The text of a spec sheet · part 1 of 2
Visual KV Series: Compact Programmable Logic Controller with Built-in Display, pages 1 to 7
Pages 1 to 7 of 14
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Keyence KV-DA4, Keyence KV-E4X, Keyence KV-U2, Keyence KV-U3, Keyence KV-24R and Keyence KV-40R
Page 1
Cat No. NKV-EU-C
New KV Series Model List Category
Name 10-point AC type
10-point DC type
16-point AC type
16-point DC type Basic unit 24-point AC type
24-point DC type
40-point AC type
40-point DC type
8-point type Expansion unit
16-point type
Description
Model KV-10AT(P)
6-point input/4-point NPN (PNP) transistor output
KV-10AR
6-point input/4-point relay output
KV-10DT(P)
6-point input/4-point NPN (PNP) transistor output
KV-10DR
6-point input/4-point relay output
KV-16AT(P)
10-point input/6-point NPN (PNP) transistor output
KV-16AR
10-point input/6-point relay output
KV-16DT(P)
10-point input/6-point NPN (PNP) transistor output
KV-16DR
10-point input/6-point relay output
KV-24AT(P)
16-point input/8-point NPN (PNP) transistor output
KV-24AR
16-point input/8-point relay output
KV-24DT(P)
16-point input/8-point NPN (PNP) transistor output
KV-24DR
16-point input/8-point relay output
KV-40AT(P)
24-point input/16-point NPN (PNP) transistor output
KV-40AR
24-point input/16-point relay output
KV-40DT(P)
24-point input/16-point NPN (PNP) transistor output
KV-40DR
24-point input/16-point relay output
KV-E8X
8-point input
KV-E8T(P)
8-point NPN (PNP) transistor output
KV-E8R
8-point relay output
KV-E4XT(P)
4-point input/4-point NPN (PNP) transistor output
KV-E4XR
4-point input/4-point relay input
KV-E16X
16-point input
KV-E16T(P)
16-point NPN (PNP) transistor output
KV-E16R
16-point relay output
Easy-to-set display
Operator panel
KV-D20
20 digits x 4 lines with customized switches/lamps (cable included)
Extension cable for expansion unit
For all expansion units and adapters
OP-35361
For 300-mm extension
Spacer for 8-point expansion unit
OP-35343
Spacer for 16-point expansion unit
OP-35344
Used to make an expansion unit flush with an AC power type basic unit.
For 10-point basic unit
OP-35346
For 16-point basic unit
OP-35346
For 24-point basic unit
OP-35347
For 40-point basic unit
OP-35348
For 8- to 16-point expansion unit
OP-35349
Handheld programmer
KV-P3E-01
Memory card slot, cable (OP-26487) included
Programming support software
KV-H6WU2
Windows version
Cable/connector for PC/AT or compatibles
OP-26487
Expansion unit spacer
Metal fixture for screw tightening
Programming
Memory card
OP-26486 M-2 M-3
Compact Programmable Logic Controller with Built-in Display
Visual KV Series
User-Friendly Design
Designed with the user in mind, the Visual KV is a high-speed compact unit. It features the industry’s first built-in access window and includes an AC power supply model and operator interface panel.
rst y Fi r t s u Ind
Visual PLC
Complete Product Line Ultra Small Size AC/DC, Transistor(NPN/PNP)/Relay High Speed Scan Time 12 base units/8 expansion units of 140 s
World’s Smallest
Used to directly mount the KV series with screws instead of a DIN rail.
ACCESS WINDOW
With simulator function, delivered in two 3.5-inch floppy disks (cable included)
Built-in Access Window
For D-sub 9-pin, Basic unit-to-PC with programming support software
Up to 1 ft away for installation flexibility
Saves/reads ladder programs via KV-P3E(01) s slot or Z-1 card reader/writer. M-2: 24 programs max.,M-3: 48 programs max.
Visit our website for other Keyence products at http://www.keyence.co.uk Specifications are subject to change without notice.
