Page 233
Chapter 5: Standard RLL Instructions - Boolean
Store Bit-of-Word (STRB)
1 2 3 4 location. 5 Operand Data Type DL250-1 Range DL260 Range A aaa bb aaa bb 6 7 In the following Store Bit-of-Word example, when bit 12 of V-memory location V1400 is on, 8 output Y2 will energize. 9 10 11 12 13 In the following Store Not Bit-of-Word example, when bit 12 of V-memory location V1400 14 is off, output Y2 will energize. A B C D
The Store Bit-of-Word instruction begins a new rung 230 or an additional branch in a rung with a normally open 240 contact. Status of the contact will be the same state as 250-1 the bit referenced in the associated memory location. 260
Store Not Bit-of-Word (STRNB) The Store Not instruction begins a new rung or an 230 additional branch in a rung with a normally closed 240
250-1 contact. Status of the contact will be opposite the state of the bit referenced in the associated memory 260
DS HPP
Used Used
Aaaa.bb
Aaaa.bb
V-memory memory map BCD, 0 to 15 See memory map BCD, 0 to 15 B See page 3-55 page 3-56
Pointer memory map BCD, 0 to 15 See memory map BCD, 0 to 15 PB See page 3-55 page 3-56
DirectSOFT
B1400.12
Y2
OUT
Handheld Programmer Keystrokes STR
SHFT
B
K
1
2
2
ENT
OUT
V
1
4
0
0
4
0
0
ENT
DirectSOFT
B1400.12
Y2
OUT
Handheld Programmer Keystrokes STRN
OUT
SHFT
B
V
K
1
2
2
ENT
1
ENT
DL205 User Manual, 4th Edition, Rev. A
5–11
Page 234
Chapter 5: Standard RLL Instructions - Boolean
Or (OR)
The Or instruction logically ors a normally open 1 contact in parallel with another contact in a rung. The
Aaaa status of the contact will be the same state as the 2 associated image register point or memory location.
(ORN) 3 Or Not The Or Not instruction logically ors a normally closed contact in parallel with another contact in a rung. The Aaaa status of the contact will be opposite the state of the 4 associated image register point or memory location.
5 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range aaa aaa aaa aaa 6 7 8 9 10 In the following Or example, when input X1 or X2 is on, output Y5 will energize. 11 12 13 14 In the following Or Not example, when input X1 is on or X2 is off, output Y5 will energize. A B C D 230 240
250-1 260
230 240
250-1 260
A X Y C S T CT SP GX GY
Inputs Outputs Control Relays Stage Timer Counter Special Relay Global Global
DS Implied HPP Used
0-177 0-177 0–377 0–377 0–77 0–77 0-117, 540-577 -
0-477 0-477 0–377 0–777 0–177 0–177 0-137, 540-617 -
DirectSOFT X1
0-777 0-777 0–1777 0–1777 0–377 0–177 0-137, 540-717 -
Handheld Programmer Keystrokes
Y5
$
B
STR
OUT
Q
C
GX OUT
DirectSOFT
5–12
DL205 User Manual, 4th Edition, Rev. A
2
F
5
ENT ENT ENT
Handheld Programmer Keystrokes
Y5
OUT
X2
1
OR
X2
X1
0-1777 0-1777 0–3777 0–1777 0–377 0–377 0-137, 540-717 0-3777 0-3777
$
B
STR
1
R ORN
C
GX OUT
F
2
5
ENT ENT ENT
Page 235
Chapter 5: Standard RLL Instructions - Boolean
Or Bit-of-Word (ORB)
240 250-1 260 230
230 240 250-1 260
1 2 3 Or Not Bit-of-Word (ORNB) The Or Not Bit-of-Word instruction logically ors a 4 normally closed Bit-of-Word contact in parallel with another contact in a rung. Status of the contact will be opposite the state of the bit referenced in the associated 5 memory location. Operand Data Type DL250-1 Range DL260 Range 6 aaa bb bb 7 8 In the following Or Bit-of-Word example, when input X1 or bit 7 of V1400 is on, output Y7 will energize. 9 10 11 12 13 In the following Or Not Bit-of-Word example, when input X1 is on or bit 7 of V1400 is off, 14 output Y7 will energize. A B C D The Or Bit-of-Word instruction logically ors a normally open Bit-of-Word contact in parallel with another contact in a rung. Status of the contact will be the same state as the bit referenced in the associated memory location.
