Page 533

Chapter 5: Intelligent Box (IBox) Instructions

ECWRMID Example

1 2 3 4 5 6 7 8 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 9 Rung 2: On the 2nd scan, set the Module ID of the ECOM100. Typically this is done using 10 NetEdit, but this IBox allows you to configure the module ID of the ECOM100 using your ladder program. The ECWRMID is leading edge triggered, not power-flow driven (similar to a counter input 11 leg). The command to write the module ID will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. 12 If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code. 13 14 A B C D Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

ECOM100 Config

1

ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)

DL205 User Manual, 4th Edition, Rev. A

IB-710 K0 K1 V400 V401 V402-502

5–311

Page 534

Chapter 5: Intelligent Box (IBox) Instructions

1 2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ECOM100 Write Name (ECWRNAM) (IB-725) 230 240 250-1 260

DS5

Used

HPP

N/A

5–312

ECOM100 Write Name will write the given Name to the ECOM100 module on a leading edge transition to the IBox. If you use a dollar sign ($) or double quote ("), use the PRINT/VPRINT escape sequence of TWO dollar signs ($$) for a single dollar sign or dollar sign-double quote ($") for a double quote character. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). The Name is stored in Flash-ROM in the ECOM100 and the execution of this IBox will disable the ECOM100 module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED SP0 (STR NOT First Scan) to drive the power flow to the IBox. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECWRNAM Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written • Module Name: specifies the Name that will be written to the module

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Module Name . . . . . . . . . . . . . . . . . . . . . . . . . . .

DL205 User Manual, 4th Edition, Rev. A

DL205 Range K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words Text

Page 535

Chapter 5: Intelligent Box (IBox) Instructions

ECWRNAM Example

1 2 3 4 5 6 7 8 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 9 Rung 2: On the 2nd scan, set the Module Name of the ECOM100. Typically this is done 10 using NetEdit, but this IBox allows you to configure the module name of the ECOM100 using your ladder program. The ECWRNAM is leading edge triggered, not power-flow driven (similar to a counter input 11 leg). The command to write the module name will be sent to the ECOM100 whenever the power flow into the IBox goes from OFF to ON. 12 If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code. 13 14 A B C D Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

ECOM100 Config

1

ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)

DL205 User Manual, 4th Edition, Rev. A

IB-710 K0 K1 V400 V401 V402-502

5–313

Page 536

Chapter 5: Intelligent Box (IBox) Instructions

1 2

3

4 5 6 7 8 9 10 11 12 13 14 A B C D

ECOM100 Write Subnet Mask (ECWRSNM) (IB-733) 230 240 250-1 260

DS5

Used

HPP

N/A

5–314

ECOM100 Write Subnet Mask will write the given Subnet Mask to the ECOM100 module on a leading edge transition to the IBox. See also ECOM100 IP Setup (ECIPSUP) IBox 717 to setup ALL of the TCP/IP parameters in a single instruction - IP Address, Subnet Mask, and Gateway Address. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Either the Success or Error bit parameter will turn on once the command is complete. If there is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or a PLC logic error (greater than 1000). The Subnet Mask is stored in Flash-ROM in the ECOM100 and the execution of this IBox will disable the ECOM100 module for at least a half second until it writes the Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED SP0 (STR NOT First Scan) to drive the power flow to the IBox. In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the ECOM100 circuit board. ECWRSNM Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed • Error Code: specifies the location where the Error Code will be written • Subnet Mask: specifies the Subnet Mask that will be written to the module

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . .

DL205 User Manual, 4th Edition, Rev. A

DL205 Range K0-255 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map - Data Words Masked IP Address

Page 537

Chapter 5: Intelligent Box (IBox) Instructions

ECWRSNM Example

1 2 3 4 5 6 7 8 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 9 Rung 2: On the 2nd scan, assign the Subnet Mask of the ECOM100 to 255.255.0.0 10 The ECWRSNM is leading edge triggered, not power-flow driven (similar to a counter input leg). The command to write the Subnet Mask will be sent to the ECOM100 whenever the 11 power flow into the IBox goes from OFF to ON. If successful, turn on C100. If there is a failure, turn on C101. If it fails, you can look at V2000 for the specific error code. 12 To configure all of the ECOM100 TCP/IP parameters in one IBox, see the ECOM100 IP Setup (ECIPSUP) IBox. 13 14 A B C D Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

ECOM100 Config

1

ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)