European Headquarters KEYENCE (UK) LIMITED 504-510 Elder House, Station Square, Elder Gate, Milton Keynes MK9 1LR, U.K. PHONE: 01908-696900 FAX: 01908-696777
Operator Interface
Expansion Units
External Display
16 to 152 I/O’s
Worldwide Headquarters KEYENCE CORPORATION 1-3-14, Higashi-Nakajima, Higashi-Yodogawa-ku, Osaka, 533-8555, Japan PHONE: 81-6-6379-2211 FAX: 81-6-6379-2131
KEYENCE CORPORATION OF AMERICA PHONE: 201-930-0100 FAX: 201-930-0099
KEYENCE DEUTSCHLAND GmbH PHONE: 0711-7973710 FAX: 0711-7977799
KEYENCE FRANCE S.A. PHONE: 01 47 92 76 76 FAX: 01 47 92 76 77
KEYENCE (MALAYSIA) SDN BHD PHONE: 03-252-2211 FAX: 03-252-2131
KEYENCE (THAILAND) CO., LTD PHONE: 02-934-6777 FAX: 02-934-6775
KEYENCE KOREA CORPORATION PHONE: 02-563-1270 FAX: 02-563-1271
KEYENCE SINGAPORE PTE LTD PHONE: 392-1011 FAX,: 392-5055
'KEYENCE CORPORATION,1999 NKV-EU-C-2-1199 Printed in Japan
2
Page 2
Cat No. NKV-EU-C
New KV Series Model List Category
Name 10-point AC type
10-point DC type
16-point AC type
16-point DC type Basic unit 24-point AC type
24-point DC type
40-point AC type
40-point DC type
8-point type Expansion unit
16-point type
Description
Model KV-10AT(P)
6-point input/4-point NPN (PNP) transistor output
KV-10AR
6-point input/4-point relay output
KV-10DT(P)
6-point input/4-point NPN (PNP) transistor output
KV-10DR
6-point input/4-point relay output
KV-16AT(P)
10-point input/6-point NPN (PNP) transistor output
KV-16AR
10-point input/6-point relay output
KV-16DT(P)
10-point input/6-point NPN (PNP) transistor output
KV-16DR
10-point input/6-point relay output
KV-24AT(P)
16-point input/8-point NPN (PNP) transistor output
KV-24AR
16-point input/8-point relay output
KV-24DT(P)
16-point input/8-point NPN (PNP) transistor output
KV-24DR
16-point input/8-point relay output
KV-40AT(P)
24-point input/16-point NPN (PNP) transistor output
KV-40AR
24-point input/16-point relay output
KV-40DT(P)
24-point input/16-point NPN (PNP) transistor output
KV-40DR
24-point input/16-point relay output
KV-E8X
8-point input
KV-E8T(P)
8-point NPN (PNP) transistor output
KV-E8R
8-point relay output
KV-E4XT(P)
4-point input/4-point NPN (PNP) transistor output
KV-E4XR
4-point input/4-point relay input
KV-E16X
16-point input
KV-E16T(P)
16-point NPN (PNP) transistor output
KV-E16R
16-point relay output
Easy-to-set display
Operator panel
KV-D20
20 digits x 4 lines with customized switches/lamps (cable included)
Extension cable for expansion unit
For all expansion units and adapters
OP-35361
For 300-mm extension
Spacer for 8-point expansion unit
OP-35343
Spacer for 16-point expansion unit
OP-35344
Used to make an expansion unit flush with an AC power type basic unit.
