The text of a spec sheet · part 1 of 1
DC Input Modules: D2-08ND3 DC Input, D2-16ND3-2 DC Input, pages 1 to 5
Pages 1 to 5 of 5
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the PLC Direct D2-08ND3 and Koyo D2-08ND3
Page 1
DC Input Modules D2-08ND3 DC Input
<--->
D2-16ND3-2 DC Input
<--->
Inputs per Module
8 (sink/source)
Inputs per Module
16 (sink/source)
Commons per Module
1 (2 I/O terminal points)
Commons per Module
2 isolated (8 I/O terminal points / com)
Input Voltage Range
10.2-26.4 VDC
Input Voltage Range
20-28 VDC
Peak Voltage
26.4 VDC
Peak Voltage
30 VDC (10 mA)
ON Voltage Level
9.5 VDC minimum
ON Voltage Level
19 VDC minimum
OFF Voltage Level
3.5 VDC maximum
OFF Voltage Level
7VDC maximum
AC Frequency
N/A
AC Frequency
N/A
Input Impedance
2.7
Input Impedance
3.9
Input Current
4.0 mA @ 12 VDC 8.5 mA @ 24 VDC
Input Current
6 mA @ 24 VDC
Minimum ON Current
3.5 mA
Maximum OFF Current
1.5 mA
Base Power Required 5VDC
100 mA
OFF to ON Response
3 to 9 ms
ON to OFF Response
3 to 9 ms
Terminal Type (included)
Removable, D2-16IOCON
Status Indicator
Logic side
Weight
2.3 oz. (65 g)
Minimum ON Current
3.5 mA
Maximum OFF Current
1.5 mA
Base Power Required 5VDC
50 mA
OFF to ON Response
1 to 8 ms
ON to OFF Response
1 to 8 ms
Terminal Type (included)
Removable, D2-8IOCON
Status Indicator
Logic side
Weight
2.3 oz. (65 g)
See page 4-78 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.
See page 4-78 for part numbers of ZIPLink cables and connection modules compatible with this I/O module. Derating Chart
Points
Derating Chart
Points
8
16
6
12 8
4 2 0 10 20 30 40 50 55 °C 50 68 86 104 122131 °F Ambient Temperature (°C/°F )
0 32
12--24VDC - + Source Sink
+
-
Internally connected
C C
0 1 2 3 D2--08ND3
12--24 VDC 4 5 6 7
IN
4 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122131 ° F Ambient Temperature (°C/°F )
24 VDC
Source Sink
-
+
+
-
IN
CA
A 0 1 2 B 3 D2--16ND3--2
24 VDC 4 5 6 7
0 4
10.2- 26.4VDC 4- 12mA
20- 28VDC 8mA CLASS2
1 5
0
C
4
2
1
3
0
5 6
24 VDC
Source Sink
+
+
CB
1
1 6
3
2
3 7
7 Internal module circuitry
D2--08ND3
INP UT
0
5 2
6
V+
NC
4
2
Internal module circuitry
3
0
5
7
2
NC
-
1
3
1
7
4
2
0
6
C
3
CA 4 5 6 7 CB 4 5 6 7
V+
INP UT
To LE D To LE D
COM - + 12--24VDC
Source
Source
For “Sinking and Sourcing Concepts”, see the Appendix section.
+
-
Sink
+
-
+
-
COM Sink
Optical Is olator
COM
Optical Is olator
24 VDC
For “Sinking and Sourcing Concepts” see the Appendix section.
Volume 13 e4-84
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 2
Wiring Solutions
Wiring Solutions using the ZIPLink Wiring System
ZIPLinks eliminate the normally tedious process of wiring between devices by utilizing prewired cables and DIN rail mount connector modules. It's as simple as plugging in a cable connector at either end or terminating wires at only one end. Prewired cables keep installation clean and efficient, using half the space at a fraction of the cost of standard terminal blocks. There are several wiring solutions available when using the ZIPLink System ranging from PLC I/O-to-ZIPLink Connector Modules that are ready for field termination, options for connecting to third party devices, GS, DuraPulse and SureServo Drives, and specialty relay, transorb and communications modules. Pre-printed I/O-specific adhesive label strips for quick marking of ZIPLink modules are provided with ZIPLink cables. See the following solutions to help determine the best ZIPLink system for your application.
