Page 31

1.2 Specifications

■ Electrical double-layer capacitor built into the basic unit Contents of data memories, current values of counters, and the contents of internal utility relays in a Visual KV Series basic unit are saved in RAM backed up with an electrical double-layer capacitor built into the Visual KV Series basic unit by the Data backup function against instantaneous power interruption. The backup time varies depending on the ambient temperature.

Visual KV Series

Data backup function against instantaneous power interruption

If power to the Visual KV Series basic unit remains OFF for more than the holding time by the RAM, the data may be cleared or become corrupted. To avoid the data being cleared, save the data in the EEPROM using the backup function to the EEPROM. ➮

For writing to and reading from the EEPROM, refer to "LOAD mode and SAVE mode" (p.1-96).

When a user program is written, it is saved in RAM. The next time the power is turned on, the user program is automatically transferred from RAM to the EEPROM and is also saved in the EEPROM. If power to the Visual KV Series basic unit will remain OFF for more than the backup time by the RAM, turn the power off immediately after writing a user program, and then turn the power on again so that the user program is transferred to the EEPROM. •

Data backup function by electrical double-layer capacitor built into the basic unit Visual KV Series: 2 months or more at 25°C (77°F) (20 days or more at 25°C (77°F) in KV-10xx)

■ EEPROM The Visual KV Series basic unit is equipped with a backup function to save programs, contents of data memories, current values of counters, etc. in the EEPROM. Even if the power is interrupted or power to the Visual KV Series basic unit remains OFF, the data is still saved. When the power turns ON again, the contents of the EEPROM is automatically read. (The contents of data memories and current values of counters should be read by manipulating the Access Window.) When data is changed and the power is turned off without saving the changed data, the changes are saved only in the built-in electrical double-layer capacitor and are not saved in the EEPROM. If the Visual KV Series basic unit remains OFF for 2 months or more at 25°C (77°F) (20 days or more at 25°C (77°F) in KV-10xx) while the data is backed up only with the built-in electrical double-layer capacitor, the saved contents may be cleared or become corrupted. If the Visual KV Series basic unit will remain OFF for a long period of time, save the data in the EEPROM. ➮

Refer to "LOAD mode and SAVE mode" (p.1-96).

•

Data backup function with the EEPROM Visual KV Series: 10 years or more at 25°C (77°F) (available number of overwrites: 100,000 times or more)

Chapter 1 Configuration and Specifications

1-7

11

Page 32

1.3 Common I/O Specifications of Basic Units

Visual KV Series

1.3 Common I/O Specifications of Basic Units This section describes the common I/O specifications of Visual KV Series basic units. There are two types of basic units, AC power type and DC power type. Two types of output types are offered: relay output and transistor output.

1.3.1 Model of a Basic Unit ■ Basic unit model designation The model of a Visual KV Series basic unit is indicated as follows:

KV-10AR Output type: R = relay output, T = transistor output Power supply type: A = AC power type, D = DC power type Number of I/O points: 10 = 10 points, 16 = 16 points, 24 = 24 points, 40 = 40 points

■ Unit type The following four types of Visual KV Series basic units are offered:

1

AC power/relay output type: KV-10AR/16AR/24AR/40AR AC power/transistor output type: KV-10AT(P)/16AT(P)/24AT(P)/40AT(P) DC power/relay output type: KV-10DR/16DR/24DR/40DR DC power/transistor output type: KV-10DT(P)/16DT(P)/24DT(P)/40DT(P)

1.3.2 Common I/O Specifications ■ Input specifications Item

24 V mode

Maximum input rating Input voltage

24 VDC, 5.3 mA

5 VDC, 1.0 mA

19V

4.5V

2mA

2.5V

Minimum ON voltage Minimum OFF current (voltage) Common method

COM is shared inside. 10 ms typical 10 µs when HSP instruction is used Variable in 7 steps from 10 µs to 10 ms while special utility relay 2813 is ON (Set by DM1940) 10 µs (representative)

Input time constant

Interrupt input response High-speed counter input response *

5 V mode (Inputs 000 to 007 can be changed to 5 V input.) 26.4 VDC

30 kHz (24V± 10%) (duty: 50%)

For 5V±10%, refer to the 5 V mode response frequency characteristic chart (representative example). 5 V mode response frequency characteristic chart (representative example)

Response frequency (kHz)

40 35 30 25 20 15 10 5 0

4.6 4.7 4.8 4.9

5

5.1 5.2 5.3 5.4

5.5

Input voltage (V)

1-8

Chapter 1 Configuration and Specifications

Page 33

1.3 Common I/O Specifications of Basic Units ■ Output specifications (relay output): KV-10AR/DR, KV-16AR/DR, KV-24AR/DR, and KV-40AR/DR

Rated load Peak load current Rising operating time (OFF ➞ ON) Falling operating time (ON ➞ OFF) Common method Relay service life Relay replacement

