DL205 PLC User Manual, Volume 1 of 2: Chapter 5: RLL and Intelligent Box Instructions, pages 503 to 512
Pages 503 to 512 of 592, from DL205 PLC User Manual, Volume 1 of 2
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the PLC Direct D2-08ND3 and Koyo D2-08ND3
Page 503
Chapter 5: Intelligent Box (IBox) Instructions
Parameter
DL205 Range
1 2 3 4 ECEMAIL Example 5 Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as 6 ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific 7 ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer 8 available for use by the other ECxxxx IBoxes using this specific ECOM100 module. 9 10 11 12 13 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in 14 BOLD italics, and the instruction name and ID will be in BOLD characters. A B C D ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V To: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Subject:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Body:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map Text Text See PRINT and VPRINT instructions
ECOM100 Config
ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
1
IB-710 K0 K1 V400 V401 V402-502
(example continued on next page)
DL205 User Manual, 4th Edition, Rev. A
5–281
Page 504
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ECEMAIL Example (cont’d)
5–282
Rung 2: When a machine goes down, send an email to Joe in maintenance and to the VP over production showing what machine is down along with the date/time stamp of when it went down. The ECEMAIL is leading edge triggered, not power-flow driven (similar to a counter input leg). An email will be sent whenever the power flow into the IBox goes from OFF to ON. This helps prevent self inflicted spamming. If the EMail is sent, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the SMTP error code or other possible error codes.
DL205 User Manual, 4th Edition, Rev. A
Page 505
Chapter 5: Intelligent Box (IBox) Instructions
ECOM100 Restore Default E-mail Setup (ECEMRDS) (IB-713)
230 240 250-1 260 DS5
Used
HPP
N/A
ECOM100 Restore Default EMail Setup, on a leading edge transition, will restore the original EMail Setup data stored in the ECOM100 back to the working copy based on the specified ECOM100#, which corresponds to a specific unique ECOM100 Configuration (ECOM100) at the top of your program. When the ECOM100 is first powered up, it copies the EMail setup data stored in ROM to the working copy in RAM. You can then modify this working copy from your program using the ECOM100 EMail Setup (ECEMSUP) IBox. After modifying the working copy, you can later restore the original setup data via your program by using this IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECEMRDS Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written
Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
DL205 Range K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–283
Page 506
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ECEMRDS Example
5–284
Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module. ECOM100 Config ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
1
IB-710 K0 K1 V400 V401 V402-502
NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters.
Rung 2: Whenever an EStop is pushed, ensure that the president of the company gets copies of all Emails being sent. The ECOM100 EMail Setup IBox allows you to set/change the SMTP Email settings stored in the ECOM100.
(example continued on next page)
DL205 User Manual, 4th Edition, Rev. A
Page 507
Chapter 5: Intelligent Box (IBox) Instructions
ECEMRDS Example (cont’d) Rung 3: Once the EStop is pulled out, take the president off the cc: list by restoring the default EMail setup in the ECOM100. The ECEMRDS is leading edge triggered, not power-flow driven (similar to a counter input leg). The ROM based EMail configuration stored in the ECOM100 will be copied over the "working copy" whenever the power flow into the IBox goes from OFF to ON (the working copy can be changed by using the ECEMSUP IBox). If successful, turn on C102. If there is a failure, turn on C103. If it fails, you can look at V2001 for the specific error code.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–285
Page 508
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ECOM100 E-mail Setup (ECEMSUP) (IB-712)
230 240 250-1 260 DS5
Used
HPP
N/A
5–286
