Visual KV Series User's Manual 1: Installation, pages 41 to 50
Pages 41 to 50 of 102
The original document is the PDF (964 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Keyence KV-E4X
Page 41
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5
KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit) Visual KV Series
This section describes the name and function of each part, the I/O specifications, the terminal layout, circuit diagrams, and dimensions of the KV-16x x.
1.5.1 Part Names and Functions 1. Input terminal block 9. Input voltage selector switch Provided on side INPUT
24V C1
001
003 002
000
005 004
007 006
009
IN
008
5V
VOLT
4. Input indicator lamps
0ch 0
1
2
3
4
5
6
7
8
9
5. Output indicator lamps 6. Connector (provided on side) 7. Access Window
10. Communication port A 11. Communication port B
KV-16AR
0
1
500
3. Power input terminal
2
3
4
8. Setting keys
5
5ch
24V-OUT-OV
501 C3
502 C4
504 503
505
OUT
(Power input terminals for AC power type are provided on the lower side.) L
AC100V-240V 0.5A 50/60Hz
No. 1
2
3
4 5 6
Output terminal block Power input terminal (KV-24DR/DT(P)) Power output terminal (KV-24AR/AT(P)) Input indicator lamps Output indicator lamps Connector (provided on side)
Access Window
8
Setting keys
10 11 ➮
Name Input terminal block
7
9
11
~ N
Input voltage selector switch Communication port A Communication port B
2. Output terminal block
Function 24 VDC input terminal block (000 to 007 can be changed to 5 V input). Output terminal block. Pulse output function is built in 500 to 502 (in transistor output type only). A 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver). Supplies 24 VDC. Supplies 100 to 240 VAC to the power input terminals on the lower side of the unit, and allows the service power supply to be taken from the 24 VDC terminal. Indicate input status. Each lamp lights up at ON. Indicate output status. Each lamp lights up at ON. Used to connect an expansion unit Used to refer to and change the current and set values of timers and counters as well as the contents of data memories. The backlight color indicates the operation status. Lit in green: RUN mode Lit in red: PROGRAM mode Flashing red: Error status Used to refer to and change current values, etc. while referring to the Access Window. Changes the input voltage of the basic unit. : 24 V input : 5 V input RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel. RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel.
For more about the Access Window, refer to "Chapter 3. Access Window" (p.1-79).
Chapter 1 Configuration and Specifications
1-17
Page 42
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5.2 Terminal Layout Drawings and I/O Circuit Diagrams KV-16AR/DR (Relay output type)
Visual KV Series
■ Terminal layout drawing
C1 001 003 005 007 009 000 002 004 006 008
500 501 502 504 24V 0V C3 C4 503 505
■ Input circuit diagram Internal circuit
001
Brown
Blue
Brown Black
Blue
Three-wire type
Blue
Brown Black
Brown Black Three-wire type
Brown Black
Blue
C1
Brown Black
Blue
Three-wire type
Blue
Brown Black
Blue
000
003
Three-wire type
Brown Black Three-wire type
Three-wire type
Black
Blue
Brown Black
Blue
Brown Black
Blue
002
005
007
Three-wire type
009
004
Three-wire type
006
Three-wire type
008
Three-wire type
Sensor
Photocoupler insulation
4.3KΩ 000 to 007
24V/5V selector circuit C1
Circuit configuration of inputs 008 to 009
4.3KΩ
1-18 Chapter 1 Configuration and Specifications
008 to 009 510Ω C1
Photocoupler insulation
Internal circuit
Circuit configuration of inputs 000 to 007
Internal circuit
1
Page 43
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit) ■ Output circuit diagram
500
501
502
500 to 501 502 to 505
C3 C4
504
Visual KV Series
Internal circuit
Internal circuit
• C3 and C4 are each independent. 24V
0V
C3
C4
503
505
11
Chapter 1 Configuration and Specifications
1-19
Page 44
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
KV-16AT(P)/DT(P) (Transistor output type) ■ Terminal layout drawing
Visual KV Series
C1 001 003 005 007 009 000 002 004 006 008
24V 500 501 502 504 24V 0V C3 R502 503 505
■ Input circuit diagram
Internal circuit
000
001
Brown Black
Blue
Brown
Blue
Brown Black
Blue
Brown Black
Blue
Three-wire type
Brown Black Three-wire type
Three-wire type
Brown Black
Blue
C1
Three-wire type
003
Blue
Brown Black
Blue
Brown Black
Blue
Three-wire type
Brown Black
Brown Black
Blue
Three-wire type
Black
Blue
002
005
007
Three-wire type
009
004
Three-wire type
006
Three-wire type
008
Three-wire type
Sensor
Photocoupler insulation
4.3KΩ 000 to 007 24 V/5 V selector circuit
C1
Circuit configuration of inputs 008 to 009 4.3 kΩ
1-20 Chapter 1 Configuration and Specifications
008 to 009 510 Ω C1
Photocoupler insulation
Internal circuit
Circuit configuration of inputs 000 to 007
Internal circuit
1
Page 45
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit) ■ Output circuit diagram
Visual KV Series
Internal circuit
24V
24V
500
501
0V
C3
502
504
503
R502
505
*
* For KV-16ATP/DTP
PNP
NPN 1.6kΩ 1 2 W
C3 R502 500 to 505
Internal circuit
Internal circuit
Insulating power supply
11 500 to 505
Insultating power supply
C3
R502 1.6 kΩ 1 2 W
• A current limiting resistor 1.6 kΩ is built in R502 (to connect a motor driver).
