Page 91
2.1 Installation Environment
2.1.4 Cautions on Wiring for Each Unit
Visual KV Series
This section describes cautions to keep in mind when wiring is performed for I/O units. Be sure to read this section before starting wiring.
Wiring procedures for basic units The wiring procedures for basic units are described below.
CAUTION
•
Turn off the power before starting wiring.
•
For the installation position, select a location whose ambient temperature is 0 to +50°C, whose ambient humidity is 35 to 85% RH, and one which is not subject to drastic temperature changes.
•
If the 24 VDC + output terminal and the 24 VDC - output terminal are switched, the power supply unit and connected units may be damaged. Never switch them.
•
Be sure that the sum of the current consumption of all connected units does not exceed the output capacity of the service power supply. If the system is operating in an overload status, the internal circuits may generate heat or be damaged. To recover from an overload status, disconnect some of the connected units.
•
Never connect the DC output of any other power supply, either in serial or parallel, to the 24 VDC output terminals. If the DC output is connected, the power supply unit may be damaged.
■ Wiring for an AC type basic unit For an AC type basic unit, perform the wiring as shown in the figure below.
KV-16AR
C1
001
KV-16AR
003 002
000
EYENCE
0
0
1
007 006
1
2
3
4
5
009
IN
008
2
3
4
5
6
7
8
9
5ch 500
24V-OUT-OV
Bottom
005 004
0ch
501 C3
502 C4
504 503
505
OUT
24 VDC service power supply (supplied from outside)
Breaker
100 to 240 VAC ±10% Insulating transformer, noise filter, etc.
Grounding
Note 1: Connect an insulating transformer (1:1) or noise filter to reduce line noise. Note 2: Use twisted cables to reduce induction effects. Note 3: When using a basic unit in a location with a lot of noise, the noise may be reduced by completely grounding the basic unit.
Chapter 2 System Installation
1-67
12
Page 92
2.1 Installation Environment ■ Wiring for a DC type basic unit For a DC type basic unit, perform the wiring as shown in the figure below.
Visual KV Series
KV-10DR
001
000 C1
002
KV-10DR
003
004
005
IN
503
OUT
C2
EYENCE
0ch 0
1
0
1
2
3
2
3
4
5
5ch 501
24V-IN-OV
500
C3
502 C4
Breaker 24 VDC external power supply
Note: Connect the power supply to the power supply input terminals with 24 VDC output, which offers a sufficient margin of power capacity. Usually, the sum of the current consumption of all connected units multiplied by 1.5 or more is required for the power capacity.
Cautions on wiring for I/O units
2
When performing wiring for an I/O unit, pay strict attention to the following contents. • • • • •
Separate input lines from output lines in wiring. If the wiring for power is located near I/O signal lines, a malfunction may occur caused by the effects of a high voltage and large current. Keep I/O signal lines away from the power wiring by at least 100 mm. Separate 24 VDC I/O lines from 100 VAC and 200 VAC lines. When using pipes for wiring, make sure that the pipes are securely grounded.
■ When I/O signal lines cannot be separated from the wiring for power In such a case, perform grounding on the KV side using batch-shielded cables. (In some environments, grounding should be performed on the reverse side of the KV.) Shielded cable
KV
Sensor
Input
RL
Output
24 VDC
Ground
Terminal The terminal screws used are M3. When performing wiring with crimp-style terminals, use the following ones. Unit: mm 6.0 maximum
6.0 maximum M3
1-68
Chapter 2 System Installation
Page 93
2.1 Installation Environment
Because the Visual KV Series is constructed to be sufficiently resistant to noise, it can usually be used without being grounded. However, when the Visual KV Series is used in an environment with a lot of noise, grounding is required. In such a case, pay strict attention to the following contents. • •
Perform complete grounding for each individual unit. In this case, the ground resistance should be 100 Ω or less. If individual grounding is not possible, perform common grounding. In this case, the length of each grounding cable should be equal. Acceptable
Recommended
KV
Other device
Unacceptable
KV
Other device
A
B
Other device
KV
B A
A=B
Complete grounding
Visual KV Series
Cautions on grounding
A>B A<B
2.1.5 Contact Protection If inductive loads such as clutches, motors, and solenoids are used, a rush current may flow when the load power supply is turned on, or a counter electromotive voltage may be generated when the load power supply is shut down. The rush current and the counter electromotive voltage can contribute considerably to shortening the service life of the contacts. To prevent this from happening, provide a contact protection circuit. ■ Contact protection circuit examples For DC load 1
For AC load 1
Contact
Contact
Load
Load
CR circuit
For DC load 2
For AC load 2 a
Contact
Diode b
Contact
Zener diode Varistor
When the supply voltage is 24 to 48 V, provide a protection circuit in position "b". When the supply voltage is 100 to 200 V, provide a protection circuit in position "a". Note 1: Use a load coil whose rating is less than the contact capacity. Note 2: Use a diode whose peak inverse voltage is 10 times or more the circuit voltage and whose forward current is not less than the load current. Note 3: Individually attach diodes, varistors, and CR circuits directly to the relay coil terminal.
