For the Keyence N-400
Page 51
Chapter 3
N-400 Setup Procedure
RS-485 The RS-485 screen is used to set the RS-485 communication parameters for the N-400. Set these parameters so that they conform to those of the connected BL series.
3
Note: We recommend that you set the baud rate to “38400 bits/s” to increase the processing speed, since the RS-485 communication between the N-400 and the BL series transfers a large volume of data.
43
Page 52
Chapter 3
N-400 Setup Procedure
3.3.2 Reading/Saving/Printing File The FILES screen is used to save updated settings in a file, to read a saved setting file, and to print the contents of a setting file.
3
•
Open: Reads a saved setting file.
•
Save: Saves updated settings in a file.
•
Compare: Compares the settings currently edited with a file previously saved.
•
Print: Prints contents of a setting file.
•
Default (Initialize settings): Restores updated settings to the default settings.
•
Version info: Displays the version information of this software.
Reading a previously saved setting file 1. To read a previously saved setting file, click on [Open]. The following screen will appear.
2. When you click on [OK] after selecting a file, the selected file can be opened.
44
Page 53
Chapter 3
N-400 Setup Procedure
Saving updated settings in a file 1. To save updated settings in a file, click on [Save]. The following screen will appear.
3
2. Click on the file name entry field, and enter a file name using the keyboard. Specify a file name within eight characters. Be sure to add the extension “NCF”. After entering the file name, click on [OK] to save the file.
Note: This software cannot accept a long file name in Windows 95.
Tips
When the saved setting file is sent to the N-400, the name of the file is simultaneously sent to the N-400. When you read the settings of the N-400 using this software, the file name is also read. It is convenient for maintenance since you can find the file that stores the settings. To enter a file name, use alphanumerics (letters and numbers) only. Otherwise, the file name cannot be sent to the N-400, because it can only recognize alphanumerics. To send a file name, be sure to enter the file name using alphanumerics and then save it. (If the file name is not saved, it cannot be sent to the N-400.)
45
Page 54
Chapter 3
N-400 Setup Procedure
Comparing the settings currently edited with a saved file 1. To compare the settings currently edited with the setting file previously saved, click on [Compare].
3
2. Select a file to be compared, and click on [OK]. Then, the system compares the selected file with the settings currently edited, and displays the result. Matched
46
Not matched
Page 55
Chapter 3
N-400 Setup Procedure
Printing contents of a setting file 1. To print settings, click on [Print]. The following screen will appear.
3 2. Adjust “Printer Setup” as required, and click on [OK]. Printing will then start.
Restoring the settings currently edited to the default (initial) settings 1. To restore the settings currently being edited to the default settings, click on [Default (Initialize settings)]. 2. If you try to initialize the settings currently being edited without saving them, the following message appears. If you wish to execute initialization, click on [OK].
Note: The initialization procedure described in this section is used to initialize the settings being edited with the setup software. The settings on the N-400 cannot be initialized.
47
Page 56
Chapter 3
3.4
N-400 Setup Procedure
Sending/Receiving Settings
Sending updated settings to the N-400 To send updated settings to the N-400, perform the following procedure. 1. Press and hold the N-400 test switch for five seconds. When the N-400 displays “S0 (50)”, the communication parameters are temporarily set as follows:
3 Tips
•
Baud rate: 9600 bits/s
•
Step bit length: 1 bit
•
Data length: 7 bits
•
PLC link: Disabled
•
Parity: Even
If you know the current communication parameter settings of the N-400, this step is not necessary. You can send data to the N-400 by setting the communication parameters of the host computer using [COM PORT] so that they conform to the current settings of the N-400. However, if PLC link is enabled, you cannot send data to the N-400 without performing this step because the handshaking protocol is set for PLC link only. 2. Click on [COM PORT] to set the communication parameters of the host computer according to the values listed in the step 1. (above procedure). Select an RS-232C port, and click on [OK].
3. Click on [Send setting (Save in N-400 EEP-ROM]. The updated settings are then sent to the N-400.
48
Page 57
Chapter 3
N-400 Setup Procedure
4. If the settings were successfully sent to the N-400, the following message appears.
If the host computer failed to send the data to the N-400, the following message appears.
3
If this message is displayed, check the following points: •
• •
Check that [COM PORT] is set to the values listed in step 1. when the N400 displays “S0 (50)”. Check that the power to the N-400 is ON. Check that the RS-232C cable pin assignment of the N-400 is the same as that of the host computer.
5. After the settings are sent, press the N-400 test switch once to reset the “S0 (50)” condition. (If the N-400 does not display “S0 (50)”, you do not need to press the test switch. ) When the N-400 displays “00”, the sending procedure is completed. (The communication parameters of the N-400 are set to the updated settings.)
49
Page 58
Chapter 3
N-400 Setup Procedure
Reading the current settings of the N-400 To read the current settings of the N-400, perform the following procedure. (This procedure is almost the same as the procedure for sending settings.) 1. Press and hold the N-400 test switch for five seconds. When the N-400 displays “S0 (50)”, the communication parameters are temporarily set as follows:
3
Tips
•
Baud rate: 9600 bits/s
•
Data length: 7 bits
•
Parity: Even
•
Step bit length: 1 bit
•
PLC link: Disabled
If you know the current communication parameter settings of the N-400, step 1. is not necessary. You can send data to the N-400 by setting the communication parameters of the host computer using [COM PORT] so that they conform to the current settings of the N-400. However, if PLC link is enabled, you cannot send data to the N-400 without performing step 1., because the handshaking protocol is set for PLC link only. 2. Click on [COM PORT] to set the communication parameters of the host computer according to the values listed in step 1. Select an RS-232C port and click on [OK].
3. Click on [Send setting (Save in N-400 EEP-ROM)]. When you click on [Read N-400 settings], the settings of the N-400 can be read on the host computer.
50
Page 59
Chapter 3
N-400 Setup Procedure
4. If the settings of the N-400 were successfully read, the following message appears.
If the host computer failed to read the data, the following message appears.
3
If this message is displayed, check the following points: •
• •
Check that [COM PORT] is set to the values listed in step 1. when the N400 displays “S0 (50).” Check that the power to the N-400 is ON. Check that the RS-232C cable pin assignment of the N-400 is the same as that of the host computer.
5. After the settings are read, press the N-400 test switch once to reset the “S0 (50)” condition. (If the N-400 does not display “S0 (50)”, you do not need to press the test switch. ) When the N-400 displays “00”, the reading procedure is completed.
51
Page 60
Chapter 3
3.5
N-400 Setup Procedure
Using Monitor This setup software provides the “Monitor” program to check if the N-400 can send data properly. The “Monitor” program allows you to display the data read by the BL series on the host computer’s monitor screen, and also to send a command from the host computer to the N-400 or BL series. 1. Click on [COM PORT] to set the communication parameters of the host computer according to the current settings of the N-400. 2. Click on [Monitor]. The MONITOR screen will appear.
3
3. When the BL series reads bar codes, the data read by the BL series is listed on the screen (in the [Received Data] field). A record of up to 1000 lines of data can be obtained. Using the scroll bar at the right of the [Received Data] field, you can see the previous data.
4. If you click [Stop], received data is not listed. (The button name is changed to [Start].) If you try to display received data again, click on [Start].
52