The text of a manual · part 5 of 12
Visual KV Series User's Manual 1: Installation, pages 31 to 40
Pages 31 to 40 of 102
The original document is the PDF (964 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Keyence KV-E4X
Page 31
1.2 Specifications
■ Electrical double-layer capacitor built into the basic unit Contents of data memories, current values of counters, and the contents of internal utility relays in a Visual KV Series basic unit are saved in RAM backed up with an electrical double-layer capacitor built into the Visual KV Series basic unit by the Data backup function against instantaneous power interruption. The backup time varies depending on the ambient temperature.
Visual KV Series
Data backup function against instantaneous power interruption
If power to the Visual KV Series basic unit remains OFF for more than the holding time by the RAM, the data may be cleared or become corrupted. To avoid the data being cleared, save the data in the EEPROM using the backup function to the EEPROM. ➮
For writing to and reading from the EEPROM, refer to "LOAD mode and SAVE mode" (p.1-96).
When a user program is written, it is saved in RAM. The next time the power is turned on, the user program is automatically transferred from RAM to the EEPROM and is also saved in the EEPROM. If power to the Visual KV Series basic unit will remain OFF for more than the backup time by the RAM, turn the power off immediately after writing a user program, and then turn the power on again so that the user program is transferred to the EEPROM. •
Data backup function by electrical double-layer capacitor built into the basic unit Visual KV Series: 2 months or more at 25°C (77°F) (20 days or more at 25°C (77°F) in KV-10xx)
■ EEPROM The Visual KV Series basic unit is equipped with a backup function to save programs, contents of data memories, current values of counters, etc. in the EEPROM. Even if the power is interrupted or power to the Visual KV Series basic unit remains OFF, the data is still saved. When the power turns ON again, the contents of the EEPROM is automatically read. (The contents of data memories and current values of counters should be read by manipulating the Access Window.) When data is changed and the power is turned off without saving the changed data, the changes are saved only in the built-in electrical double-layer capacitor and are not saved in the EEPROM. If the Visual KV Series basic unit remains OFF for 2 months or more at 25°C (77°F) (20 days or more at 25°C (77°F) in KV-10xx) while the data is backed up only with the built-in electrical double-layer capacitor, the saved contents may be cleared or become corrupted. If the Visual KV Series basic unit will remain OFF for a long period of time, save the data in the EEPROM. ➮
Refer to "LOAD mode and SAVE mode" (p.1-96).
•
Data backup function with the EEPROM Visual KV Series: 10 years or more at 25°C (77°F) (available number of overwrites: 100,000 times or more)
Chapter 1 Configuration and Specifications
1-7
11
Page 32
1.3 Common I/O Specifications of Basic Units
Visual KV Series
1.3 Common I/O Specifications of Basic Units This section describes the common I/O specifications of Visual KV Series basic units. There are two types of basic units, AC power type and DC power type. Two types of output types are offered: relay output and transistor output.
1.3.1 Model of a Basic Unit ■ Basic unit model designation The model of a Visual KV Series basic unit is indicated as follows:
KV-10AR Output type: R = relay output, T = transistor output Power supply type: A = AC power type, D = DC power type Number of I/O points: 10 = 10 points, 16 = 16 points, 24 = 24 points, 40 = 40 points
■ Unit type The following four types of Visual KV Series basic units are offered:
1
AC power/relay output type: KV-10AR/16AR/24AR/40AR AC power/transistor output type: KV-10AT(P)/16AT(P)/24AT(P)/40AT(P) DC power/relay output type: KV-10DR/16DR/24DR/40DR DC power/transistor output type: KV-10DT(P)/16DT(P)/24DT(P)/40DT(P)
1.3.2 Common I/O Specifications ■ Input specifications Item
24 V mode
Maximum input rating Input voltage
24 VDC, 5.3 mA
5 VDC, 1.0 mA
19V
4.5V
2mA
2.5V
Minimum ON voltage Minimum OFF current (voltage) Common method
COM is shared inside. 10 ms typical 10 µs when HSP instruction is used Variable in 7 steps from 10 µs to 10 ms while special utility relay 2813 is ON (Set by DM1940) 10 µs (representative)
Input time constant
Interrupt input response High-speed counter input response *
5 V mode (Inputs 000 to 007 can be changed to 5 V input.) 26.4 VDC
30 kHz (24V± 10%) (duty: 50%)
For 5V±10%, refer to the 5 V mode response frequency characteristic chart (representative example). 5 V mode response frequency characteristic chart (representative example)
Response frequency (kHz)
40 35 30 25 20 15 10 5 0
4.6 4.7 4.8 4.9
5
5.1 5.2 5.3 5.4
5.5
Input voltage (V)
1-8
Chapter 1 Configuration and Specifications
Page 33
1.3 Common I/O Specifications of Basic Units ■ Output specifications (relay output): KV-10AR/DR, KV-16AR/DR, KV-24AR/DR, and KV-40AR/DR
Rated load Peak load current Rising operating time (OFF ➞ ON) Falling operating time (ON ➞ OFF) Common method Relay service life Relay replacement
