Chapter 3: CPU Specifications and Operations
DL230 System V-memory System V-memory
Description of Contents
V2320–V2377
The default location for multiple preset values for the UP counter.
V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625
Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value. Sets the V-memory location that contains the message. Sets the total number (1 - 16) of V-memory locations to be displayed. Sets the V-memory location that contains the numbers to be displayed. Sets the V-memory location that contains the character code to be displayed. Sets the bit control pointer.
V7626 V7627 V7630
V7631–V7632 V7633
Power Up mode change preset value password. Reservered for future use. Starting location for the multi–step presets for channel 1. The default value is 2320, which indicates the first value should be obtained from V2320. Since there are 24 presets available, the default range is V2320 – V2377. You can change the starting point if necessary. Not used Sets the desired mode for the high speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT Manual, D2-CTRIF-M for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change, and power-up in Run Mode option.
Default Values/Ranges N/A V0 – V2377 V0 - V2377 1 - 16 V0 - V2377 V0 - V2377 V-memory location for X,Y, or C points used. 0,1,2,3,12 Default = 0000 Default: V2320 Range: V0 – V2320 N/A Default: 0000 Lower Byte Range: Range: 0 – None 10 – Up 40 – Interrupt 50 – Pulse Catch 60 – Filtered discrete In. Upper Byte Range: Bits 8 – 11, 14,15: Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run
V7637
Contains set up information for high speed counter, interrupt, pulse catch, pulse Default: 0000 train output, and input filter for X0 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse Default: 0000 train output, and input filter for X1 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse Default: 0000 train output, and input filter for X2 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse Default: 0000 train output, and input filter for X3 (when D2–CTRINT is installed).
V7640–V7642 V7640 V7641 V7642
Additional setup parameters for the DV-1000 Timer preset value pointer Counter preset value pointer Timer preset block size (high byte) / Counter preset block size (low byte)
V7643–V7647
Not used Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed.
V7634 V7635 V7636
V7751
V2000 - V2377 V2000 - V2377 1 - 99 N/A N/A
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–41
Page 136
Chapter 3: CPU Specifications and Operations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
System V-memory V7752 V7753 V7754 V7755 V7756 V7757 V7760–V7764 V7765 V7666–V7774 V7775 V7776 V7777
3–42
Description of Contents I/O Configuration Error, stores the module ID code for the module that does not match the current configuration. I/O Configuration Error, stores the correct module ID code. I/O Configuration Error, identifies the base and slot number. Error code, stores the fatal error code. Error code, stores the major error code. Error code, stores the minor error code. Module Error, stores the slot number and error code where an I/O error occurs. Scan, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition. Not used Scan, stores the current scan time (milliseconds). Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds). Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds).
DL205 User Manual, 4th Edition, Rev. A
Default Values/Ranges N/A N/A
N/A
N/A N/A N/A N/A
Page 137
Chapter 3: CPU Specifications and Operations
DL240 System V-memory System V-memory
Default Values/Ranges
Description of Contents default location for multiple preset values for UP/DWN and UP counter 1 or pulse N/A V3630–V3707 The output function. V3710–V3767 The default location for multiple preset values for UP/DWN and UP counter 2. V3770–V3773 Not used V3774–V3777 Default locations for analog potentiometer data (channels 1–4, respectively).
N/A N/A Range: 0 – 9999
V7620–V7627 Locations for DV–1000 operator interface parameters V7620 Sets the V-memory location that contains the value. V7621 Sets the V-memory location that contains the message. V7622 Sets the total number (1 – 16) of V-memory locations to be displayed. V7623 Sets the V-memory location that contains the numbers to be displayed. V7624 Sets the V-memory location that contains the character code to be displayed. V7625 Sets the bit control pointer V7626 Power Up Mode V7627 Change Preset Value Password.
V0 – V3760 V0 – V3760 1 – 16 V0 – V3760 V0 – V3760 V-memory location for X, Y, or C points used. 0,1,2,3,12 Default=0000
V7630 V7631
V7632
Starting location for the multi–step presets for channel 1. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary. Starting location for the multi–step presets for channel 2. Since there are 24 presets available, the default range is V3710– V3767. You can change the starting point if necessary.
Contains the baud rate setting for Port 2. You can use AUX 56 (from the Handheld Programmer) or, use DirectSOFT to set the port parameters if 9600 baud is unacceptable. Also allows you to set a delay time between the assertion of the RTS signal and the transmission of data. This is useful for radio modems that require a key-up delay before data is transmitted. e.g. a value of 0302 sets 10ms Turnaround Delay (TAD) and 9600 baud.