For 10-point basic unit
OP-35346
For 16-point basic unit
OP-35346
For 24-point basic unit
OP-35347
For 40-point basic unit
OP-35348
For 8- to 16-point expansion unit
OP-35349
Handheld programmer
KV-P3E-01
Memory card slot, cable (OP-26487) included
Programming support software
KV-H6WU2
Windows version
Cable/connector for PC/AT or compatibles
OP-26487
Expansion unit spacer
Metal fixture for screw tightening
Programming
Memory card
OP-26486 M-2 M-3
Compact Programmable Logic Controller with Built-in Display
Visual KV Series
User-Friendly Design
Designed with the user in mind, the Visual KV is a high-speed compact unit. It features the industry’s first built-in access window and includes an AC power supply model and operator interface panel.
rst y Fi r t s u Ind
Visual PLC
Complete Product Line Ultra Small Size AC/DC, Transistor(NPN/PNP)/Relay High Speed Scan Time 12 base units/8 expansion units of 140 s
World’s Smallest
Used to directly mount the KV series with screws instead of a DIN rail.
ACCESS WINDOW
With simulator function, delivered in two 3.5-inch floppy disks (cable included)
Built-in Access Window
For D-sub 9-pin, Basic unit-to-PC with programming support software
Up to 1 ft away for installation flexibility
Saves/reads ladder programs via KV-P3E(01) s slot or Z-1 card reader/writer. M-2: 24 programs max.,M-3: 48 programs max.
Visit our website for other Keyence products at http://www.keyence.co.uk Specifications are subject to change without notice.
European Headquarters KEYENCE (UK) LIMITED 504-510 Elder House, Station Square, Elder Gate, Milton Keynes MK9 1LR, U.K. PHONE: 01908-696900 FAX: 01908-696777
Operator Interface
Expansion Units
External Display
16 to 152 I/O’s
Worldwide Headquarters KEYENCE CORPORATION 1-3-14, Higashi-Nakajima, Higashi-Yodogawa-ku, Osaka, 533-8555, Japan PHONE: 81-6-6379-2211 FAX: 81-6-6379-2131
KEYENCE CORPORATION OF AMERICA PHONE: 201-930-0100 FAX: 201-930-0099
KEYENCE DEUTSCHLAND GmbH PHONE: 0711-7973710 FAX: 0711-7977799
KEYENCE FRANCE S.A. PHONE: 01 47 92 76 76 FAX: 01 47 92 76 77
KEYENCE (MALAYSIA) SDN BHD PHONE: 03-252-2211 FAX: 03-252-2131
KEYENCE (THAILAND) CO., LTD PHONE: 02-934-6777 FAX: 02-934-6775
KEYENCE KOREA CORPORATION PHONE: 02-563-1270 FAX: 02-563-1271
KEYENCE SINGAPORE PTE LTD PHONE: 392-1011 FAX,: 392-5055
'KEYENCE CORPORATION,1999 NKV-EU-C-2-1199 Printed in Japan
2
Page 3
Built-in Operator Interface PLC & User Friendly Operator Panel 2/3rd the size of conventional AC type PLCs The new AC version 40 I/O KV is 2/3rd the size of conventional PLCs. The slender design not only saves mounting space, but allows the entire system including the distribution panel and the control box to be downsized. (*For AC types that use screw-type terminal blocks)
110
70
World’s Fastest Class Displays operational instruction messages.
The Visual KV CPU features a built-in display (Access Window) that allows the PLC’s data to be checked upon start-up and during modification or changeover.
Access Window Allows Information to be Conveniently Available When making precise on-line adjustments When checking or changing some device values the PLC does not need to be connected to internal devices, such as a timer, while to either a PC or handheld programmer. the PLC is operating.
When you need to stop the PLC and check the program without connecting to a PC or handheld programmer.
Other Functions
3
The Operator Panel Provides Features of a Full Scale Display The on-screen feedback digital trimmer allows workers to make adjustments without stopping the production line.
At a glance, the status of registered customized switches F1 to F4 and lamps 1 to 4 can be confirmed.
Input and output status of the I/O terminals can be monitored.
Error Message Function
User Message Function
Beep function
Display customization
The Visual KV features a key lock function to prevent accidental changes to the settings.
Error codes are immediately displayed on the LCD. With a conventional PLC, the PLC had to be connected to a handheld programmer in order to determine the error code.
With a simple ladder program, a flashing LED display message (No.0 to 255) can appeal, indicating a user error code.