Specifications 250 VAC/30 VDC 2 A (inductive load) 4 A (resistive load) 5A
Visual KV Series
Item
10 ms or less 10 ms or less Each common terminal is independent. Electrical service life: 100,000 times or more (20 times/min) Mechanical service life: 20,000,000 times or more Not allowed
■ Output specifications (transistor output): KV-10AT(P)/DT(P), KV-16AT(P)/DT(P), KV-24AT(P)/DT(P), and KV-40AT(P)/DT(P) Item Rated load Peak load current Maximum voltage at OFF Leak current in OFF status Residual voltage in ON status Rising operation time (OFF ➞ ON) Falling operation time (ON ➞ OFF) Common method Output frequency Built-in serial resistance
Specifications 30 VDC 0.1 A (500 to 502) 0.3 A (others) 0.2 A (500 to 502) 1 A (others) 30 VDC
11
100 µA or less 0.8 V or less 10 µs or less (500 to 502) (at 5 to 100 mA) 20 µs or less (others) (at 10 to 300 mA) 10 µs or less (500 to 502) (at 5 to 100 mA) 100 µs or less (others) (at 10 to 300 mA) 1 common 50 kHz (500 to 502) 1.6 KΩ 1/2W (R500 to R502)
Chapter 1 Configuration and Specifications
1-9
Page 34
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4
KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
Visual KV Series
This section describes the name and function of each part, the I/O specifications, the terminal layout, circuit diagrams, and dimensions of the KV-10xx.
1.4.1 Part Names and Functions 1. Input terminal block 9. Input voltage selector switch Provided on side INPUT
24V 001
000 C1
002
003
004
005
C2
IN
5V
VOLT
4. Input indicator lamps
0ch 0
1
2
3
4
5
5. Output indicator lamps 6. Connector (provided on side) 7. Access Window 10. Communication port A
8. Setting keys KV-10AR
0
1
2
3
5ch 501
3. Power input terminal
1
24V-OUT-OV
500
C3
502 C4
503
OUT
(Power input terminals for AC power types are provided on the lower side.) L
~ N
2. Output terminal block AC100V-240V 0.4A 50/60Hz
No. 1
2
3
4 5 6
Output terminal block Power input terminal (KV-10DR/DT(P)) Power output terminal (KV-10AR/AT(P)) Input indicator lamps Output indicator lamps Connector (provided on side)
7
Access Window
8
Setting keys
9 10 ➮
Name Input terminal block
Input voltage selector switch Communication port A
Function 24 VDC input terminal block (000 to 005 can be changed to 5 V input). Output terminal block. Pulse output function is built in 500 to 502 (in transistor output type only). A 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver). Supplies 24 VDC. Supplies 100 to 240 VAC to the power input terminals on the lower side of the unit, and allows the service power supply to be taken from the 24 VDC terminal. Indicate input status. Each lamp lights up at ON. Indicate output status. Each lamp lights up at ON. Used to connect an expansion unit Used to refer to and change the current and set values of timers and counters as well as the contents of data memories. The backlight color indicates the operation status. Lit in green: RUN mode Lit in red: PROGRAM mode Flashing red: Error status Used to refer to and change current values, etc. while referring to the Access Window. Changes the input voltage of the basic unit. : 24 V input : 5 V input RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel.
For more about the Access Window, refer to "Chapter 3. Access Window" (p.1-79).
1-10 Chapter 1 Configuration and Specifications
Page 35
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4.2 Terminal Layout Drawings and I/O Circuit Diagrams KV-10AR/DR (Relay output type)
Visual KV Series
■ Terminal layout drawing
000 001 002 003 004 005 C1 C2
501 502 24V 0V 500 C3 C4 503
11
Internal circuit
Photocoupler insulation
4.3KΩ 000 to 005
24V/5V selector circuit C1 C2
000
Three-wire type
Blue
Brown
Brown Black
Blue
Brown Black
Blue
Brown Black
Blue
Three-wire type
Three-wire type
Black Three-wire type
001
002
Brown Black
Blue
Brown Black
Blue
003
Three-wire type
004
005
C1
Three-wire type
C2
Internal circuit
■ Input circuit diagram
Sensor
Chapter 1 Configuration and Specifications
1-11
Page 36
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit) ■ Output circuit diagram
Visual KV Series
Internal circuit
Internal circuit
501
500 501 to 503
C3 C4
502
• C3 and C4 are each independent. 24V
0V
500
C3
C4
1
1-12 Chapter 1 Configuration and Specifications
503
Page 37
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
KV-10AT(P)/DT(P) (Transistor output type) ■ Terminal layout drawing
Visual KV Series
000 001 002 003 004 005 C1 C2
501 502 24V 0V 500 C3 C4 503
11 Internal circuit
Photocoupler insulation
4.3KΩ 000 to 005
24V/5V selector circuit C1 C2
000
Three-wire type
Blue
Brown
Brown Black
Blue
Brown Black
Blue
Brown Black
Blue
Three-wire type
Three-wire type
Black Three-wire type
001
002
Brown Black
Blue
Brown Black
Blue
003
Three-wire type
004
005
C1
Three-wire type
C2
Internal circuit
■ Input circuit diagram
Sensor
Chapter 1 Configuration and Specifications
1-13
Page 38
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit) ■ Output circuit diagram
Visual KV Series
Internal circuit
501
24V
0V
500
C3
502
R502
503
*
* For KV-10ATP/DTP
NPN 1.6kΩ 1 2 W
Insulating power supply
C3 R502 500 to 503
Internal circuit
Internal circuit
1
PNP
500 to 503 C3
• 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver).
