Page 563
Chapter 5: Intelligent Box (IBox) Instructions
CTREDPT Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–341
Page 564
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Edit Preset Table Entry and Reload (CTREDRL) (IB-1002)
230 240 250-1 260 DS5
Used
HPP
N/A
5–342
CTRIO Edit Preset Table Entry and Reload, on a leading edge transition to this IBox, will perform this dual operation to a CTRIO Output resource in one CTRIO command. This IBox will take more than one PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTREDRL Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Table#: specifies the Table number of which an Entry is to be edited • Entry#: specifies the Entry location in the Preset Table to be edited • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time in msecs for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL205 User Manual, 4th Edition, Rev. A
Page 565
Chapter 5: Intelligent Box (IBox) Instructions Parameter
DL205 Range
1 2 3 4 5 CTREDRL Example Rung 1: This sets up the CTRIO module in slot 2 of the local base. Each CTRIO module in 6 the system will need a separate CTRIO Config IBox before any CTRxxxx IBoxes can be used. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 7 through V2061 for its output data. 8 9 10 11 12 NOTE: The CTRIO Configuration IBox instruction does not require a permissive contact. The top line will be identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 13 14 A B C D CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Table# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-255; See DL205 V-memory map - Data Words K0-255; See DL205 V-memory map - Data Words K0-5; See DL205 V-memory map - Data Words K0-65535; See DL205 V-memory map - Data Words K0-2147434528; See DL205 V-memory map See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map
(example continued on next page)
DL205 User Manual, 4th Edition, Rev. A
5–343
Page 566
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTREDRL Example (cont’d)
5–344
Rung 2: This rung is a sample method for enabling the CTREDRL command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTREDRL instruction to change the second preset in file 1 from a reset value of 20 to a reset value of 30. Operating procedure for this example code is to load the CTREDRL_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on, continue to a count above 20 and the output #0 light will turn off. Now reset the counter with C1, enable C0 to execute CTREDRL command to change the second preset count value to 30, then turn encoder to value of 10+ (output #0 should turn on) and continue on to a value of 30+ and the output #0 light will turn off. Note that it is not necessary to reload this file separately, however, the command can only change one value at a time.
(example continued on next page)
DL205 User Manual, 4th Edition, Rev. A
Page 567
Chapter 5: Intelligent Box (IBox) Instructions
CTREDRL Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–345
Page 568
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Initialize Preset Table (CTRINPT) (IB-1004)
230 240 250-1 260 DS5
Used
HPP
N/A
5–346
CTRIO Initialize Preset Table, on a leading edge transition to this IBox, will create a single entry Preset Table in memory but not as a file, on a specific CTRIO Output resource. This IBox will take more than one PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTRINPT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time in msecs for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL205 User Manual, 4th Edition, Rev. A
Page 569
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 CTRINPT Example 5 Rung 1: This sets up the CTRIO module in slot 2 of the local base. Each CTRIO module in the system will need a separate CTRIO Config IBox before any CTRxxxx IBoxes can be used. 6 The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data. 7 8 9 10 11 NOTE: The CTRIO Configuration IBox instruction does not require a permissive contact. The top line will be 12 identified in BOLD italics, and the instruction name and ID will be in BOLD characters. 13 14 A B C D Parameter
DL205 Range
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-5; See DL205 V-memory map - Data Words K0-65535; See DL205 V-memory map - Data Words K0-2147434528; See DL205 V-memory map See DL205 V-memory map - Data Words See DL205 V-memory map See DL205 V-memory map
(example continued on next page)
DL205 User Manual, 4th Edition, Rev. A
5–347
Page 570
Chapter 5: Intelligent Box (IBox) Instructions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRINPT Example (cont’d)
5–348
Rung 2: This rung is a sample method for enabling the CTRINPT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRINPT instruction to create a single entry preset table, but not as a file, and use it for the output #0. In this case the single preset will be set at a count of 15 for output #0. Operating procedure for this example code is to load the CTRINPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 15 and output #0 light will not come on. Now reset the counter with C1, enable C0 to execute CTRINPT command to create a single preset table with a preset to set output#0 at a count of 15, then turn encoder to value of 15+ (output #0 should turn on).
DL205 User Manual, 4th Edition, Rev. A
Page 571
Chapter 5: Intelligent Box (IBox) Instructions
CTRINPT Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–349
Page 572
Chapter 5: Intelligent Box (IBox) Instructions
1 2
3
4 5 6 7 8 9 10 11 12 13 14 A B C D
CTRIO Initialize Preset Table on Reset (CTRINTR) (IB-1010)
DS5
Used
CTRIO Initialize Preset Table on Reset, on a leading edge transition to this IBox, will create a single entry Preset Table in memory but not as a file, on a specific CTRIO Output resource.This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information.
HPP
N/A
Entry Type:
230 240 250-1 260
5–350
K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTRINTR Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time in msecs for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL205 User Manual, 4th Edition, Rev. A