The KV-D20 features a beep function to provide audio cues to workers.
Workers can choose from various display options to create a customized, easy-to-see display.
4
Processing time Minimum scan time
KV-16T KV-16DT
The processing time is
IN to OUT time (500-step basic instructions)
KV-16T decreased by 50%
KV-16DT
IN to OUT time (500-step application/ arithmetic instructions)
KV-16T compared to that of our conventional product.
KV-16DT
Industry First Design
Patent pending
The PLC has a 2-colour backlit LCD(5 digits x 3), that is used for display functions. Typical Applications
Built-In Operator Convenience Functions
Key Lock Function
The fastest processing among products of this class. The minimum scan time is 140 s and the minimum instruction execution time is 0.7 s.
A modular cable completes the connection.
FUNCTIONS
In addition to having the same functions as the Visual KV PLC’s Access Window, the operator panel displays comments generated by a ladder program. This easy to use display features a variety of functions.
*
World’s Smallest Design
SYSTEM/ VARIATION
Ladder Comment DisplayAllows you to easily check, change or detect abnormalities.
Displays the current and preset values of the counter or timer.
Serves as a handheld programmer when changing the preset value.
Displays the error code.
SPECIFICATIONS
No PC or Handheld Programmer Required to Monitor Operation or Make Minor Changes
OUTLINE for Factory Staff
DIMENSIONS
For Design Engineers
5
Page 4
Built-in Operator Interface PLC & User Friendly Operator Panel 2/3rd the size of conventional AC type PLCs The new AC version 40 I/O KV is 2/3rd the size of conventional PLCs. The slender design not only saves mounting space, but allows the entire system including the distribution panel and the control box to be downsized. (*For AC types that use screw-type terminal blocks)
110
70
World’s Fastest Class Displays operational instruction messages.
The Visual KV CPU features a built-in display (Access Window) that allows the PLC’s data to be checked upon start-up and during modification or changeover.
Access Window Allows Information to be Conveniently Available When making precise on-line adjustments When checking or changing some device values the PLC does not need to be connected to internal devices, such as a timer, while to either a PC or handheld programmer. the PLC is operating.
When you need to stop the PLC and check the program without connecting to a PC or handheld programmer.
Other Functions
3
The Operator Panel Provides Features of a Full Scale Display The on-screen feedback digital trimmer allows workers to make adjustments without stopping the production line.
At a glance, the status of registered customized switches F1 to F4 and lamps 1 to 4 can be confirmed.
Input and output status of the I/O terminals can be monitored.
Error Message Function
User Message Function
Beep function
Display customization
The Visual KV features a key lock function to prevent accidental changes to the settings.
Error codes are immediately displayed on the LCD. With a conventional PLC, the PLC had to be connected to a handheld programmer in order to determine the error code.
With a simple ladder program, a flashing LED display message (No.0 to 255) can appeal, indicating a user error code.
The KV-D20 features a beep function to provide audio cues to workers.
Workers can choose from various display options to create a customized, easy-to-see display.
4
Processing time Minimum scan time
KV-16T KV-16DT
The processing time is
IN to OUT time (500-step basic instructions)
KV-16T decreased by 50%
KV-16DT
IN to OUT time (500-step application/ arithmetic instructions)
KV-16T compared to that of our conventional product.
KV-16DT
Industry First Design
Patent pending
The PLC has a 2-colour backlit LCD(5 digits x 3), that is used for display functions. Typical Applications
Built-In Operator Convenience Functions
Key Lock Function
The fastest processing among products of this class. The minimum scan time is 140 s and the minimum instruction execution time is 0.7 s.
A modular cable completes the connection.
FUNCTIONS
In addition to having the same functions as the Visual KV PLC’s Access Window, the operator panel displays comments generated by a ladder program. This easy to use display features a variety of functions.
*
World’s Smallest Design
SYSTEM/ VARIATION
Ladder Comment DisplayAllows you to easily check, change or detect abnormalities.
Displays the current and preset values of the counter or timer.