Aaaa.bb
Aaaa.bb
A
DS
Implied
HPP
Used aaa
V-memory memory map BCD, 0 to 15 See memory map BCD, 0 to 15 B See page 3-55 page 3-56
Pointer memory map BCD, 0 to 15 See memory map BCD, 0 to 15 PB See page 3-55 page 3-56
X1
Y7
OUT
B1400.7
Handheld Programmer Keystrokes STR OR
1
ENT
SHFT
B
K
7
ENT
7
ENT
OUT
V
1
4
V
1
4
0
0
DirectSOFT
X1
Y7
OUT
B1400.7
Handheld Programmer Keystrokes STR
ORN
OUT
1
ENT
SHFT
B
K
7
ENT
7
ENT
0
DL205 User Manual, 4th Edition, Rev. A
0
5–13
Page 236
Chapter 5: Standard RLL Instructions - Boolean
And (AND)
The And instruction logically ands a normally open 1 contact in series with another contact in a rung. The status of the contact will be the same state as the 2 associated image register point or memory location.
And Not (ANDN) 3 The And Not instruction logically ands a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of 4 the associated image register point or memory location.
5 Operand Data Type DL230 Range DL240 Range DL250-1 DL260 Range aaa aaa aaa aaa 6 7 8 9 10 In the following And example, when input X1 and X2 are on output Y5 will energize. 11 12 13 14 In the following And Not example, when input X1 is on and X2 is off output Y5 will energize. A B C D Aaaa
230 240
250-1 260
Aaaa
230 240
250-1 260
A X Y C S T CT SP GX GY
Inputs Outputs Control Relays Stage Timer Counter Special Relay Global Global
DS Implied HPP Used
0–177 0–177 0–377 0–377 0–77 0–77 0-117, 540-577 -
0–477 0–477 0–377 0–777 0–177 0–177 0-137, 540-617 -
DirectSOFT X1
X2
Y5
DirectSOFT
$
B
STR
1
V AND
C
GX OUT
F
2
5
ENT ENT ENT
Handheld Programmer Keystrokes
X2
Y5
OUT
5–14
0–1777 0–1777 0–3777 0–1777 0–377 0–377 0-137, 540-717 0-3777 0-3777
Handheld Programmer Keystrokes
OUT
X1
0–777 0–777 0–1777 0–1777 0–377 0–177 0-137, 540-717 -
DL205 User Manual, 4th Edition, Rev. A
$
B
1
STR
W ANDN
C
GX OUT
F
2
5
ENT ENT ENT
Page 237
Chapter 5: Standard RLL Instructions - Boolean
AND Bit-of-Word (ANDB) The And Bit-of-Word instruction logically ands a 230 normally open contact in series with another contact in 240 a rung. The status of the contact will be the same state 250-1 as the bit referenced in the associated memory location. 260
And Not Bit-of-Word (ANDNB) The And Not Bit-of-Word instruction logically ands a 230 normally closed contact in series with another contact in 240 a rung. The status of the contact will be opposite the 250-1 state of the bit referenced in the associated memory 260 location. Operand Data Type
Aaaa.bb
Aaaa.bb
DL250-1 Range
DL260 Range aaa bb aaa bb
V-memory memory map B See page 3-55
BCD, 0 to 15
BCD, 0 to 15
Pointer memory map PB See page 3-55
BCD
See memory map page 3-56 See memory map page 3-56
A
BCD
In the following And Bit-of-Word example, when input X1 and bit 4 of V1400 is on output DS Implied HPP Used
DirectSOFT X1
B1400.4
Y5 OUT
Handheld Programmer Keystrokes STR
1
AND
ENT
SHFT
B
K
4
ENT
5
ENT
OUT
V
1
4
0
0
Y5 will energize. In the following And Not Bit-of-Word example, when input X1 is on and bit 4 of V1400 is off output Y5 will energize. DirectSOFT X1
Y5
B1400.4
OUT
Handheld Programmer Keystrokes STR ANDN
OUT
1
ENT
SHFT
B
K
4
ENT
V
5
ENT
1
4
0
0