Default: V3630 Range: V0 – V3710 Default: V3710 Range: V0 – V3710 Default: 2 – 9600 baud Lower Byte = Baud Rate Lower Byte Range: 00 = 300 01 = 1200 02 = 9600 03 = 19.2K Upper Byte = Time Delay Upper Byte Range: 01 = 2ms 02 = 5ms 03 = 10ms 04 = 20ms 05 = 50ms 06 = 100ms 07 = 500ms
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–43
Page 138
Chapter 3: CPU Specifications and Operations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
System V-memory
Description of Contents
V7633
Sets the desired mode for the high speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT manual, D2-CTRIF-M, for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change
V7634
Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X0 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X1 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X2 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X3 (when D2–CTRINT is installed).
V7635 V7636 V7637
Default Values/Ranges Default: 0000 Lower Byte Range: 0 – None 10 – Up 20 – Up/Dwn. 30 – Pulse Out 40 – Interrupt 50 – Pulse Catch 60 – Filtered Dis. Upper Byte Range: Bits 8 – 11, 15 Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run Bit 14: Mode chg. enable (K-sequence only) Default: 0000 Default: 0000 Default: 0000 Default: 0000
Default: 0000 Range: 0 – 9999 Default: 0000 V7642–V7643 Location for setting the lower and upper limits for the CH2 analog pot. Range: 0 – 9999 Default: 0000 V7644–V7645 Location for setting the lower and upper limits for the CH3 analog pot. Range: 0 – 9999 Default: 0000 V7646–V7647 Location for setting the lower and upper limits for the CH4 analog pot. Range: 0 – 9999 V7650–V7737 Locations reserved for setup information used with future options (remote I/O and data communications) V7720–V7722 Locations for DV–1000 operator interface parameters. V2000–V2377 V7720 Titled Timer preset value pointer V7721 Titled Counter preset value pointer V2000–V2377 V7722 HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size 1–99 V7746 Location contains the battery voltage, accurate to 0.1V. For example, a value of 32 indicates 3.2 volts V7747 Location contains a 10ms counter. This location increments once every 10ms.. Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed. If you’ve used ASCII messages (DL240 only) then the data label (DLBL) reference number for that V7751 message is stored here. V7752 I/O configuration Error, stores the module ID code for the module that does not match the current config. V7640–V7641 Location for setting the lower and upper limits for the CH1 analog pot.
3–44
DL205 User Manual, 4th Edition, Rev. A
Page 139
Chapter 3: CPU Specifications and Operations System V-memory
Description of Contents
V7753 I/O Configuration Error, stores the correct module ID code. V7754 I/O Configuration Error, identifies the base and slot number. V7755 Error code, stores the fatal error code. V7756 Error code, stores the major error code. V7757 Error code, stores the minor error code. V7760–V7764 Module Error, stores the slot number and error code where an I/O error occurs. V7765 Scan - stores the number of scan cycles that have occurred since the last Program to Run Mode transition. V7766 Contains the number of seconds on the clock. (00 to 59). V7767 Contains the number of minutes on the clock. (00 to 59). V7770 Contains the number of hours on the clock. (00 to 23). V7771 Contains the day of the week. (Mon, Tue, etc.). V7772 Contains the day of the month (1st, 2nd, etc.). V7773 Contains the month. (01 to 12) V7774 Contains the year. (00 to 99) V7775 Scan, stores the current scan time (milliseconds). Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition V7776 (milliseconds). Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition V7777 (milliseconds).
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–45
Page 140
Chapter 3: CPU Specifications and Operations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DL250–1 System V-memory (DL250 also) System V-memory
Default Values/Ranges
Description of Contents
V3710–V3767 V3770–V3777
The default location for multiple preset values for UP/DWN and UP counter 1 or pulse N/A output function The default location for multiple preset values for UP/DWN and UP counter 2. N/A Not used N/A
V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625 V7626 V7627
Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value Sets the V-memory location that contains the message Sets the total number (1 – 32) of V-memory locations to be displayed Sets the V-memory location that contains the numbers to be displayed Sets the V-memory location that contains the character code to be displayed Sets the bit control pointer Sets the power up mode Change Preset Value password
V3630–V3707
V7630 V7631 V7632 V7633
V7634 V7635 V7636
3–46
V0 – V3760 V0 – V3760 1 – 32 V0 – V3760 V0 – V3760 V-memory for X, Y, or C 0,1,2,3,12 Default=0000
Starting location for the multi–step presets for channel 1. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary. Starting location for the multi–step presets for channel 2. Since there are 24 presets available, the default range is V3710– V3767. You can change the starting point if necessary. Reserved Sets the desired mode for the high speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT manual, D2-CTRIF-M, for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change, and power-up in Run Mode option.