Serves as a handheld programmer when changing the preset value.
Displays the error code.
SPECIFICATIONS
No PC or Handheld Programmer Required to Monitor Operation or Make Minor Changes
OUTLINE for Factory Staff
DIMENSIONS
For Design Engineers
5
Page 5
Built-in Operator Interface PLC & User Friendly Operator Panel 2/3rd the size of conventional AC type PLCs The new AC version 40 I/O KV is 2/3rd the size of conventional PLCs. The slender design not only saves mounting space, but allows the entire system including the distribution panel and the control box to be downsized. (*For AC types that use screw-type terminal blocks)
110
70
World’s Fastest Class Displays operational instruction messages.
The Visual KV CPU features a built-in display (Access Window) that allows the PLC’s data to be checked upon start-up and during modification or changeover.
Access Window Allows Information to be Conveniently Available When making precise on-line adjustments When checking or changing some device values the PLC does not need to be connected to internal devices, such as a timer, while to either a PC or handheld programmer. the PLC is operating.
When you need to stop the PLC and check the program without connecting to a PC or handheld programmer.
Other Functions
3
The Operator Panel Provides Features of a Full Scale Display The on-screen feedback digital trimmer allows workers to make adjustments without stopping the production line.
At a glance, the status of registered customized switches F1 to F4 and lamps 1 to 4 can be confirmed.
Input and output status of the I/O terminals can be monitored.
Error Message Function
User Message Function
Beep function
Display customization
The Visual KV features a key lock function to prevent accidental changes to the settings.
Error codes are immediately displayed on the LCD. With a conventional PLC, the PLC had to be connected to a handheld programmer in order to determine the error code.
With a simple ladder program, a flashing LED display message (No.0 to 255) can appeal, indicating a user error code.
The KV-D20 features a beep function to provide audio cues to workers.
Workers can choose from various display options to create a customized, easy-to-see display.
4
Processing time Minimum scan time
KV-16T KV-16DT
The processing time is
IN to OUT time (500-step basic instructions)
KV-16T decreased by 50%
KV-16DT
IN to OUT time (500-step application/ arithmetic instructions)
KV-16T compared to that of our conventional product.
KV-16DT
Industry First Design
Patent pending
The PLC has a 2-colour backlit LCD(5 digits x 3), that is used for display functions. Typical Applications
Built-In Operator Convenience Functions
Key Lock Function
The fastest processing among products of this class. The minimum scan time is 140 s and the minimum instruction execution time is 0.7 s.
A modular cable completes the connection.
FUNCTIONS
In addition to having the same functions as the Visual KV PLC’s Access Window, the operator panel displays comments generated by a ladder program. This easy to use display features a variety of functions.
*
World’s Smallest Design
SYSTEM/ VARIATION
Ladder Comment DisplayAllows you to easily check, change or detect abnormalities.
Displays the current and preset values of the counter or timer.
Serves as a handheld programmer when changing the preset value.
Displays the error code.
SPECIFICATIONS
No PC or Handheld Programmer Required to Monitor Operation or Make Minor Changes
OUTLINE for Factory Staff
DIMENSIONS
For Design Engineers
5
Page 6
Incorporates a 30kHz, 2 phase, 24-bit counter and eliminates the need for an additional high-speed counter.
To achieve this measurement, simply input the frequency counting period into the specified data memory using a real number in "ms". The measured result is automatically input into the specified data memory. The measured result can be displayed on the Access Window.
Channel 2
A-phase: 005 (B-phase: 007)
24-bit high-speed counter CTC1
High-speed counter comparators CTC2, CTC3
4 High Speed Interrupt Inputs
FUNCTIONS
A-phase: 004 (B-phase: 006)
The frequency of the gear revolutions can be displayed.
Direct output
Specified Frequency Pulse Output Function Easily controls motor speed.
500
Without complicated programming, pulses with a specified frequency (16 to 50000Hz) can be output. Just input the frequency (Hz) into the specified data memory using a real number. The pulses with the specified frequency are then output from the output (501). The function allows multi-step speed control, as shown to the right.