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–15
Page 238
Chapter 5: Standard RLL Instructions - Boolean
And Store (ANDSTR)
OUT The And Store instruction logically ands two 1 branches of a rung in series. Both branches must 1 2 begin with the Store instruction. 2
In the following And Store example, the branch consisting of contacts X2, X3, and X4 have 3 been anded with the branch consisting of contact X1. 4 5 6 7 8 9 (ORSTR) 1 10 Or Store The Or Store instruction logically ors two branches OUT of a rung in parallel. Both branches must begin with the Store instruction. 2 11
12 In the following Or Store example, the branch consisting of X1 and X2 have been ored with the branch consisting of X3 and X4. 13 14 A B C D 230 240
250-1 260
DS Implied HPP Used
DirectSOFT X1
Handheld Programmer Keystrokes
X2
X3
Y5
$
B
STR
OUT
1
$
C
STR
X4
2
V AND
D
Q
E
3 4
OR
L ANDST
ENT ENT ENT ENT
ENT
GX OUT
F
5
ENT
230 240
250-1 260
DS Implied HPP Used
DirectSOFT X1
Handheld Programmer Keystrokes
X2
Y5
$
X3
X4
B
STR
OUT
1
V AND
C
$
D
2
3
STR
V AND
M ORST GX OUT
5–16
DL205 User Manual, 4th Edition, Rev. A
E
4
ENT ENT ENT ENT
ENT
F
5
ENT
Page 239
Chapter 5: Standard RLL - Boolean
Out (OUT)
230 240 250-1 260
The Out instruction reflects the status of the rung (on/off ) and outputs the discrete (on/off ) state to the specified image register point or memory Aaaa location. Multiple Out instructions referencing the OUT same discrete location should not be used since only the last Out instruction in the program will control the physical output point. Instead, use the next instruction, the Or Out. Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range
Inputs Outputs Control Relays Global Global
A aaa aaa aaa aaa
X Y C GX GY
0–177 0–177 0–377 -
0–477 0–477 0–377 -
0–777 0–777 0–1777 -
0–1777 0–1777 0–3777 0–3777 0–3777
In the following Out example, when input X1 is on, output Y2 and Y5 will energize. DS HPP
Used Used
DirectSOFT
Handheld Programmer Keystrokes
X1
Y2 OUT Y5 OUT
$
B STR
1
GX OUT
C
GX OUT
F
2 5
ENT ENT ENT
In the following Out example the program contains two Out instructions using the same location (Y10). The physical output of Y10 is ultimately controlled by the last rung of logic referencing Y10. X1 will override the Y10 output being controlled by X0. To avoid this situation, multiple outputs using the same location should not be used in programming. If you need to have an output controlled by multiple inputs see the OROUT instruction on page 5–19. X0
Y10 OUT
X1
Y10 OUT
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–17
Page 240
Chapter 5: Standard RLL Instructions - Boolean
1 2
3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Out Bit-of-Word (OUTB) 230 240 250-1 260
DS HPP
5–18
The Out Bit-of-Word instruction reflects the status of the rung (on/off ) and outputs the discrete (on/off ) state to the specified bit in the referenced memory location. Multiple Out Bit-of-Word instructions referencing the same bit of the same word generally should not be used since only the last Out instruction in the program will control the status of the bit. Operand Data Type
Aaaa.bb OUT
DL250-1 Range A aaa memory map B See page 3-55 memory map PB See page 3-55