ECOM100 EMail Setup, on a leading edge transition, will modify the working copy of the EMail setup currently in the ECOM100 based on the specified ECOM100#, which corresponds to a specific unique ECOM100 Configuration (ECOM100) at the top of your program. You may pick and choose any or all fields to be modified using this instruction. Note that these changes are cumulative: if you execute multiple ECOM100 EMail Setup IBoxes, then all of the changes are made in the order they are executed. Also note that you can restore the original ECOM100 EMail Setup that is stored in the ECOM100 to the working copy by using the ECOM100 Restore Default EMail Setup (ECEMRDS) IBox. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). You are limited to approximately 100 characters/bytes of setup data for the entire instruction. So if needed, you could divide the entire setup across multiple ECEMSUP IBoxes on a fieldby-field basis, for example do the Carbon Copy (cc:) field in one ECEMSUP IBox and the remaining setup parameters in another. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECEMSUP Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written • SMTP Server IP Addr: optional parameter that specifies the IP Address of the SMTP Server on the ECOM100’s network • Sender Name: optional parameter that specifies the sender name that will appear in the “From:” field to those who receive the e-mail • Sender EMail: optional parameter that specifies the sender EMail address that will appear in the “From:” field to those who receive the e-mail
DL205 User Manual, 4th Edition, Rev. A
Page 509
Chapter 5: Intelligent Box (IBox) Instructions ECEMSUP Parameters (cont’d)
1 2 • Timeout (sec): optional parameter that specifies the number of seconds to wait for the SMTP Server to send the EMail to all the recipients • Cc: optional parameter that specifies a list of “carbon copy” Email addresses to send all EMails to 3 4 Parameter DL205 Range 5 6 7 8 9 10 11 12 13 14 A B C D • Port Number: optional parameter that specifies the TCP/IP Port Number to send SMTP requests; usually this does not need to be configured (see your network administrator for information on this setting)
ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words
DL205 User Manual, 4th Edition, Rev. A
5–287
Page 510
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ECEMSUP Example
5–288
Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.
ECOM100 Config ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)
1
IB-710 K0 K1 V400 V401 V402-502
(example continued on next page)
NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters.
DL205 User Manual, 4th Edition, Rev. A
Page 511
Chapter 5: Intelligent Box (IBox) Instructions
ECEMSUP Example (cont’d) Rung 2: Whenever an EStop is pushed, ensure that president of the company gets copies of all EMails being sent.The ECOM100 EMail Setup IBox allows you to set/change the SMTP EMail settings stored in the ECOM100. The ECEMSUP is leading edge triggered, not power-flow driven (similar to a counter input leg). At power-up, the ROM based EMail configuration stored in the ECOM100 is copied to a RAM based "working copy". You can change this working copy by using the ECEMSUP IBox. To restore the original ROM based configuration, use the Restore Default EMail Setup ECEMRDS IBox. If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code.
Rung 3: Once the EStop is pulled out, take the president off the cc: list by restoring the default EMail setup in the ECOM100.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–289
Page 512
Chapter 5: Intelligent Box (IBox) Instructions
1 2
3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ECOM100 IP Setup (ECIPSUP) (IB-717) 230 240 250-1 260
DS5
Used
HPP
N/A
5–290
ECOM100 IP Setup will configure the three TCP/IP parameters in the ECOM100: IP Address, Subnet Mask, and Gateway Address, on a leading edge transition to the IBox. The ECOM100 is specified by the ECOM100#, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). This setup data is stored in Flash-ROM in the ECOM100 and will disable the ECOM100 module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED SP0 (NOT First Scan) to drive the power flow to the IBox. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECIPSUP Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written • IP Address: specifies the module’s IP Address • Subnet Mask: specifies the Subnet Mask for the module to use • Gateway Address: specifies the Gateway Address for the module to use
Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V IP Address . . . . . . . . . . . . . . . . . . . . . IP Address Subnet Mask Address . . . . . . . IP Address Mask Gateway Address . . . . . . . . . . . . . . . . IP Address
DL205 User Manual, 4th Edition, Rev. A
DL205 Range K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words 0.0.0.1. to 255.255.255.254 0.0.0.1. to 255.255.255.254 0.0.0.1. to 255.255.255.254