501
Incorporates 4 high-speed interrupt inputs with a maximum speed of 10 s.
The preset speed of a motor can be manually changed by simply using the Access Window. This feature is ideal for systems that require frequent setting changes or fine adjustments.
Complicated multi-step ramp up-and-down control is possible. 50kHz 30kHz
20kHz 5kHz
0Hz
0Hz
Applications
When an interrupt input occurs, the routine scanning is suspended and the interrupt inputs are immediately processed with a response time of only 10 s.The Visual KV is optimal for fast sensor input on high-speed lines.
Routine scan
Time adjustment of sheet immersion in a treatment bath
Tension adjustment of hoop material
000 001 002 003
SPECIFICATIONS
Channel 1
High-speed counter comparators CTC0, CTC1
Rotary encoder, etc.
The Visual KV is unmatched in cost and performance, even when evaluated as only a 4 interrupt unit.
The Visual KV can be used as a simple stepper motor controller by setting the output frequency on the Access Window.*
Simple Ramping Control Function The Visual KV incorporates a positioning control function similar to expensive units for application practicality and cost reduction.
Incorporates a single-axis stepper motor control independent of the highspeed counter function that allows a motor up to 50kHz to be controlled. The simple positioning control stepper function can be activated by just inputting the setting values into the specific data memories. Speed DM1481
DM1480
DM1482
Amount of movement
Setting items for the positioning control function (x-axis) Start-up frequency (Hz) : DM1480 Run frequency (Hz) : DM1481 Acceleration/deceleration period (ms) : DM1482 Number of output pulses (high order): DM1485 (low order): DM1484 Operation start relay : 2310 Forced slowdown stop relay : 2308 Emergency stop relay : 2309
Only 1-line of ladder logic is needed to create the positioning control function.
The Visual KV base unit can control stepper motors.* 6
0002 #01000 DW DM1480
#05000 DW DM1481
#03000 DW DM1482
Start-up frequency 1 kHz
Run frequency 5 kHz
Acceleration/ deceleration period 3 sec
#00001 DW DM1485
#34464 2310 DW DM1484
Number of output pulses 100.000
SYSTEM/ VARIATION
The Visual KV base unit incorporates 2-channel, 2 phase high-speed counters and high-speed counter comparators. This allows direct connection with a rotary encoder and counting input from the encoder. The Visual KV can be used for various applications, such as speed measurement and high speed interval counting; by utilizing the input capture functions, that automatically saves input values to the 4 interrupt inputs during high-speed counting. 24-bit high-speed counter CTC0 the rotational frequency of a gear or rotary Frequency Counter Function Measures encoder without complicated programming.
Synchronization Control Function A single Visual KV unit enables synchronization control. Pulses with a measured frequency can be output* by combining the frequency counter function with the specified-frequency pulse output.
Speed measurement
Synchronization control
Cam Switch Function Serves as a simple cam switch. An operation similar to that of a Cam can be achieved by combining an inexpensive rotary encoder with the Visual KV. Connect the rotary encoder to the Visual KV and input the desired angles into the specified data memories. The relays can then be turned on or off at the specified angles (up to 32 points, in increments of 1 degree.) This Function of the Visual KV can be utilized as an alternative to an expensive Cam switch in order to reduce overall costs.
DIMENSIONS
2-Channel High Speed Counters
OUTLINE
Practical Functions
A, B, and Z phases Rotary encoder (Incremental type)
120¡
240¡
360¡
*: A motor driver is required separately. 7
Page 7
Incorporates a 30kHz, 2 phase, 24-bit counter and eliminates the need for an additional high-speed counter.
To achieve this measurement, simply input the frequency counting period into the specified data memory using a real number in "ms". The measured result is automatically input into the specified data memory. The measured result can be displayed on the Access Window.