V-memory Pointer
DL260 Range bb aaa bb
BCD, 0 to 15
See memory map page 3-56 See memory map page 3-56
BCD, 0 to 15
BCD
BCD
In the following Out Bit-of-Word example, when input X1 is on, bit 3 of V1400 and bit 6 of V1401 will turn on. Used Used
DirectSOFT X1
B1400.3 OUT B1401.6
Handheld Programmer Keystrokes OUT STR OUT
OUT
1 SHFT
B
K
3
SHFT
B
K
6
ENT V
1
4
0
0
V
1
4
0
1
ENT
ENT
The following Out Bit-of-Word example contains two Out Bit-of-Word instructions using the same bit in the same memory word. The final state bit 3 of V1400 is ultimately controlled by the last rung of logic referencing it. X1 will override the logic state controlled by X0. To avoid this situation, multiple outputs using the same location must not be used in programming. X0
B1400.3 OUT
X1
B1400.3 OUT
DL205 User Manual, 4th Edition, Rev. A
Page 241
Chapter 5: Standard RLL Instructions - Boolean
Or Out (OROUT)
230 240 250-1 260
1 2 3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa 4 5 6 In the following example, when X1 or X4 is on, Y2 will energize. 7 8 9 10 11 Not (NOT) The Not instruction inverts the status of the rung at 12 the point of the instruction. 13 In the following example when X1 is off, Y2 will energize. This is because the Not instruction inverts the status of the rung at the Not instruction. 14 A B C D The Or Out instruction allows more than one rung of discrete logic to control a single output. Multiple Or Out instructions referencing the same output coil may be used, since all contacts controlling the output are logically ORed together. If the status of any rung is on, the output will also be on.
Inputs Outputs Control Relays Global Global DS HPP
Used Used
X Y C GX GY
0–177 0-177 0–377 -
DirectSOFT X1
0–477 0-477 0–377 -
0–777 0-777 0–1777 -
$
B
STR
O INST#
1
D
F
3
5
$
E
STR
Y2
OR OUT
230 240 250-1 260 DS HPP
Used Used
O INST#
DirectSOFT X1
0–1777 0-1777 0–3777 0–3777 0–3777
Handheld Programmer Keystrokes
Y2
OR OUT
X4
A aaa OR OUT
4
D
F
3
5
ENT ENT
ENT
C
ENT
C
2
ENT
ENT ENT
2
ENT
Handheld Programmer Keystrokes
Y2
$
B
1
STR
OUT
SHFT
GX OUT
N TMR
ENT
O INST#
T MLR
C
ENT
2
DL205 User Manual, 4th Edition, Rev. A
ENT
5–19
Page 242
Chapter 5: Standard RLL Instructions - Boolean
1
2
3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Positive Differential (PD) The Positive Differential instruction is typically known as a one shot. When the input logic produces an off to on transition, the output will energize for one CPU scan.
230 240 250-1
A aaa PD
260
Operand Data Type
Inputs Outputs Control Relays
DS HPP
5–20
DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa
X Y C
0–177 0–177 0–377
0–477 0–477 0–377
0–777 0–777 0–1777
0–1777 0–1777 0–3777
In the following example, every time X1 makes an off to on transition, C0 will energize for one scan. Used Used DirectSOFT X1
Handheld Programmer Keystrokes C0
$
B STR
PD SHFT
1 P CV
SHFT
ENT D
A 3
0
ENT
NOTE: To generate a “one–shot” pulse on an on–to–off transition, place a NOT instruction immediately before the PD instruction. The DL250–1 and DL260 CPUs support the STRND instruction.
DL205 User Manual, 4th Edition, Rev. A