Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of DC Input Modules: D2-08ND3 DC Input, D2-16ND3-2 DC Input

Spec sheet · Koyo

DC Input Modules: D2-08ND3 DC Input, D2-16ND3-2 DC Input

Spec sheet5 pagesPDF 1.2 MB

Catalog spec pages for the DL205 D2-08ND3 and D2-16ND3-2 DC input modules, with ZIPLink wiring options and DL205 power budgets.

Download the PDF1.2 MB

Covers · 2 models

The models it covers

Summary

What is in it

Five catalog pages for DL205 PLC DC input modules. The first page gives specifications, derating charts and wiring diagrams for the D2-08ND3 (8 sink/source inputs, 10.2-26.4 VDC) and the D2-16ND3-2. The other pages describe ZIPLink wiring solutions, a selector table matching DL205 input, output, combo and analog modules to ZIPLink connector modules and cables, and power requirement charts listing the power supplied by DL205 bases and consumed by each DL205 device.

Its parts

  1. DC Input Modules
  2. Wiring Solutions
  3. PLC I/O Modules to ZIPLink Connector Modules DL205
  4. Power Requirements

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Five catalog pages on DL205 DC input modules: a specification page for the D2-08ND3 and D2-16ND3-2 with wiring diagrams, an overview of ZIPLink wiring solutions, the DL205 ZIPLink selector tables, and the DL205 power supplied and consumed charts. It helps check the D2-08ND3 ratings, plan its field wiring and work out a base power budget.

Type
D2-08ND3: DC input module for the DL205 p. 1, 5
Inputs
D2-08ND3: 8 (sink/source) p. 1
Commons
D2-08ND3: 1 (2 I/O terminal points) p. 1
Input voltage
D2-08ND3: 10.2-26.4 VDC; peak 26.4 VDC p. 1
ON/OFF levels
D2-08ND3: ON 9.5 VDC minimum; OFF 3.5 VDC maximum p. 1
Input current
D2-08ND3: 4.0 mA @ 12 VDC; 8.5 mA @ 24 VDC p. 1
Input impedance
D2-08ND3: 2.7 k p. 1
ON/OFF current
Minimum ON 3.5 mA; maximum OFF 1.5 mA p. 1
Base power
D2-08ND3: 50 mA from the 5V supply p. 5
Status indicator
Logic side p. 1
Weight
2.3 oz. (65 g) p. 1

What this sheet walks you through

  • Wiring diagram and internal input circuit p. 1
  • Choosing a ZIPLink wiring solution for PLC I/O p. 2, 3
  • Selecting ZIPLink modules and cables for DL205 I/O modules p. 4
  • Working out a DL205 base power budget p. 5

Good to know

  • Do not exceed the voltage and current rating of a ZIPLink module. p. 4
  • ZIPLink fuses (5 x 20 mm) are not included. p. 4

Questions this sheet answers

What input voltage does the D2-08ND3 accept?

10.2-26.4 VDC, with a peak of 26.4 VDC; inputs turn ON at 9.5 VDC minimum. p. 1

How many inputs does the D2-08ND3 have?

8 sink/source inputs with one common (2 I/O terminal points). p. 1

How much base power does the D2-08ND3 draw?

50 mA from the 5V base supply, per the DL205 Power Consumed chart. p. 5

Which PLC family is the D2-08ND3 for?

The DL205; it is listed among the DC input modules in the DL205 power consumed chart. p. 5

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. DC Input Modules1
  2. Wiring Solutions2
  3. PLC I/O Modules to ZIPLink Connector Modules DL2054
  4. Power Requirements5

From the PDF’s own bookmarks.

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 51-5

The file

Revision and size

RevisionVolume 13
PublisherAutomationDirect
Pages5
PDF1.2 MB
TextText from the PDF itself.

The first pages · 4 of 5

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 5
Page 2
Page 2of 5
Page 3
Page 3of 5
Page 4
Page 4of 5

More documents · 1

For the same models