DL205 User Manual, 4th Edition, Rev. A

IB-710 K0 K1 V400 V401 V402-502

5–315

Page 538

Chapter 5: Intelligent Box (IBox) Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ECOM100 RX Network Read (ECRX) (IB-740)

230 240 250-1 260 DS5

Used

HPP

N/A

5–316

ECOM100 RX Network Read performs the RX instruction with built-in interlocking with all other ECOM100 RX (ECRX) and ECOM100 WX (ECWX) IBoxes in your program to simplify communications networking. It will perform the RX on the specified ECOM100#'s network, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will read element data from the specified slave into the given destination V-memory buffer, giving other ECOM100 RX and ECOM100 WX IBoxes on that ECOM100# network a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these ECRX and ECWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically! ECRX Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave ECOM(100) PLC that will be targeted by the ECRX instruction • From Slave Element (Src): specifies the slave address of the data to be read • Number of Bytes: specifies the number of bytes to read from the slave ECOM(100) PLC • To Master Element (Dest): specifies the location where the slave data will be placed in the master ECOM100 PLC • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Slave Element (Src) X,Y,C,S,T,CT,GX,GY,V Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Master Element (Dest) . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

DL205 User Manual, 4th Edition, Rev. A

DL205 Range K0-255 See DL205 V-memory map - Data Words K0-90 See DL205 V-memory map K1-128 See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map

Page 539

Chapter 5: Intelligent Box (IBox) Instructions

ECRX Example

1 2 3 4 5 6 7 8 9 NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 10 11 12 13 14 A B C D Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

ECOM100 Config

1

ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)

IB-710 K0 K1 V400 V401 V402-502

(example continued on next page)

DL205 User Manual, 4th Edition, Rev. A

5–317

Page 540

Chapter 5: Intelligent Box (IBox) Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ECRX Example (cont’d)

5–318

Rung 2: Using ECOM100# K0, read X0-X7 from Slave K7 and write them to slave K5 as fast as possible. Store them in this local PLC in C200-C207, and write them to C300-C307 in slave K5. Both the ECRX and ECWX work with the ECOM100 Config IBox to simplify all networking by handling all of the interlocks and proper resource sharing. They also provide very simplified error reporting. You no longer need to worry about any SP "busy bits" or "error bits", or what slot number a module is in, or have any counters or shift registers or any other interlocks for resource management. In this example, SP1 (always ON) is driving both the ECRX and ECWX IBoxes in the same rung. On the scan that the Network Read completes, the Network Write will start that same scan. As soon as the Network Write completes, any pending operations below it in the program would get a turn. If there are no pending ECOM100 IBoxes below the ECWX, then the very next scan the ECRX would start its request again. Using the ECRX and ECWX for all of your ECOM100 network reads and writes is the fastest the PLC can do networking. For local Serial Ports, DCM modules, or the original ECOM modules, use the NETCFG and NETRX/NETWX IBoxes.

DL205 User Manual, 4th Edition, Rev. A

Page 541

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 WX Network Write(ECWX) (IB-741)

230 240 250-1 260 DS5

Used

HPP

N/A

ECOM100 WX Network Write performs the WX instruction with built-in interlocking with all other ECOM100 RX (ECRX) and ECOM100 WX (ECWX) IBoxes in your program to simplify communications networking. It will perform the WX on the specified ECOM100#'s network, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will write data from the master's V-memory buffer to the specified slave starting with the given slave element, giving other ECOM100 RX and ECOM100 WX IBoxes on that ECOM100# network a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these ECRX and ECWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically! ECWX Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave ECOM(100) PLC that will be targeted by the ECWX instruction • From Master Element (Src): specifies the location in the master ECOM100 PLC where the data will be sourced from • Number of Bytes: specifies the number of bytes to write to the slave ECOM(100) PLC • To Slave Element (Dest): specifies the slave address the data will be written to • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter

DL205 Range

ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Master Element (Src) . . . . . . . . . . . . . . . V Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Slave Element (Dest) . . X,Y,C,S,T,CT,GX,GY,V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

K0-255 See DL205 V-memory map - Data Words K0-90 See DL205 V-memory map - Data Words K1-128 See DL205 V-memory map See DL205 V-memory map See DL205 V-memory map

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–319

Page 542

Chapter 5: Intelligent Box (IBox) Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ECWX Example

5–320

Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module. V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

ECOM100 Config ECOM100 ECOM100# Slot Status Workspace Msg Buffer (65 WORDs)

1

IB-710 K0 K1 V400 V401 V402-502

NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters.

DL205 User Manual, 4th Edition, Rev. A