Default: V3630 Range: V0 – V3710
Contains set up information for high speed counter, interrupt, pulse catch,pulse train output, and input filter for X0 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X1 (when D2–CTRINT is installed). Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X2 (when D2–CTRINT is installed).
Default: 1006
DL205 User Manual, 4th Edition, Rev. A
Default: V3710 Range: V0 – V3710 Default: 0060 Lower Byte Range: Range: 0 – None 10 – Up 20 – Up/Dwn. 30 – Pulse Out 40 – Interrupt 50 – Pulse Catch 60 – Filtered Dis. Upper Byte Range: Bits 8 – 11, 14–15 Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run
Default: 1006 Default: 1006
Page 141
Chapter 3: CPU Specifications and Operations
System V-memory
Description of Contents
Default Values/Ranges
V7637
Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X3 (when D2–CTRINT is installed).
Default: 1006
V7640
Loop Table Beginning address
V7641 V7642 V7643–V7647 V7650 V7651 V7652 V7653 V7654 V7655 V7656 V7657 V7660–V7717
V1400–V7340 V10000–V17740 1–4
Number of Loops Enabled Error Code – V–memory Error Location for Loop Table Reserved Port 2 End–code setting Setting (A55A), Non–procedure communications start. Port 2 Data format –Non–procedure communications format setting. Port 2 Format Type setting – Non–procedure communications type code setting. Port 2 Terminate–code setting – Non–procedure communications Termination code setting. Port 2 Store v–mem address – Non–procedure communication data store V–Memory address Port 2 Setup area –0–7 Comm protocol (flag 0) 8–15 Comm time out/response delay time (flag 1) Port 2 Setup area – 0–15 Communication (flag 2, flag 3) Port 2: Setup completion code Set–up Information – Locations reserved for set up information used with future options. Locations for DV–1000 operator interface parameters. Titled Timer preset value pointer Title Counter preset value pointer HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size Port 2 Communication Auto Reset Timer setup Output Hold or reset setting: Expansion bases 1 and 2 (DL250–1) Location contains a 10ms counter. This location increments once every 10ms. Reserved
V7720–V7722 V7720 V7721 V7722 V7740 V7741 V7747 V7750 V7751 V7752 V7753 V7754 V7755 V7756 V7757 V7760–V7764 V7765
Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed. If you’ve used ASCII messages (DL240 only), then the data label (DLBL) reference number for that message is stored here. I/O configuration Error, stores the module ID code for the module that does not match the current configuration. I/O Configuration Error, stores the correct module ID code. I/O Configuration Error, identifies the base and slot number. Error code, stores the fatal error code. Error code, stores the major error code. Error code, stores the minor error code. Module Error, stores the slot number and error code where an I/O error occurs. Scan, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–47
Page 142
Chapter 3: CPU Specifications and Operations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
System V-memory V7766 V7767 V7770 V7771 V7772 V7773 V7774 V7775 V7776 V7777 V36000–36057 V36100–36157 V36400–36427 V37700–37737
Description of Contents Contains the number of seconds on the clock. (00 to 59) Contains the number of minutes on the clock. (00 to 59) Contains the number of hours on the clock. (00 to 23) Contains the day of the week. (Mon, Tue, etc.) Contains the day of the month (1st, 2nd, etc.) Contains the month. (01 to 12) Contains the year. (00 to 99) Scan, stores the current scan time (milliseconds) Scan, stores the minimum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds) Scan, stores the maximum scan time that has occurred since the last Program Mode to Run Mode transition (milliseconds) Analog pointer method for expansion base 1 (DL250–1) Analog pointer method for expansion base 2 (DL250–1) Analog pointer method for local base Port 2: Setup register for Koyo Remote I/O
The following system control relays are used for Koyo Remote I/O setup on Communications Port 2. System CRs C740 C741 C743 C750 to C757 C760 to C767
3–48
Description of Contents Completion of setups – ladder logic must turn this relay on when it has finished writing to the Remote I/O setup table Erase received data – turning on this flag will erase the received data during a communication error Re-start – Turning on this relay will resume after a communications hang-up on an error. Setup Error – The corresponding relay will be ON if the setup table contains an error (C750 = master, C751 = slave 1 C757 = slave 7) Communications Ready – The corresponding relay will be ON if the setup table data is valid (C760 = master, C761 = slave 1 C767 = slave 7)
DL205 User Manual, 4th Edition, Rev. A
Page 143
Chapter 3: CPU Specifications and Operations
DL260 System V-memory System V-memory
Description of Contents
1 Default Values/Ranges 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
V3630–V3707
The default location for multiple preset values for UP/DWN and UP counter 1 or pulse output function
N/A
V3710–V3767
The default location for multiple preset values for UP/DWN and UP counter 2
N/A
V3770–V3777 V7620–V7627 V7620 V7621 V7622 V7623 V7624 V7625 V7626 V7627
Not used
N/A
Locations for DV–1000 operator interface parameters Sets the V-memory location that contains the value Sets the V-memory location that contains the message Sets the total number (1 – 32) of V-memory locations to be displayed Sets the V-memory location that contains the numbers to be displayed Sets the V-memory location that contains the character code to be displayed Sets the bit control pointer Sets the power up mode Change Preset Value password
V0 – V3760 V0 – V3760 1 – 32 V0 – V3760 V0 – V3760 V-memory for X, Y, or C 0,1,2,3,12 Default=0000
V7630
Starting location for the multi–step presets for channel 1. Since there are 24 presets available, the default range is V3630 – V3707. You can change the starting point if necessary.
