Page 91

2.1 Installation Environment

2.1.4 Cautions on Wiring for Each Unit

Visual KV Series

This section describes cautions to keep in mind when wiring is performed for I/O units. Be sure to read this section before starting wiring.

Wiring procedures for basic units The wiring procedures for basic units are described below.

CAUTION

•

Turn off the power before starting wiring.

•

For the installation position, select a location whose ambient temperature is 0 to +50°C, whose ambient humidity is 35 to 85% RH, and one which is not subject to drastic temperature changes.

•

If the 24 VDC + output terminal and the 24 VDC - output terminal are switched, the power supply unit and connected units may be damaged. Never switch them.

•

Be sure that the sum of the current consumption of all connected units does not exceed the output capacity of the service power supply. If the system is operating in an overload status, the internal circuits may generate heat or be damaged. To recover from an overload status, disconnect some of the connected units.

•

Never connect the DC output of any other power supply, either in serial or parallel, to the 24 VDC output terminals. If the DC output is connected, the power supply unit may be damaged.

■ Wiring for an AC type basic unit For an AC type basic unit, perform the wiring as shown in the figure below.

KV-16AR

C1

001

KV-16AR

003 002

000

EYENCE

0

0

1

007 006

1

2

3

4

5

009

IN

008

2

3

4

5

6

7

8

9

5ch 500

24V-OUT-OV

Bottom

005 004

0ch

501 C3

502 C4

504 503

505

OUT

24 VDC service power supply (supplied from outside)

Breaker

100 to 240 VAC ±10% Insulating transformer, noise filter, etc.

Grounding

Note 1: Connect an insulating transformer (1:1) or noise filter to reduce line noise. Note 2: Use twisted cables to reduce induction effects. Note 3: When using a basic unit in a location with a lot of noise, the noise may be reduced by completely grounding the basic unit.

Chapter 2 System Installation

1-67

12

Page 92

2.1 Installation Environment ■ Wiring for a DC type basic unit For a DC type basic unit, perform the wiring as shown in the figure below.

Visual KV Series

KV-10DR

001

000 C1

002

KV-10DR

003

004

005

IN

503

OUT

C2

EYENCE

0ch 0

1

0

1

2

3

2

3

4

5

5ch 501

24V-IN-OV

500

C3

502 C4

Breaker 24 VDC external power supply

Note: Connect the power supply to the power supply input terminals with 24 VDC output, which offers a sufficient margin of power capacity. Usually, the sum of the current consumption of all connected units multiplied by 1.5 or more is required for the power capacity.

Cautions on wiring for I/O units

2

When performing wiring for an I/O unit, pay strict attention to the following contents. • • • • •

Separate input lines from output lines in wiring. If the wiring for power is located near I/O signal lines, a malfunction may occur caused by the effects of a high voltage and large current. Keep I/O signal lines away from the power wiring by at least 100 mm. Separate 24 VDC I/O lines from 100 VAC and 200 VAC lines. When using pipes for wiring, make sure that the pipes are securely grounded.

■ When I/O signal lines cannot be separated from the wiring for power In such a case, perform grounding on the KV side using batch-shielded cables. (In some environments, grounding should be performed on the reverse side of the KV.) Shielded cable

KV

Sensor

Input

RL

Output

24 VDC

Ground

Terminal The terminal screws used are M3. When performing wiring with crimp-style terminals, use the following ones. Unit: mm 6.0 maximum

6.0 maximum M3

1-68

Chapter 2 System Installation

Page 93

2.1 Installation Environment

Because the Visual KV Series is constructed to be sufficiently resistant to noise, it can usually be used without being grounded. However, when the Visual KV Series is used in an environment with a lot of noise, grounding is required. In such a case, pay strict attention to the following contents. • •

Perform complete grounding for each individual unit. In this case, the ground resistance should be 100 Ω or less. If individual grounding is not possible, perform common grounding. In this case, the length of each grounding cable should be equal. Acceptable

Recommended

KV

Other device

Unacceptable

KV

Other device

A

B

Other device

KV

B A

A=B

Complete grounding

Visual KV Series

Cautions on grounding

A>B A<B

2.1.5 Contact Protection If inductive loads such as clutches, motors, and solenoids are used, a rush current may flow when the load power supply is turned on, or a counter electromotive voltage may be generated when the load power supply is shut down. The rush current and the counter electromotive voltage can contribute considerably to shortening the service life of the contacts. To prevent this from happening, provide a contact protection circuit. ■ Contact protection circuit examples For DC load 1

For AC load 1

Contact

Contact

Load

Load

CR circuit

For DC load 2

For AC load 2 a

Contact

Diode b

Contact

Zener diode Varistor

When the supply voltage is 24 to 48 V, provide a protection circuit in position "b". When the supply voltage is 100 to 200 V, provide a protection circuit in position "a". Note 1: Use a load coil whose rating is less than the contact capacity. Note 2: Use a diode whose peak inverse voltage is 10 times or more the circuit voltage and whose forward current is not less than the load current. Note 3: Individually attach diodes, varistors, and CR circuits directly to the relay coil terminal.