Specifications 250 VAC/30 VDC 2 A (inductive load) 4 A (resistive load) 5A

Visual KV Series

Item

10 ms or less 10 ms or less Each common terminal is independent. Electrical service life: 100,000 times or more (20 times/min) Mechanical service life: 20,000,000 times or more Not allowed

■ Output specifications (transistor output): KV-10AT(P)/DT(P), KV-16AT(P)/DT(P), KV-24AT(P)/DT(P), and KV-40AT(P)/DT(P) Item Rated load Peak load current Maximum voltage at OFF Leak current in OFF status Residual voltage in ON status Rising operation time (OFF ➞ ON) Falling operation time (ON ➞ OFF) Common method Output frequency Built-in serial resistance

Specifications 30 VDC 0.1 A (500 to 502) 0.3 A (others) 0.2 A (500 to 502) 1 A (others) 30 VDC

11

100 µA or less 0.8 V or less 10 µs or less (500 to 502) (at 5 to 100 mA) 20 µs or less (others) (at 10 to 300 mA) 10 µs or less (500 to 502) (at 5 to 100 mA) 100 µs or less (others) (at 10 to 300 mA) 1 common 50 kHz (500 to 502) 1.6 KΩ 1/2W (R500 to R502)

Chapter 1 Configuration and Specifications

1-9

Page 34

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

1.4

KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

Visual KV Series

This section describes the name and function of each part, the I/O specifications, the terminal layout, circuit diagrams, and dimensions of the KV-10xx.

1.4.1 Part Names and Functions 1. Input terminal block 9. Input voltage selector switch Provided on side INPUT

24V 001

000 C1

002

003

004

005

C2

IN

5V

VOLT

4. Input indicator lamps

0ch 0

1

2

3

4

5

5. Output indicator lamps 6. Connector (provided on side) 7. Access Window 10. Communication port A

8. Setting keys KV-10AR

0

1

2

3

5ch 501

3. Power input terminal

1

24V-OUT-OV

500

C3

502 C4

503

OUT

(Power input terminals for AC power types are provided on the lower side.) L

~ N

2. Output terminal block AC100V-240V 0.4A 50/60Hz

No. 1

2

3

4 5 6

Output terminal block Power input terminal (KV-10DR/DT(P)) Power output terminal (KV-10AR/AT(P)) Input indicator lamps Output indicator lamps Connector (provided on side)

7

Access Window

8

Setting keys

9 10 ➮

Name Input terminal block

Input voltage selector switch Communication port A

Function 24 VDC input terminal block (000 to 005 can be changed to 5 V input). Output terminal block. Pulse output function is built in 500 to 502 (in transistor output type only). A 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver). Supplies 24 VDC. Supplies 100 to 240 VAC to the power input terminals on the lower side of the unit, and allows the service power supply to be taken from the 24 VDC terminal. Indicate input status. Each lamp lights up at ON. Indicate output status. Each lamp lights up at ON. Used to connect an expansion unit Used to refer to and change the current and set values of timers and counters as well as the contents of data memories. The backlight color indicates the operation status. Lit in green: RUN mode Lit in red: PROGRAM mode Flashing red: Error status Used to refer to and change current values, etc. while referring to the Access Window. Changes the input voltage of the basic unit. : 24 V input : 5 V input RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel.

For more about the Access Window, refer to "Chapter 3. Access Window" (p.1-79).

1-10 Chapter 1 Configuration and Specifications

Page 35

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

1.4.2 Terminal Layout Drawings and I/O Circuit Diagrams KV-10AR/DR (Relay output type)

Visual KV Series

■ Terminal layout drawing

000 001 002 003 004 005 C1 C2

501 502 24V 0V 500 C3 C4 503

11

Internal circuit

Photocoupler insulation

4.3KΩ 000 to 005

24V/5V selector circuit C1 C2

000

Three-wire type

Blue

Brown

Brown Black

Blue

Brown Black

Blue

Brown Black

Blue

Three-wire type

Three-wire type

Black Three-wire type

001

002

Brown Black

Blue

Brown Black

Blue

003

Three-wire type

004

005

C1

Three-wire type

C2

Internal circuit

■ Input circuit diagram

Sensor

Chapter 1 Configuration and Specifications

1-11

Page 36

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit) ■ Output circuit diagram

Visual KV Series

Internal circuit

Internal circuit

501

500 501 to 503

C3 C4

502

• C3 and C4 are each independent. 24V

0V

500

C3

C4

1

1-12 Chapter 1 Configuration and Specifications

503

Page 37

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

KV-10AT(P)/DT(P) (Transistor output type) ■ Terminal layout drawing

Visual KV Series

000 001 002 003 004 005 C1 C2

501 502 24V 0V 500 C3 C4 503

11 Internal circuit

Photocoupler insulation

4.3KΩ 000 to 005

24V/5V selector circuit C1 C2

000

Three-wire type

Blue

Brown

Brown Black

Blue

Brown Black

Blue

Brown Black

Blue

Three-wire type

Three-wire type

Black Three-wire type

001

002

Brown Black

Blue

Brown Black

Blue

003

Three-wire type

004

005

C1

Three-wire type

C2

Internal circuit

■ Input circuit diagram

Sensor

Chapter 1 Configuration and Specifications

1-13

Page 38

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit) ■ Output circuit diagram

Visual KV Series

Internal circuit

501

24V

0V

500

C3

502

R502

503

*

* For KV-10ATP/DTP

NPN 1.6kΩ 1 2 W

Insulating power supply

C3 R502 500 to 503

Internal circuit

Internal circuit

1

PNP

500 to 503 C3

• 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver).