• A current limiting resistor 1.6 kΩ is built in R502 (to connect a motor driver).
1.5.3 AC Power Input (KV-16AR/AT(P)) L
~ N
L
N
AC100V-240V 0.5A 50/60Hz
FG
Chapter 1 Configuration and Specifications
1-21
Page 46
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature Visual KV Series
CAUTION
If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged. The graphs below show the relationship between the ambient temperature and the continuous simultaneous ON ratio. Load current L: (Service power (AC power output (Expansion (Individual current consumption = + – output current) capacity at 600 mA) unit current when KV-D20 is connected) consumption) Derating when KV-16AR is mounted upward
Derating when KV-16AR is mounted in front
36 37 (96.8)(98.6) 40 (104) 41 (105.8) 35 (95) 39 L=0 (102.2) L=1/2Max. L=Max. L=0
50% 44% 38%
L=1/2Max. L=Max.
18% 13%
Individual unit With expansion unit
Supply voltage: 100 to 240 V
Continuous simultaneous ON ratio (%)
110 100 90 80 70 60 50 40 30 20 10 0
49
30 (86)
35 (95)
110 100 90 80 70 60 50 40 30 20 10 0
44 47 49 (111.2) (116.6) (120.2) L=0, 1/2Max. L=0, 1/2Max.
50%
Individual unit With expansion unit 35 (95)
39 (102.2)
41(105.8)
L=0
L=Max. L=0
50% 44% 38%
L=1/2Max. L=Max.
Individual unit With expansion unit 30 (86)
35 (95)
18% 13%
40 (104)
49
45 (120.2) 50 (113) (122)
50%
Individual unit With expansion unit 45 (113)
Continuous simultaneous ON ratio (%)
Continuous simultaneous ON ratio (%)
75%
40 (104)
110 100 90 80 70 60 50 40 30 20 10 0
75%
50%
Individual unit With expansion unit 40 (104)
91%
L=Max.
75% 66%
L=Max.
50%
Individual unit With expansion unit 30 (86)
35 (95)
40 (104)
45 (113)
50 (122)
44 (111.2) 49 (120.2) 93%
58%
Individual unit With expansion unit 35 (95)
40 (104)
45 (113)
50 (122)
Derating when KV-16DT(P) is mounted in front
47 (116.6)
45 (113)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ).
1-22 Chapter 1 Configuration and Specifications
Continuous simultaneous ON ratio (%)
43 (109.4)
35 (95)
46 (114.8)
Ambient temperature [°C] [°F] for figure in ( ).
Derating when KV-16DT(P) is mounted upward
30 (86)
L=0, 1/2Max. L=0, 1/2Max.
30 (86)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0
47 44 49 (111.2) (116.6)(120.2)
Derating when KV-16DR is mounted in front
43 (109.4) 47 (116.6)
35 (95)
50 (122)
Ambient temperature [°C] [°F] for figure in ( ).
Derating when KV-16DR is mounted upward
30 (86)
45 (113)
Supply voltage: 100 to 240 V 110 100 90 80 70 60 50 40 30 20 10 0
Ambient temperature [°C] [°F] for figure in ( ). 110 100 90 80 70 60 50 40 30 20 10 0
40 (104)
Derating when KV-16AT(P) is mounted in front
Continuous simultaneous ON ratio (%)
Continuous simultaneous ON ratio (%)
36 37 (96.8)(98.6) 40 (104) 35 (95)
75% 66%
L=Max.
Supply voltage: 100 to 240 V
L=1/2Max.
91%
Ambient temperature [°C] [°F] for figure in ( ).
Derating when KV-16AT(P) is mounted upward 110 100 90 80 70 60 50 40 30 20 10 0
46 (114.8)
L=Max.
30 (86)
45 (120.2) 50 (113) (122)
40 (104)
Ambient temperature [°C] [°F] for figure in ( ).
Continuous simultaneous ON ratio (%)
1
Continuous simultaneous ON ratio (%)
Supply voltage: 100 to 240 V
110 100 90 80 70 60 50 40 30 20 10 0
44 (111.2)
49 (120.2) 93%
58%
Individual unit With expansion unit 30 (86)
35 (95)
40 (104)
45 (113)
Ambient temperature [°C] [°F] for figure in ( ).