Chapter 2 System Installation
1-69
12
Page 94
2.2 Connecting Visual KV Series Expansion Units
Visual KV Series
2.2 Connecting Visual KV Series Expansion Units This section describes the method to connect Visual KV Series expansion units to a Visual KV Series basic unit and the various functions of expansion units.
2.2.1 Visual KV Series Expansion Units Visual KV Series expansion input units
KV-E4X
KV-E8X
KV-E16X
Visual KV Series expansion output units
2 KV-E4R
KV-E4T
KV-E8R
KV-E8T(P)
Visual KV Series expansion I/O units
KV-E4XR
1-70
KV-E4XT(P)
Chapter 2 System Installation
KV-E16R
KV-E16T(P)
Page 95
2.2 Connecting Visual KV Series Expansion Units
•
Connect a basic unit and an expansion unit with an expansion cable.
•
An expansion cable approximately 60 mm long is provided as standard.
•
When extending the expansion cable, use long expansion cables (300 mm) (OP-35361).
•
Up to two expansion cables (300 mm) can be connected to one basic unit.
•
The READY/ERROR LED is lit during normal communication, flashes when an abnormality occurs, and is not lit when the power is not supplied correctly. If this LED is not lit, check whether the expansion cables are correctly connected.
Visual KV Series
2.2.2 Connecting Visual KV Series Expansion Units
Standard cable (approx. 60 mm) Basic unit
Expansion unit
Expansion cable (60 mm)
Long cable (approx. 300 mm) Basic unit
Expansion unit
Expansion cable (300 mm)
12
Expansion unit
Expansion cable (300 mm)
Standard cable (approx. 60) + Long cable (approx. 300 mm) Basic unit
Expansion unit
Expansion cable (60 mm)
CAUTION
Expansion unit
Expansion cable (300 mm)
Be sure to turn off the power before connecting or disconnecting expansion cables. If they are connected or disconnected while the power is on, the units may be damaged or fail. Note: Keep noise sources such as power cables and electromagnetic switches away from expansion cables (300 mm) as much as possible.
Chapter 2 System Installation
1-71
Page 96
2.2 Connecting Visual KV Series Expansion Units
Connection methods
Visual KV Series
1. Peel off the tape stuck to the right side of the basic unit.
2. Connect an expansion cable to the connector.
■ When extending a cable Replace a standard expansion cable (60 mm) with an optional expansion cable (300 mm) (OP-35361).
2
1. Disconnect the standard expansion cable from the expansion unit connector.
2. Connect an optional expansion cable (300 mm) to the expansion unit connector. 3. Connect the optional expansion cable (300 mm) to the basic unit connector.
1-72
Chapter 2 System Installation
Page 97
2.2 Connecting Visual KV Series Expansion Units
Number of connectable units
Basic unit
Input
Output
Input
Expansion units Input Output
Output Output
Visual KV Series
● When the basic unit is a KV-10xx/16xx/24 xx Up to four input units and four output units (that is, up to 8 total expansion units) can be connected to one basic unit. Input
Up to 8 units
● When the basic unit is a KV-40 xx Up to three input units and four output units (that is, up to 7 total expansion units) can be connected to one basic unit. Basic unit
Output
Output
Expansion units Input Output Input
Output
Input
12 Up to 7 units
● When KV-E4XT/KV-E4XR expansion I/O units are connected One I/O unit is regarded as two units (that is, one input and one output unit). For example, when only expansion I/O units are connected to one basic unit, up to four expansion I/O units can be connected. Up to three expansion I/O units can be connected to a KV-40 xx basic unit. When two expansion I/O units are connected
Basic unit
Input Output
Input
I/O
1 0
1 1
Expansion units I/O Output
6 units 1 1
0 1
Output
Input
0 1
1 0
=4 =4
Note 1: There are no restrictions about the order of connected expansion units. Note 2: When connecting expansion units to an AC power type basic unit, be sure that the total current consumption of all connected units does not exceed the output capacity of the Visual KV Series basic unit. Otherwise, consider to use a DC power type basic unit in conbination with an external DC power supply having enough capacity.