Insultating power supply

~ N

L

N

AC100V-240V 0.4A 50/60Hz

FG

1-14 Chapter 1 Configuration and Specifications

1.6 kΩ 1 2 W

• 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver).

1.4.3 AC Power Input (KV-10AR/AT(P)) L

R502

Page 39

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged. The graphs below show the relationship between the ambient temperature and the continuous simultaneous ON ratio. Load current L: (Service power (AC power output (Expansion (Individual current consumption = + – output current) capacity at 400 mA) unit current when KV-D20 is connected) consumption)

110 100 90 80 70 60 50 40 30 20 10 0

Derating when KV-10AR is mounted in front

39 41 42 (102.2) (105.8) (107.6) 44 (111.2) 46 (114.8)

L=0 L=1/2Max. L=Max.

63% L=0 L=1/2Max. 38%

L=Max.

25%

Individual unit With expansion unit

Continuous simultaneous ON ratio (%)

Continuous simultaneous ON ratio (%)

Derating when KV-10AR is mounted upward

49

30 (86)

35 (95)

40 (104)

110 100 90 80 70 60 50 40 30 20 10 0

45 (120.2)50 (113) (122)

47 48 (116.0)(118.4) L=Max. L=0,1/2Max.

45 (113) 86% 79%

L=Max.

64%

Individual unit With expansion unit

30 (86)

35 (95)

40 (104)

45 (113)

50 (122)

Ambient temperature [°C] [°F] for figure in ( ).

Derating when KV-10AT(P) is mounted upward

Derating when KV-10AT(P) is mounted in front

110 100 90 80 70 60 50 40 30 20 10 0

41 43 46 47 (105.8)(109.4)(114.8)(116.6) L=0 L=1/2Max. L=Max.

86% 68% 60%

L=0

30%

Individual unit With expansion unit 30 (86)

35 (95)

40 (104)

45 (113)

Continuous simultaneous ON ratio (%)

Continuous simultaneous ON ratio (%)

Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0

Individual unit With expansion unit 40 (104)

45 (113)

Continuous simultaneous ON ratio (%)

Continuous simultaneous ON ratio (%)

58%

35 (95)

50 (122)

110 100 90 80 70 60 50 40 30 20 10 0

Derating when KV-10DT(P) is mounted upward

Individual unit With expansion unit 40 (104)

45 (113)

Ambient temperature [°C] [°F] for figure in ( ).

50 (122)

Continuous simultaneous ON ratio (%)

88%

35 (95)

50 (122)

48 (118.4)

80%

Individual unit With expansion unit

30 (86)

35 (95)

40 (104)

45 (113)

50 (122)

Derating when KV-10DT(P) is mounted in front

49 (120.2)

30 (86)

45 (113)

Ambient temperature [°C] [°F] for figure in ( ).

Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0

40 (104)

Derating when KV-10DR is mounted in front

45 (113)

30 (86)

35 (95)

Ambient temperature [°C] [°F] for figure in ( ).

Derating when KV-10DR is mounted upward 110 100 90 80 70 60 50 40 30 20 10 0

Individual unit With expansion unit 30 (86)

50 (122)

Ambient temperature [°C] [°F] for figure in ( ).

Continuous simultaneous ON ratio (%)

CAUTION

Visual KV Series

1.4.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature

110 100 90 80 70 60 50 40 30 20 10 0

Individual unit With expansion unit 30 (86)

35 (95)

40 (104)

45 (113)

50 (122)

Ambient temperature [°C] [°F] for figure in ( ).

Chapter 1 Configuration and Specifications

1-15

11

Page 40

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

1.4.5 Dimensions ■ Main unit Front view

Side view (KV-10AR/AT(P))

Side view (KV-10DR/DT(P))

Visual KV Series

24.5 9.9

35.4

90

35.4

90

3.8

4

3.8

4

17 4.1

22

55

70

22

Bottom view (KV-10AR/AT(P))

17.5

1 20.5

■ Metal fixture for screw tightening 4-ø5.0 (Mounting hole) Main unit mounting hole*

99 111

(2 positions)

40 54 t=2

* Two M3.5 countersunk-head screws are included for mounting the main unit.

1-16 Chapter 1 Configuration and Specifications