50 (122)
Page 47
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5.5 Dimensions ■ Main unit Side view (KV-16DR/DT(P))
24.5 13.3
35.4
90
35.4
90
3.8
4
3.8
4
Visual KV Series
Side view (KV-16AR/AT(P))
Front view
17 4.1
22
65
70
22
43
Bottom view of AC type
17.5
11 20.5
■ Metal fixture for screw tightening 6-ø5.0 (Mounting hole) Main unit mounting hole (2 positions)
99 111
31 50 64 t=2
* Two M3.5 countersunk-head screws are included for mounting the main unit.
Chapter 1 Configuration and Specifications
1-23
Page 48
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
1.6
KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
Visual KV Series
This section describes the name and function of each part, the I/O specifications, the terminal layout, circuit diagrams, and dimensions of the KV-24xx.
1.6.1 Part Names and Functions 1. Input terminal block 9. Input voltage selector switch Provided on side INPUT
24V C1
001 000
003 002
005 004
007
009
006
008
011 010
013 012
015 014
IN
0
5V
VOLT
0ch 1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
5. Output indicator lamps 6. Connector (provided on side)
10. Communication port A 11. Communication port B
7. Access Window KV-24AR
0
1
2
3
4
5
6
8. Setting keys
7
5ch 500
3. Power input terminal
4. Input indicator lamps
501 C3
24V-OUT-OV
502 C4
503 C5
504 C6
506 505
507
OUT
(Power input terminals for AC power type are provided on the lower side.)
1
L
~
N
AC100V-240V 0.6A 50/60Hz
No. 1
2
3
4 5 6
Output terminal block Power input terminal (KV-24DR/DT(P)) Power output terminal (KV-24AR/AT(P)) Input indicator lamps Output indicator lamps Connector (provided on side)
7
Access Window
8
Setting keys
9 10 11 ➮
Name Input terminal block
Input voltage selector switch Communication port A Communication port B
2. Output terminal block
Function 24 VDC input terminal block (000 to 007 can be changed to 5 V input). Output terminal block. Pulse output function is built in 500 to 502 (in transistor output type only). A 1.6 kΩ current limiting resistor is built in R502 (to connect a motor driver). Supplies 24 VDC. Supplies 100 to 240 VAC to the power input terminals on the lower side of the unit, and allows the service power supply to be taken from the 24 VDC terminal. Indicate input status. Each lamp lights up at ON. Indicate output status. Each lamp lights up at ON. Used to connect an expansion unit. Used to refer to and change the current and set values of timers and counters as well as the contents of data memories. The backlight color indicates the operation status. Lit in green: RUN mode Lit in red: PROGRAM mode Flashing red: Error status Used to refer to and change current values, etc. while referring to the Access Window. Changes the input voltage of the basic unit. : 24 V input : 5 V input RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel. RJ-11 Modular connector for connecting a personal computer, handheld programmer, or operator interface panel.
For more about the Access Window, refer to "Chapter 3. Access Window" (p.1-79).
1-24 Chapter 1 Configuration and Specifications
Page 49
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
1.6.2 Terminal Layout Drawings and I/O Circuit Diagrams KV-24AR/DR (Relay output type)
Visual KV Series
■ Terminal layout drawing C1 001 003 005 007 009 011 013 015 000 002 004 006 008 010 012 014
500 501 502 503 504 506 24V 0V
C3 C4 C5 C6 505 507
11
■ Input circuit diagram Internal circuit
000
001
Blue
Brown
Brown Black
Brown Black
Blue
Three-wire type
Brown Black Three-wire type
Blue
Three-wire type
Blue
Brown Black
Blue
Brown Black
Blue
C1
Three-wire type
003
Three-wire type
Brown Black
Blue
Brown Black
Blue
Blue
Brown Black
Brown Black
Three-wire type
Three-wire type
Blue
002
005
007
Brown Black
Blue
Brown Black
Blue
004
Three-wire type
009
Brown Black
Blue
Brown Black
Brown Black Three-wire type
Sensor
Photocoupler insulation
4.3KΩ 000 to 007 24V/5V selector circuit
C1
Circuit configuration of inputs 008 to 015 4.3KΩ 008 to 015
Photocoupler insulation
510Ω C1
Chapter 1 Configuration and Specifications
Internal circuit
Circuit configuration of inputs 000 to 007
Internal circuit
Three-wire type
Black Three-wire type
Blue
Three-wire type
Blue
Brown Black
Blue
011
006
Three-wire type
013
015
008
Three-wire type
010
Three-wire type
012
Three-wire type
014
1-25
Page 50
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit) ■ Output circuit diagram
Visual KV Series
Internal circuit
500
24V
0V
501
C3
502
C4
503
C5
504
C6
506
505
507
1 500 501 502 to 503 504 to 507
C3 C4 C5 C6
• C3 to C6 are each independent.
1-26 Chapter 1 Configuration and Specifications