Solution 1: DirectLOGIC, CLICK and Productivity3000 I/O Modules to ZIPLink Connector Modules
When looking for quick and easy I/O-to-field termination, a ZIPLink connector module used in conjunction with a prewired ZIPLink cable, consisting of an I/O terminal block at one end and a multi-pin connector at the other end, is the best solution.
Solution 2: DirectLOGIC, CLICK and Productivity3000 I/O Modules to 3rd Party Devices
When wanting to connect I/O to another device within close proximity of the I/O modules, no extra terminal blocks are necessary when using the ZIPLink Pigtail Cables. ZIPLink Pigtail Cables are prewired to an I/O terminal block with color-coded pigtail with soldered-tip wires on the other end.
Solution 3: GS Series and DuraPulse Drives Communication Cables
Need to communicate via Modbus RTU to a drive or a network of drives? ZI PLink cables are available in a wide range of configurations for connecting to PLCs and SureServo, SureStep, Stellar Soft Starter and AC drives. Add a ZIPLink communications module to quickly and easily set up a multi-device network.
Using the PLC I/O Modules to ZIPLink Connector Modules selector tables located in this section, 1. Locate your I/O module/PLC. 2. Select a ZIPLink Module. 3. Select a corresponding ZIPLink Cable.
Using the I/O Modules to 3rd Party Devices selector tables located in this section, 1. Locate your PLC I/O module. 2. Select a ZIPLink Pigtail Cable that is compatible with your 3rd party device.
Using the Drives Communication selector tables located in this section, 1. Locate your Drive and type of communications. 2. Select a ZIPLink cable and other associated hardware.
Volume 13 e4-80
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 3
Wiring Solutions Solution 4: Serial Communications Cables
ZIPLink offers communications cables for use with DirectLOGIC, CLICK, and Productivity3000 CPUs, that can also be used with other communications devices. Connections include a 6-pin RJ12 or 9-pin, 15-pin and 25pin D-sub connectors which can be used in conjunction with the RJ12 or D-Sub Feedthrough modules.
Company Information Systems Overview
Using the Serial Communications Cables selector table located in this section, 1. Locate your connector type 2. Select a cable.
Programmable Controllers Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos
Solution 5: Specialty ZIPLink Modules
For additional application solutions, ZIPLink modules are available in a variety of configurations including stand-alone relays, 24VDC and 120VAC transorb modules, D-sub and RJ12 feedthrough modules, communication port adapter and distribution modules, and SureServo 50-pin I/O interface connection.
Motor Controls
Using the ZIPLink Specialty Module s selector table located in this section, 1. Locate the type of application. 2. Select a ZIPLink module.
Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process
Solution 6: ZIPLink Connector Modules to 3rd Party Devices
If you need a way to connect your device to terminal blocks without all that wiring time, then our pigtail cables with color-coded soldered-tip wires are a good solution. Used in conjunction with any compatible ZIPLink Connector Modules, a pigtail cable keeps wiring clean and easy and reduces troubleshooting time.
Relays/ Timers
Using the Unive rs al Conne ctor Modules and Pigtail Cables table located in this section, 1. Select module type. 2. Select the number of pins. 3. Select cable.
Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13 w w w. a u to m a t i o n d i re c t . c o m / d l 205
Programmable Controllers e4-81
Page 4
PLC I/O Modules to ZIPLink Connector Modules - DL205
DL205 PLC Input Module ZIPLink Selector ZIPLink PLC Input Module
# of Terms
D2-08ND3
10
D2-16ND3-2
19
Part Component Module No.