Insultating power supply
~ N
L
N
AC100V-240V 0.4A 50/60Hz
FG
1-14 Chapter 1 Configuration and Specifications
1.6 kΩ 1 2 W
• 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver).
1.4.3 AC Power Input (KV-10AR/AT(P)) L
R502
Page 39
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged. The graphs below show the relationship between the ambient temperature and the continuous simultaneous ON ratio. Load current L: (Service power (AC power output (Expansion (Individual current consumption = + – output current) capacity at 400 mA) unit current when KV-D20 is connected) consumption)
110 100 90 80 70 60 50 40 30 20 10 0
Derating when KV-10AR is mounted in front
39 41 42 (102.2) (105.8) (107.6) 44 (111.2) 46 (114.8)
L=0 L=1/2Max. L=Max.
63% L=0 L=1/2Max. 38%
L=Max.
25%
Individual unit With expansion unit
Continuous simultaneous ON ratio (%)
Continuous simultaneous ON ratio (%)
Derating when KV-10AR is mounted upward
49
30 (86)
35 (95)
40 (104)
110 100 90 80 70 60 50 40 30 20 10 0
45 (120.2)50 (113) (122)
47 48 (116.0)(118.4) L=Max. L=0,1/2Max.
45 (113) 86% 79%
L=Max.
64%
Individual unit With expansion unit
30 (86)
35 (95)
40 (104)
45 (113)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ).
Derating when KV-10AT(P) is mounted upward
Derating when KV-10AT(P) is mounted in front
110 100 90 80 70 60 50 40 30 20 10 0
41 43 46 47 (105.8)(109.4)(114.8)(116.6) L=0 L=1/2Max. L=Max.
86% 68% 60%
L=0
30%
Individual unit With expansion unit 30 (86)
35 (95)
40 (104)
45 (113)
Continuous simultaneous ON ratio (%)
Continuous simultaneous ON ratio (%)
Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0
Individual unit With expansion unit 40 (104)
45 (113)
Continuous simultaneous ON ratio (%)
Continuous simultaneous ON ratio (%)
58%
35 (95)
50 (122)
110 100 90 80 70 60 50 40 30 20 10 0
Derating when KV-10DT(P) is mounted upward
Individual unit With expansion unit 40 (104)
45 (113)
Ambient temperature [°C] [°F] for figure in ( ).
50 (122)
Continuous simultaneous ON ratio (%)
88%
35 (95)
50 (122)
48 (118.4)
80%
Individual unit With expansion unit
30 (86)
35 (95)
40 (104)
45 (113)
50 (122)
Derating when KV-10DT(P) is mounted in front
49 (120.2)
30 (86)
45 (113)
Ambient temperature [°C] [°F] for figure in ( ).
Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0
40 (104)
Derating when KV-10DR is mounted in front
45 (113)
30 (86)
35 (95)
Ambient temperature [°C] [°F] for figure in ( ).
Derating when KV-10DR is mounted upward 110 100 90 80 70 60 50 40 30 20 10 0
Individual unit With expansion unit 30 (86)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ).
Continuous simultaneous ON ratio (%)
CAUTION
Visual KV Series
1.4.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature
110 100 90 80 70 60 50 40 30 20 10 0
Individual unit With expansion unit 30 (86)
35 (95)
40 (104)
45 (113)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ).
Chapter 1 Configuration and Specifications
1-15
11
Page 40
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4.5 Dimensions ■ Main unit Front view
Side view (KV-10AR/AT(P))
Side view (KV-10DR/DT(P))
Visual KV Series
24.5 9.9
35.4
90
35.4
90
3.8
4
3.8
4
17 4.1
22
55
70
22
Bottom view (KV-10AR/AT(P))
17.5
1 20.5
■ Metal fixture for screw tightening 4-ø5.0 (Mounting hole) Main unit mounting hole*
99 111
(2 positions)
40 54 t=2
* Two M3.5 countersunk-head screws are included for mounting the main unit.
1-16 Chapter 1 Configuration and Specifications
43