Chapter 2 System Installation

1-69

12

Page 94

2.2 Connecting Visual KV Series Expansion Units

Visual KV Series

2.2 Connecting Visual KV Series Expansion Units This section describes the method to connect Visual KV Series expansion units to a Visual KV Series basic unit and the various functions of expansion units.

2.2.1 Visual KV Series Expansion Units Visual KV Series expansion input units

KV-E4X

KV-E8X

KV-E16X

Visual KV Series expansion output units

2 KV-E4R

KV-E4T

KV-E8R

KV-E8T(P)

Visual KV Series expansion I/O units

KV-E4XR

1-70

KV-E4XT(P)

Chapter 2 System Installation

KV-E16R

KV-E16T(P)

Page 95

2.2 Connecting Visual KV Series Expansion Units

•

Connect a basic unit and an expansion unit with an expansion cable.

•

An expansion cable approximately 60 mm long is provided as standard.

•

When extending the expansion cable, use long expansion cables (300 mm) (OP-35361).

•

Up to two expansion cables (300 mm) can be connected to one basic unit.

•

The READY/ERROR LED is lit during normal communication, flashes when an abnormality occurs, and is not lit when the power is not supplied correctly. If this LED is not lit, check whether the expansion cables are correctly connected.

Visual KV Series

2.2.2 Connecting Visual KV Series Expansion Units

Standard cable (approx. 60 mm) Basic unit

Expansion unit

Expansion cable (60 mm)

Long cable (approx. 300 mm) Basic unit

Expansion unit

Expansion cable (300 mm)

12

Expansion unit

Expansion cable (300 mm)

Standard cable (approx. 60) + Long cable (approx. 300 mm) Basic unit

Expansion unit

Expansion cable (60 mm)

CAUTION

Expansion unit

Expansion cable (300 mm)

Be sure to turn off the power before connecting or disconnecting expansion cables. If they are connected or disconnected while the power is on, the units may be damaged or fail. Note: Keep noise sources such as power cables and electromagnetic switches away from expansion cables (300 mm) as much as possible.

Chapter 2 System Installation

1-71

Page 96

2.2 Connecting Visual KV Series Expansion Units

Connection methods

Visual KV Series

1. Peel off the tape stuck to the right side of the basic unit.

2. Connect an expansion cable to the connector.

■ When extending a cable Replace a standard expansion cable (60 mm) with an optional expansion cable (300 mm) (OP-35361).

2

1. Disconnect the standard expansion cable from the expansion unit connector.

2. Connect an optional expansion cable (300 mm) to the expansion unit connector. 3. Connect the optional expansion cable (300 mm) to the basic unit connector.

1-72

Chapter 2 System Installation

Page 97

2.2 Connecting Visual KV Series Expansion Units

Number of connectable units

Basic unit

Input

Output

Input

Expansion units Input Output

Output Output

Visual KV Series

● When the basic unit is a KV-10xx/16xx/24 xx Up to four input units and four output units (that is, up to 8 total expansion units) can be connected to one basic unit. Input

Up to 8 units

● When the basic unit is a KV-40 xx Up to three input units and four output units (that is, up to 7 total expansion units) can be connected to one basic unit. Basic unit

Output

Output

Expansion units Input Output Input

Output

Input

12 Up to 7 units

● When KV-E4XT/KV-E4XR expansion I/O units are connected One I/O unit is regarded as two units (that is, one input and one output unit). For example, when only expansion I/O units are connected to one basic unit, up to four expansion I/O units can be connected. Up to three expansion I/O units can be connected to a KV-40 xx basic unit. When two expansion I/O units are connected

Basic unit

Input Output

Input

I/O

1 0

1 1

Expansion units I/O Output

6 units 1 1

0 1

Output

Input

0 1

1 0

=4 =4

Note 1: There are no restrictions about the order of connected expansion units. Note 2: When connecting expansion units to an AC power type basic unit, be sure that the total current consumption of all connected units does not exceed the output capacity of the Visual KV Series basic unit. Otherwise, consider to use a DC power type basic unit in conbination with an external DC power supply having enough capacity.

Chapter 2 System Installation

1-73

Page 98

2.2 Connecting Visual KV Series Expansion Units

2.2.3 Confirming the Connection Settings of Expansion Units

Visual KV Series

Relay No. (unit No., address No., contact No.) The relay No. of each expansion unit is automatically assigned in the order of connection.