D2-32ND3¹
Output Module D2-04TD1² D2-08TD1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-08TD2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU205
ZL-D2-CBL19*
Relay
ZL-RRL16-24-1
ZL-D2-CBL19*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU20
ZL-D2-CBL19*
Relay
ZL-RRL16-24-2
ZL-D2-CBL19*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Relay
ZL-RRL16-24-1
ZL-D2-CBL19*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Relay
ZL-RRL16-24-2
ZL-D2-CBL19*
Feedthrough
ZL-RTB40
Fuse
ZL-RFU405
Feedthrough
ZL-RTB40
Fuse
ZL-RFU405
ZL-RTB20
ZL-D2-CBL10*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Sensor
ZL-LTB16-24
ZL-D2-CBL19*
ZL-RTB40
40 Sensor Feedthrough
D2-32ND3-2¹
Cable Part No. †
Feedthrough
Feedthrough
ZL-LTB32-24 ZL-RTB40
40 Sensor
ZL-LTB32-24
ZL-D24-CBL40*X ZL-D24-CBL40*X ZL-D24-CBL40* ZL-D24-CBL40* ZL-D2-CBL10*
D2-08NA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-12NA
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
† X in the part number represents a 45° angle.
DL205 PLC Combo In/Out Module ZIPLink Selector ZIPLink PLC
Feedthrough
Module Part Cable Part No. No. ZL-RTB20
ZL-D2-CBL10*
DL205 PLC Analog Module ZIPLink Selector ZIPLink PLC Analog Module
# of Terms Component
Module
Cable
F2-04AD-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-04AD-1L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08AD-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-04AD-2
10
Feedthrough
ZL-RTB20
F2-04AD-2L
10
Feedthrough
ZL-RTB20
D2-16TD2-2
19
F2-16TD1P
19
ZL-D24-CBL40*X
ZL-RTB20
10
19
ZL-D24-CBL40*X
Feedthrough
D2-08CDR
D2-16TD1-2
ZL-D24-CBL40*
10
# of Terms Component
# of Terms Component
ZL-D24-CBL40*
D2-08NA-1
Combo Module
DL205 PLC Output Module ZIPLink Selector ZIPLink PLC
ZL-D2-CBL10*
F2-16TD2P
D2-32TD1¹
D2-32TD2¹
19
Module Part Cable Part No. No. †
40
40
ZL-D24-CBL40* ZL-D24-CBL40*X ZL-D24-CBL40* ZL-D24-CBL40*X ZL-D24-CBL40* ZL-D24-CBL40*X ZL-D24-CBL40* ZL-D24-CBL40*X
D2-08TA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08TA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU205
ZL-D2-CBL19*
D2-12TA
19
D2-04TRS³ D2-08TR F2-08TRS³
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-08TR4
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU205
ZL-D2-CBL19*
D2-12TR
ZL-D2-CBL10*
19
F2-08AD-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
† X in the part number represents a 45° angle plug
F2-02DA-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-02DA-1L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
* Select the cable length by replacing the * with: Blank = 0.5m, -1 = 1.0m, or -2 = 2.0m.
F2-02DAS-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
1 To make a custom cable for the 32-point modules, use: Ribbon-style Connector
F2-08DA-1
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-02DA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
ZL-D24-CON-R, Solder-style 180° connector ZL-D24-CON or Solder-style 45° connector ZL-D24-CON-X
F2-02DA-2L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-02DAS-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08DA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-4AD2DA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-8AD4DA-1
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-8AD4DA-2
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-04RTD4
Matched Only
See Note 4
F2-04THM4
Matched Only
See Note 4
2 Caution: The D2-04TD1, D2-04TRS, and F2-08TRS outputs are derated not to exceed module specs 2A per point and 2A per common when used with the ZIPLink wiring system. 3 The F2-08TR outputs are derated not to exceed 2A per point and 4A per common when used with the ZIPLink wiring system. 4 The F2-04RTD and F2-04THM modules are not supported by the ZIPLink wiring system. 5 Note: Fuses (5 x 20 mm) are not included. See Edison Electronic Fuse section for (5 x 20 mm) fuse. S500 and GMA electronic circuit protection for fast-acting maximum protection. S506 and GMC electronic circuit protection for time-delay performance. Ideal for inductive circuits. To ensure proper operation, do not exceed the voltage and current rating of ZIPLink module. ZL-RFU20 = 2A per circuit; ZL-RFU40 = 400 mA per circuit.