Channel 2
A-phase: 005 (B-phase: 007)
24-bit high-speed counter CTC1
High-speed counter comparators CTC2, CTC3
4 High Speed Interrupt Inputs
FUNCTIONS
A-phase: 004 (B-phase: 006)
The frequency of the gear revolutions can be displayed.
Direct output
Specified Frequency Pulse Output Function Easily controls motor speed.
500
Without complicated programming, pulses with a specified frequency (16 to 50000Hz) can be output. Just input the frequency (Hz) into the specified data memory using a real number. The pulses with the specified frequency are then output from the output (501). The function allows multi-step speed control, as shown to the right.
501
Incorporates 4 high-speed interrupt inputs with a maximum speed of 10 s.
The preset speed of a motor can be manually changed by simply using the Access Window. This feature is ideal for systems that require frequent setting changes or fine adjustments.
Complicated multi-step ramp up-and-down control is possible. 50kHz 30kHz
20kHz 5kHz
0Hz
0Hz
Applications
When an interrupt input occurs, the routine scanning is suspended and the interrupt inputs are immediately processed with a response time of only 10 s.The Visual KV is optimal for fast sensor input on high-speed lines.
Routine scan
Time adjustment of sheet immersion in a treatment bath
Tension adjustment of hoop material
000 001 002 003
SPECIFICATIONS
Channel 1
High-speed counter comparators CTC0, CTC1
Rotary encoder, etc.
The Visual KV is unmatched in cost and performance, even when evaluated as only a 4 interrupt unit.
The Visual KV can be used as a simple stepper motor controller by setting the output frequency on the Access Window.*
Simple Ramping Control Function The Visual KV incorporates a positioning control function similar to expensive units for application practicality and cost reduction.
Incorporates a single-axis stepper motor control independent of the highspeed counter function that allows a motor up to 50kHz to be controlled. The simple positioning control stepper function can be activated by just inputting the setting values into the specific data memories. Speed DM1481
DM1480
DM1482
Amount of movement
Setting items for the positioning control function (x-axis) Start-up frequency (Hz) : DM1480 Run frequency (Hz) : DM1481 Acceleration/deceleration period (ms) : DM1482 Number of output pulses (high order): DM1485 (low order): DM1484 Operation start relay : 2310 Forced slowdown stop relay : 2308 Emergency stop relay : 2309
Only 1-line of ladder logic is needed to create the positioning control function.
The Visual KV base unit can control stepper motors.* 6
0002 #01000 DW DM1480
#05000 DW DM1481
#03000 DW DM1482
Start-up frequency 1 kHz
Run frequency 5 kHz
Acceleration/ deceleration period 3 sec
#00001 DW DM1485
#34464 2310 DW DM1484
Number of output pulses 100.000
SYSTEM/ VARIATION
The Visual KV base unit incorporates 2-channel, 2 phase high-speed counters and high-speed counter comparators. This allows direct connection with a rotary encoder and counting input from the encoder. The Visual KV can be used for various applications, such as speed measurement and high speed interval counting; by utilizing the input capture functions, that automatically saves input values to the 4 interrupt inputs during high-speed counting. 24-bit high-speed counter CTC0 the rotational frequency of a gear or rotary Frequency Counter Function Measures encoder without complicated programming.
Synchronization Control Function A single Visual KV unit enables synchronization control. Pulses with a measured frequency can be output* by combining the frequency counter function with the specified-frequency pulse output.
Speed measurement
Synchronization control
Cam Switch Function Serves as a simple cam switch. An operation similar to that of a Cam can be achieved by combining an inexpensive rotary encoder with the Visual KV. Connect the rotary encoder to the Visual KV and input the desired angles into the specified data memories. The relays can then be turned on or off at the specified angles (up to 32 points, in increments of 1 degree.) This Function of the Visual KV can be utilized as an alternative to an expensive Cam switch in order to reduce overall costs.
DIMENSIONS
2-Channel High Speed Counters
OUTLINE
Practical Functions
A, B, and Z phases Rotary encoder (Incremental type)
120¡
240¡
360¡
*: A motor driver is required separately. 7