Expansion unit relay list ■ Input units Connection order 1st input unit 2nd input unit 3rd input unit 4th input unit

KV-E4X KV-10/ KV-40 16/24

KV-E8X KV-10/ KV-40 16/24

KV-E16X KV-10/ KV-40 16/24

100 to 103

200 to 203

100 to 107

200 to 207

100 to 115

200 to 115

200 to 203

300 to 303

200 to 207

300 to 307

200 to 215

300 to 315

300 to 303

400 to 403

300 to 307

400 to 407

300 to 315

400 to 415

400 to 403

–

400 to 407

–

400 to 415

–

■ Output units Connection order 1st output unit 2nd output unit 3rd output unit 4th output unit

2

KV-E4T/R

KV-E8T(P)/R

KV-E16T(P)/R

600 to 603

600 to 607

600 to 615

700 to 703

700 to 707

700 to 715

800 to 803

800 to 807

800 to 815

900 to 903

900 to 907

900 to 915

■ I/O units KV -E4X R/ T(P ) Connect ion order 1st input unit 2nd input unit 3rd input unit 4t h input unit 1st out put unit 2nd out put unit 3rd out put unit 4t h out put unit

1-74

Input r e la y

Out put r e la y

KV -10/ 16/ 24

KV -40

KV -10/ 16/ 24

KV -40

100 to 103

200 to 203, - 200 to 203

300 to 303, - 300 to 303

400 to 403, - 400 to 403, - - - - 600 to 603

600 to 603, - 700 to 703

700 to 703, - 800 to 803

800 to 803, - 900 to 903

900 to 903

Chapter 2 System Installation

Page 99

2.2 Connecting Visual KV Series Expansion Units

The connection status (connected or unconnected) of a connected expansion unit can be confirmed using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer. ➮

Refer to "Chapter 3. Access Window" (p.1-79), "Chapter 6. Handheld Programmer" (p.1-195), and the "6.2.9. Displaying the Use Status" (p. 2-70).

Visual KV Series

Connection information for expansion units

The connection information is written to data memory DM1937 as shown in the table below. Bit 15

Bit 7 6 5 4 3 2 1 0

Unused ("0" is always written.)

DM1937 display digit Bit 0* Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 *

"0" or "1" is written.

Indication contents Connection of expansion input unit with relay Nos. 0100 to 0115 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0200 to 0215 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0300 to 0315 0: Unconnected or disconnected 1: Connected Connection of expansion input unit with relay Nos. 0400 to 0415 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0600 to 0615 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0700 to 0715 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0800 to 0815 0: Unconnected or disconnected 1: Connected Connection of expansion output unit with relay Nos. 0900 to 0915 0: Unconnected or disconnected 1: Connected

Always set to "0" when the KV-40xx is used. KV-40

KV-E8X KV-E4XT(P)

KV-E8R

KV-E16T(P)

In the case of connection above, DM1937 is set as follows. DM1937 (binary) 900 800 700 600 400 300 200 100

Decimal (Hexadecimal) Normal status: 0 1 1 1 0 1 1 0 = #118($0076) * Always set to "0" when the KV-40xx is used.

KV-E16T KV-E8R

KV-E4XT KV-E8X

DM1937 (binary) Decimal (Hexadecimal) When KV-E8X has failed: 0 1 1 1 0 1 0 0 = #116($0074) DM1937 (binary) Decimal (Hexadecimal) When KV-E4XT has failed: 0 1 1 0 0 0 1 0 = #98($0062)

Chapter 2 System Installation

1-75

12

Page 100

2.2 Connecting Visual KV Series Expansion Units

Input time constant for expansion units

Visual KV Series

The initial setting of the time constant is "10 ms" for each expansion unit. The input time constant can be set to "10 µs" using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer. Change the value of special utility relays 2609 to 2612. Special utility relay No. 2609* 2610 2611 2612 *

Function Input time constant of expansion input unit with relay Nos. 0100 to 0115 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0200 to 0215 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0300 to 0315 OFF: 10 ms ON: 10 µs Input time constant of expansion input unit with relay Nos. 0400 to 0415 OFF: 10 ms ON: 10 µs

Not used for the KV-40xx.

Clearing the input value when disconnecting The system can be set so that the input value is cleared when disconnection has occurred for some reason. This setting can be performed using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld programmer.

2

Change the value of special utility relay 2613. Enter "0" or "1". Special utility relay No. 2613

1-76

Chapter 2 System Installation

Function Clears input when expansion is disconnected. OFF: Holds previous value. ON: Clears input.