NOTE: ZIPLINK CONNECTOR MODULES SPECIFICATIONS FOLLOW THE COMPATIBILITY MATRIX TABLES. ZIPLINK CABLES SPECIFICATIONS ARE AT THE END OF THIS ZIPLINK SECTION. Volume 13 e4-82
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 5
Power Requirements These charts help determine your power requirements
This section shows the amount of power supplied by each of the base power supplies and the amount of power consumed by each DL205 device. The Power Consumed charts list how much INTERNAL power from each power source is required for the DL205 devices. Use this information when calculating the power budget for your system. In addition to the internal power sources, the DL205 bases offer a 24 VDC auxiliary power supply with external power connections. This auxiliary power supply can power external devices.
Use ZIPLinks to reduce power requirements
If your application requires a lot of relay outputs, consider using the ZIPLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to the Terminal Blocks and Wiring Solutions section in this catalog for more information. This logo is placed next to the I/O modules that are supported by the ZIPLink connection systems. See the I/O module specifications at the end of this section.
Device D2-03B-1
Operator Interface DV-1000
150
C-more MicroGraphic
210
0 0
5V(mA) 24V Auxiliary
Bases 300
D2-06BDC1-1
<--->
2600
None
D2-03BDC1-1 <--->
2600
None
D2-06BDC2-1
<--->
2600
300
D2-04B-1
<--->
2600
300
D2-09B-1
<--->
2600
300
D2-04BDC1-1 <--->
2600
None
D2-09BDC1-1
<--->
2600
None
D2-06B-1
2600
300
D2-09BDC2-1
<--->
2600
300
<--->
Power Consumed
Power Consumed Device
5V(mA)
24V Auxiliary
Device
5V(mA)
24V Auxiliary
Analog Modules
CPUs D2-230
120
0
F2-04AD-1
100
5
D2-240
120
0
F2-04AD-2
110
5
D2-250-1
330
0
F2-08AD-1
100
5
D2-260
330
0
F2-08AD-2
100
5
H2-WPLC*-**
680
0
F2-02DA-1
40
60 (note 1)
F2-02DA-1L
40
70 @ 12V (note 1)
0
F2-02DA-2
40
60
40
70 @ 12V
DC Input Modules D2-08ND3
50
D2-16ND3-2
100
0
F2-02DA-2L
D2-32ND3
25
0
D2-32ND3-2
25
0
F2-02DAS-1 F2-02DAS-2
100 100
50 / channel 60 / channel
F2-08DA-1
30
50 (note 1)
F2-08DA-2
60
140
F2-4AD2DA
60
80 (note 1)
F2-8AD4DA-1
35
100 (note 1)
F2-8AD4DA-2
35
80 (note 1)
F2-04RTD
90
0
F2-04THM
110
60
AC Input Modules D2-08NA-1 D2-08NA-2 D2-16NA
50 100 100
0 0 0
Input Simulator Module F2-08SIM
50
0
DC Output Modules D2-04TD1
60
20
D2-08TD1
100
0
D2-08TD2
100
0
200 200
80 0
F2-16TD1P
70
50
F2-16TD2P
70
50
D2-32TD2
24V Auxiliary
Price
2600
D2-32TD1
5V(mA)
Device
<--->
D2-16TD2-2
Device
Power Supplied
Price 5V(mA) 24V Auxiliary
Bases
D2-16TD1-2
Power Consumed
HERE
350 350
0 0
AC Output Modules D2-08TA
250
0
F2-08TA
250
0
D2-12TA
350
0
Relay Output Modules D2-04TRS
250
0
D2-08TR
250
0
F2-08TR(S)
670
0
D2-12TR
450
0
200
D2-CTRINT
50*
0
D2-CM / D2-EM
100/130
0
H2-CTRIO
400
0
D2-DCM
300
0
F2-DEVNETS
160
0
F2-SDS-1
160
0
H2-PBC
530
0
H2-EBC(-F)
450, (640)
0
H2-ECOM(-F)
450, (640)
0
H2-ECOM100
300
0
F2-CP128
235
0
H2-ERM(-F)
320, (450)
0
D2-RMSM
200
0
D2-RSSS
150
0
Remote I/O
Programming Devices D2-HPP
200
0
*requires external 5VDC for outputs Note 1: Add an additional 20 mA per output loop.
Combination In/Out Module D2-08CDR
Specialty Modules
0
Volume 13 e4-46
Programmable Controllers
1 - 80 0 - 633 - 0405