
Visual KV Series User's Manual 1: Installation, pages 81 to 90
Pages 81 to 90 of 102
The original document is the PDF (964 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Keyence KV-E4X
Page 81
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit) ■ Output circuit diagram
Visual KV Series
Internal circuit
Y0
V3
Y2
C2
Y1
Y3
V4
*
* For KV-E4XTP
PNP
NPN
Internal circuit
Y0 to Y3
Internal circuit
Insulating power supply
C2
Insultating power supply
C2
Y0 to Y3
• V1 to V2 and V3 to V4 are short-circuited inside (so they can be used as relay terminal blocks).
Chapter 1 Configuration and Specifications
1-57
11
Page 82
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
1.10.5 Dimensions
Visual KV Series
■ Main unit
Front view
Side view
35.4 90
45
4 43.5
■ Metal fixture for screw tightening
4-ø5.0
1
(Mounting hole) Main unit mounting hole* (2 positions)
99 111
25 38 t=2
* Two M3.5 countersunk-head screws are included for mounting the main unit.
1-58 Chapter 1 Configuration and Specifications
4
Page 83
1.11 KV-D20 (Operator interface panel)
1.11 KV-D20 (Operator Interface Panel) Visual KV Series
This section describes the name and function of each part, the general specifications, the functional specifications, and dimensions of the operator interface panel.
1.11.1 Part Names and Functions 1 Customized indicator lamps
1
2
3
4
5 Communication port (provided on rear face) 2 Liquid crystal display screen 6 Bit guide
7 6 5 4 3 2 1 0
F1
F2
F3
F4
11 3. Customized switches
N o.
N ame
1
Cust omiz ed indicat or lamps
2
Liquid cry st al display screen
3
Cust omiz ed swit ch
4
5
6
4. Setting operation switches
Funct ion Assigned to special utility relays as follows. Lamp 1: 2504 Lamp 2: 2505 Lamp 3: 2506 Lamp 4: 2507 When a relay turns ON, the corresponding LED becomes lit. Displays ladder comments (up to 20 characters) and all devices in KV Series. Assigned to special utility relays as follows. F 1: 2500 F 2: 2501 F 3: 2502 F 4: 2503 When a switch is turned on, the corresponding relay turns ON.
S et t ing operat ion Changes screen display. swit ches RJ-11 Modular connector. Used for communication between KV basic units while Communicat ion connected to the basic unit's communication port with an port accessory cable (OP-26487). This port also supplies driving power for the KV-D20. Shows the corresponding number of each bit on the KV-I/O B it guide monitor screen, the operator screen, or the 8-bit ON/OFF indication in the device mode.
Chapter 1 Configuration and Specifications
1-59
Page 84
1.11 KV-D20 (Operator interface panel)
1.11.2 General Specifications Item
Visual KV Series
Supply voltage
Supplied from the communication port of the KV (5 VDC)
Current consumption
5 VDC, 180 mA max. (60 mA max. when converted for 24 V)
Ambient temperature
0 to +50°C (32 to122°F), No freezing
Relative humidity
35 to 85%, No condensation
Ambient storage temperature
-20 to +70°C (-4 to 158°F), No freezing
Withstand voltage
Noise immunity Vibration Insulation resistance Operating atmosphere
1
Specifications
Weight Enclosure rating
1,500 VAC for 1 minute (Between power terminal and I/O terminal as well as between entire external terminals and case) 1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by noise simulator) Conforms to EN standard (EN61000-4-2/-3/-4/-6) 10 to 55 Hz, double amplitude: 1.5 mm, 2 hours in each of X, Y and Z axis directions 50 MΩ or more (Between power terminal and I/O terminal as well as between entire external terminals and case by 500 VDC megohmmeter) No excessive dust or corrosive gases. Main unit: Approx. 160 g Communication cable: Approx. 60 g Mounting fixture: 30 g (2 pieces) Built-in panel, IP-65F only for the front operation panel
1.11.3 Functional Specifications Item Number of connectable units Display screen
Specifications 1 per basic unit Blue-negative type backlighted LCD, 20 digits x 4 lines
Character size
2.95 x 4.75 mm (5 x 7 dots) 4 switches assigned to special utility relays F1: 2500 F2: 2501 F3: 2502 F4: 2503
Customized switches Setting operation switch Customized indicator lamps
Four red LEDs assigned to special utility relays Lamp 1: 2504 Lamp 2: 2505 Lamp 3: 2506 Lamp 4: 2507
1-60 Chapter 1 Configuration and Specifications
Page 85
1.11 KV-D20 (Operator interface panel)
1.11.4 Dimensions ■ Main unit
75
112
Visual KV Series
Panel thickness: 1.0 to 3.0 mm
67
34
5
133 (including mounting fixtures)
■ Panel cut size
11
145 +1
68 0
+1
105 0
83
Chapter 1 Configuration and Specifications
1-61
Page 86
Visual KV Series
1
1-62 Chapter 1 Configuration and Specifications
Page 87
Visual KV Series
Chapter 2 System Installation This chapter describes the installation and connection of each Visual KV Series unit as well as system maintenance. 2.1
Installation Environment ......................................................... 1-64
2.1.1 2.1.2 2.1.3 2.1.4 2.1.5