Chapter 2 System Installation
1-73
Page 98
2.2 Connecting Visual KV Series Expansion Units
2.2.3 Confirming the Connection Settings of Expansion Units
Visual KV Series
Relay No. (unit No., address No., contact No.) The relay No. of each expansion unit is automatically assigned in the order of connection.
Expansion unit relay list ■ Input units Connection order 1st input unit 2nd input unit 3rd input unit 4th input unit
KV-E4X KV-10/ KV-40 16/24
KV-E8X KV-10/ KV-40 16/24
KV-E16X KV-10/ KV-40 16/24
100 to 103
200 to 203
100 to 107
200 to 207
100 to 115
200 to 115
200 to 203
300 to 303
200 to 207
300 to 307
200 to 215
300 to 315
300 to 303
400 to 403
300 to 307
400 to 407
300 to 315
400 to 415
400 to 403
–
400 to 407
–
400 to 415
–
■ Output units Connection order 1st output unit 2nd output unit 3rd output unit 4th output unit
2
KV-E4T/R
KV-E8T(P)/R
KV-E16T(P)/R
600 to 603
600 to 607
600 to 615
700 to 703
700 to 707
700 to 715
800 to 803
800 to 807
800 to 815
900 to 903
900 to 907
900 to 915
■ I/O units KV -E4X R/ T(P ) Connect ion order 1st input unit 2nd input unit 3rd input unit 4t h input unit 1st out put unit 2nd out put unit 3rd out put unit 4t h out put unit
1-74
Input r e la y
Out put r e la y
KV -10/ 16/ 24
KV -40
KV -10/ 16/ 24
KV -40
100 to 103
200 to 203, - 200 to 203
300 to 303, - 300 to 303
400 to 403, - 400 to 403, - - - - 600 to 603
600 to 603, - 700 to 703
700 to 703, - 800 to 803
800 to 803, - 900 to 903
900 to 903
Chapter 2 System Installation
Page 99
2.2 Connecting Visual KV Series Expansion Units
The connection status (connected or unconnected) of a connected expansion unit can be confirmed using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer. ➮
Refer to "Chapter 3. Access Window" (p.1-79), "Chapter 6. Handheld Programmer" (p.1-195), and the "6.2.9. Displaying the Use Status" (p. 2-70).
Visual KV Series
Connection information for expansion units
The connection information is written to data memory DM1937 as shown in the table below. Bit 15
Bit 7 6 5 4 3 2 1 0
Unused ("0" is always written.)
DM1937 display digit Bit 0* Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 *
"0" or "1" is written.
Indication contents Connection of expansion input unit with relay Nos. 0100 to 0115 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0200 to 0215 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0300 to 0315 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0400 to 0415 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0600 to 0615 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0700 to 0715 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0800 to 0815 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0900 to 0915 0: Unconnected or disconnected 1: Connected
Always set to "0" when the KV-40xx is used. KV-40
KV-E8X KV-E4XT(P)
KV-E8R
KV-E16T(P)
In the case of connection above, DM1937 is set as follows. DM1937 (binary) 900 800 700 600 400 300 200 100
Decimal (Hexadecimal) Normal status: 0 1 1 1 0 1 1 0 = #118($0076) * Always set to "0" when the KV-40xx is used.
KV-E16T KV-E8R
KV-E4XT KV-E8X
DM1937 (binary) Decimal (Hexadecimal) When KV-E8X has failed: 0 1 1 1 0 1 0 0 = #116($0074) DM1937 (binary) Decimal (Hexadecimal) When KV-E4XT has failed: 0 1 1 0 0 0 1 0 = #98($0062)
Chapter 2 System Installation
1-75
12
Page 100
2.2 Connecting Visual KV Series Expansion Units
Input time constant for expansion units
Visual KV Series
The initial setting of the time constant is "10 ms" for each expansion unit. The input time constant can be set to "10 µs" using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer. Change the value of special utility relays 2609 to 2612. Special utility relay No. 2609* 2610 2611 2612 *
Function Input time constant of expansion input unit with relay Nos. 0100 to 0115 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0200 to 0215 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0300 to 0315 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0400 to 0415 OFF: 10 ms ON: 10 µs
Not used for the KV-40xx.
Clearing the input value when disconnecting The system can be set so that the input value is cleared when disconnection has occurred for some reason. This setting can be performed using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer.
2
Change the value of special utility relay 2613. Enter "0" or "1". Special utility relay No. 2613
1-76
Chapter 2 System Installation
Function Clears input when expansion is disconnected. OFF: Holds previous value. ON: Clears input.