2.2 Connecting Visual KV Series Expansion Units
An expansion unit operates at a cycle of 800 µs without depending on the scan time. When performing input while setting the input time constant of an expansion unit to 10 µs, or when synchronizing the output of a basic unit with the output of an expansion unit, pay strict attention to the following contents.
When inputting
Visual KV Series
2.2.4 Transferring I/O Information between Expansion Units and the Basic Unit
■ When the scan time is longer than 800 µs (communication cycle) plus 10 µs (input time constant) Set the input signal ON time equal to or longer than the scan time. Scan time Receive
Communication cycle in expansion unit Input signal
Receive
Receive
ON OFF
Incomplete receive
OK
■ When the scan time is equal to or shorter than 800 µs (communication cycle) plus 10 µs (input time constant) Set the input signal ON time to 810 µs or longer. Scan time Receive
Communication cycle in expansion unit
Receive
ON
Input signal OFF
Incomplete receive
OK
In the case of output The output of an expansion unit is delayed by a maximum of 800 µs from the output of a basic unit. When synchronizing the output of an expansion unit with the output of a basic unit, pay strict attention to the communication cycle. ON
Output of basic unit Output of expansion unit
OFF ON
800µs
800µs
OFF
Note: When the output ON time is 800 µs or shorter, the output may be aborted.
Chapter 2 System Installation
1-77
12
Page 102
2.3 Inspection and Maintenance
2.3 Inspection and Maintenance Visual KV Series
This section describes the inspection and maintenance procedures for units.
2.3.1 Inspection While basic units and other units have been used for a long period of time, the connector connection area may become loose, the battery may wear out, or another nonconformity may occur in operation. To avoid any nonconformities, inspect the basic units, other units, and the wiring periodically. The major inspection items are as follows. •
Check to ensure that the connector connection area is not disconnected or loose.
•
Check to ensure that terminals on terminal blocks are not loose.
•
Check to ensure that the wiring cables among units and each equipment are not damaged.
2.3.2 Maintenance While basic units and other units have been used for a long period of time, dirt will adhered. Wipe off any collected dirt with a clean, dry cloth. Wipe off any dust and dirt that has collected on small and narrow portions with cotton swabs.
2 CAUTION
1-78
Be sure to turn off the power before starting any inspection or maintenance of the units.
Chapter 2 System Installation