Default: V3630 Range: V0 – V3710
V7631
Starting location for the multi–step presets for channel 2. Since there are 24 V3710 presets available, the default range is V3710– V3767. You can change the starting Default: Range: V0 – V3710 point if necessary.
V7632 V7633
Reserved Sets the desired mode for the high speed counter, interrupt, pulse catch, pulse train, and input filter (see the D2-CTRINT manual, D2-CTRIF-M, for more information). Location is also used for setting the with/without battery option, enable/disable CPU mode change, and power-up in Run Mode option.
V7634
Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X0 (when D2–CTRINT is installed) Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X1 (when D2–CTRINT is installed) Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X2 (when D2–CTRINT is installed)
V7635 V7636
Default: 0060 Lower Byte Range: Range: 0 – None 10 – Up 20 – Up/Dwn 30 – Pulse Ou 40 – Interrupt 50 – Pulse Catch 60 – Fltered Dis. Upper Byte Range Bits 8 – 11, 14–15 Unused Bit 12: With Batt. installed: 0 = disable BATT LED 1 = enable BATT LED Bit 13: Power-up in Run Default: 1006 Default: 1006 Default: 1006
DL205 User Manual, 4th Edition, Rev. A
3–49
Page 144
Chapter 3: CPU Specifications and Operations
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
System V-memory
Description of Contents
Default Values/Ranges
V7637
Contains set up information for high speed counter, interrupt, pulse catch, pulse train output, and input filter for X3 (when D2–CTRINT is installed).
Default: 1006
V7640
PID Loop Table Beginning address
V400–640 V1400–V7340 V10000–V35740
V7641 V7642 V7643 - V7647 V7650 V7651 V7652 V7653 V7654 V7655 V7656 V7657 V7660–V7717 V7720–V7722 V7720 V7721 V7722 V7740 V7741 V7742 V7747 V7750
Number of Loops Enabled 1–16 Error Code – V–memory Error Location for Loop Table Reserved Port 2 End–code Setting (A55A), Nonprocedure communications start. Port 2 Data format - Non-procedure communications format setting. Port 2 Format Type setting – Non–procedure communications type code setting. Port 2 Terminate–code setting – Non–procedure communications Termination code setting Port 2 Store v–mem address – Non–procedure communication data store V–Memory address. Port 2 Setup area –0–7 Comm protocol (flag 0) 8–15 Comm time out/response delay time (flag 1) Port 2 Setup area – 0–15 Communication (flag 2, flag 3) Port 2: Setup completion code Set–up Information – Locations reserved for set up information used with future options Locations for DV-1000 operator interface parameters. Titled Timer preset value pointer Title Counter preset value pointer HiByte-Titled Timer preset block size, LoByte-Titled Counter preset block size Port 2 Communication Auto Reset Timer setup Output Hold or reset setting: Expansion bases 1 and 2 Output Hold or reset setting: Expansion bases 3 and 4 Location contains a 10ms counter. This location increments once every 10ms. Reserved
V7751 V7752 V7753 V7754 V7755 V7756 V7757 V7763–V7764 V7765
3–50
Fault Message Error Code, stores the 4-digit code used with the FAULT instruction when the instruction is executed. If you’ve used ASCII messages (DL240 only) then the data label (DLBL) reference number for that message is stored here. I/O configuration Error, stores the module ID code for the module that does not match the current configuration. I/O Configuration Error, stores the correct module ID code. I/O Configuration Error, identifies the base and slot number. Error code, stores the fatal error code. Error code, stores the major error code. Error code, stores the minor error code. Module Error, stores the slot number and error code where an I/O error occurs. Scan, stores the total number of scan cycles that have occurred since the last Program Mode to Run Mode transition.