Installation Environment ........................................................................ 1-64 Installation Position ............................................................................... 1-65 Installation Procedure ........................................................................... 1-66 Cautions on Wiring for Each Unit .......................................................... 1-67 Contact Protection ................................................................................. 1-69
2.2
Connecting Visual KV Series Expansion Units .................... 1-70
2.2.1 2.2.2 2.2.3 2.2.4
Visual KV Series Expansion Units ........................................................ 1-70 Connecting Visual KV Series Expansion Units ..................................... 1-71 Confirming the Connection Settings of Expansion Units ....................... 1-74 Transferring I/O Information between Expansion Units and the Basic Unit ........................................................................................ 1-77
2.3
Inspection and Maintenance ................................................... 1-78
2.3.1 2.3.2
Inspection .............................................................................................. 1-78 Maintenance .......................................................................................... 1-78
Page 88
2.1 Installation Environment
2.1 Installation Environment Visual KV Series
This section describes cautions with the environment in which each unit is installed and the installation position inside the panel.
2.1.1 Installation Environment Never install a unit in the following locations:
2 CAUTION
1-64
•
Locations exposed to direct sunlight
•
Locations whose ambient temperature is outside the allowable range of 0 to +50°C
•
Locations whose ambient humidity is outside the allowable range of 35 to 85% RH
•
Locations subject to drastic temperature change where condensation may occur
•
Locations with corrosive or flammable gases
•
Locations with excessive dust, salt, iron powder, or soot
•
Locations subject to direct vibrations and impacts
•
Locations subject to splashes of water, oil, chemicals, etc.
•
Locations where a strong magnetic or electrical field is generated
Units are made of synthetic resin. If the unit surface touches a solvent with a strong dissolving force, it could melt. Keep such solvents away from the units.
Chapter 2 System Installation
Page 89
2.1 Installation Environment
2.1.2 Installation Position
Front installation
Installation on ceiling
Correct
Incorrect
Upward installation *
Vertical installation
Correct
Incorrect
Visual KV Series
■ Installation direction When attaching a unit inside a panel, install the unit so that the front face (equipped with the Access Window, communication ports, etc.) faces front or upwards.
12 * Upward installation does not comply with CE marking.
■ Distance between adjacent panels/equipment When installing a unit, keep the distances shown below between the panel or equipment so that the power supply can release heat.
20 mm
10 mm Unit
20 mm
Note 1: If the temperature inside the panel exceeds 50°C, which is specified as the maximum ambient operating temperature, then install heat exchangers, etc. to reduce the temperature. Note 2: Ensure sufficient ventilation space so that the power supply can release heat. Note 3: Never install a unit just above any equipment which generates a lot of heat.
Chapter 2 System Installation
1-65
Page 90
2.1 Installation Environment
2.1.3 Installation Procedure This section describes how to attach a connected unit directly to a panel, to a DIN rail, or to a DIN rail with an expansion unit spacer.
Visual KV Series
■ Attaching a unit directly to a panel Attach the metal fixture for screw tightening to each KV Series unit using the countersunk-head screws through the countersunk holes. Mount the fixture directly to the panel.
■ Attaching a unit to a DIN rail Hang an upper claw of a Visual KV Series basic unit to the upper side of the DIN rail, and press the basic unit onto the DIN rain until a click sound is heard.
2
■ Removing a unit from a DIN rail Pull a lower claw of a Visual KV Series basic unit downward from the front direction using a screwdriver, and then remove the basic unit from the DIN rail.
Expansion unit spacer When an expansion unit spacer is attached to a Visual KV Series expansion unit, its height becomes flush with an AC power type Visual KV Series basic unit. The procedure to attach a Visual KV Series expansion unit to an expansion unit spacer is the same as the procedure to attach a Visual KV Series unit to a DIN rail. Refer to the instruction manual supplied with the Visual KV Series for DIN rail mounting.
■ Dimensions for expansion unit spacers OP-35342 Spacer for 4-I/O expansion unit
OP-35343 Spacer for 8-I/O expansion unit
ø4.0
ø4.0
42.8
28 38
OP-35344 Spacer for 16-I/O expansion unit
ø4.0
42.8
35 45
42.8
55 65
25.3
4 66
1-66
Chapter 2 System Installation