Page 17

7--17

Discrete Output Modules

D3--16TA--2, 110--220 VAC Output Module 16 2 (isolated) 15--265 VAC Triac 265 VAC 47--63 Hz 1.5 VAC @ 0.5A 0.5A / point 3A / common 6A / per module

Max leakage current Max inrush current

4 mA @ 265 VAC 10A for 10 ms 5A for 100 ms

Minimum load Base power required *

10 mA @ 15VAC 9V 25mA Max /ON pt. 400 mA Max 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

1 ms Max 9 ms Max Removable Logic Side 7.2 0z. (210 g) (2) One 5A per common Non--replaceable

Discrete Output Modules

Outputs per module Commons per module Operating voltage Output type Peak voltage AC frequency ON voltage drop Max current

* 9V typical values 17mA/ON pt., 272 mA total

Derating Chart for D3--16TA--2 Points 16

110--220VAC OUTPUT D3--16TA--2

I

15--265VAC

CI 0

L L

2

L

4

L L

15--265VAC

6

L L

CII

L L

1

L

3

L

5

L

7

L

L

L

1 3 5 7 0 2 4 6

0 2 4 6 C 1 3 5 7

4 5 6 7

0 1 2 3

4 5 6 7

II

0.30A

12

0.5A

8 Max 3A/common

4

C

0.2A

0

1

0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

3 5 7

15--265VAC

0

Line

Common 5A

2

9V .33

4 6 II

47Ω L

Output

DL305 User Manual, Rev. D

Discrete Output Modules

L

I

0 1 2 3

Page 18

7--18

Discrete Output Modules

D3--08TR, Relay Output Module

Discrete Output Modules

Outputs per module Commons per module Operating voltage

8 2 (isolated) 5--265VAC 5--30VDC Form A (SPST) 265VAC / 30VDC 47--63 Hz N/A 4A / point AC 5A / point DC 6A / common

Output type Peak voltage AC frequency ON voltage drop Max current

Max leakage current Max inrush current

Minimum load Base power required

5 mA @ 5v 9V 45 mA/ON pt. (360 mA Max) 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

5 ms 5 ms Non-removable Logic Side 7 oz. (200 g) (2) One 10A per common User replaceable

1 mA @ 220VAC 5A Derating Chart for D3--08TR

Typical Relay Life (Operations) Voltage Resistive Solenoid Closures 220VAC 220VAC 110VAC 110VAC 24VDC

4A 4A 5A

0.5A 0.05A 0.5A 0.1A 0.5A

Discrete Output Modules

5--265VAC

100k 800k 100k 650k 100k

C1 L

RELAY OUTPUT D3--08TR

6

0

4

1

5

2

6

3

7

4 2 0 0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

C 1 0 1

L

0

1

L

2

3

2 3

L

4 5 L

4

5

6

7

L

Common

10A 9V

6 7

L

C 2

L

-- + 5--30VDC

Points 8

C2

DL305 User Manual, Rev. D

L

Output

Relay

Page 19

7--19

Discrete Output Modules

F3--08TRS--1, Relay Output Module Outputs per module Commons per module Operating voltage*

Max leakage current Max inrush current Minimum load

N/A 10A Inductive 100 mA @12VDC

Base power required

Output type

6 Form A (SPST) 2 Form C (SPDT)

Peak voltage AC frequency ON voltage drop Max current (resistive)

265 VAC / 120 VDC 47--63 Hz N/A 10A / point AC/DC 30A / module AC/DC

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

9V 37mA / ON pt. (296 mA Max) 24V N/A 13 ms Max 9 ms Max Removable Logic Side 8.9 oz. (252 g) (8) One 10A (125V) per common Non-replaceable

Discrete Output Modules

8 8 (isolated) 12--125 VAC 125--250 VAC requires external fuses 12--30 VDC

NOTE: Contact life may be lengthened beyond those values shown by the use of an appropriate arc suppression. This technique is discussed earlier in this chapter. Derating Chart for F3--08TRS--1

Typical Relay Life (Operations)

Points 8

Output Current 10A/point (30A/module)

6 4

RELAY OUTPUT F3--08TRS--1

0 0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F) L

0C

+

L

--

1C L

2C

--

+

L

3C L

L

4C 5C

L

6C

--

+

L

L L

7C 7NC

0 C

0 NC 0 NO 1 NO 2 NO 3 NO 4 NO 5 NO 6 NO 7 NO

1 C 2 C 3 C 4 C 5 C 6 C 7 C 7 NC

4 5 6 7

12--250VAC

0 NC

Discrete Output Modules

0 1 2 3

2

Maximum Resistive Operating Voltage or Inductive Inrush Load Current 28VDC 120VAC 240VAC 25K 1/4HP 10.0A 50K 50K 5.0A 200K 100K 3.0A 325K 125K 50K >50M .05A 10A Common

0 NO 1 NO

NO

L

2 NO 3 NO

12--30VDC

--

+

4 NO 5 NO 6 NO 7 NO

9V

Outputs 1--6 10A Common

L

L

NC NO

Outputs 0 & 7 *Maximum DC voltage rating is 120 VDC at .5 Amp, 30,000 cycles typical Motor starters up to and including a NEMA size 4 can be used with this module.

DL305 User Manual, Rev. D

9V

Page 20

7--20

Discrete Output Modules

F3--08TRS--2, Relay Output Module

Discrete Output Modules

Outputs per module Commons per module Operating voltage*

8 8 (isolated) 12--125 VAC 125--250 VAC requires external fuses 12--30 VDC

Max leakage current Max inrush current Minimum load

N/A 10A Inductive 100 mA @12VDC

Base power required

Output type

6 Form A (SPST) 2 Form C (SPDT)

Peak voltage AC frequency ON voltage drop Max current (resistive)

265 VAC / 120 VDC 47--63 Hz N/A 5A / point AC/DC 40A / module AC/DC

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses 19379--K--10A Wickman

9V 37mA / ON pt. (296 mA Max) 24V N/A 13 ms Max 9 ms Max Removable Logic Side 9 oz. (255 g) (8) One 5A (125V) per common User replaceable

NOTE: Contact life may be lengthened beyond those values shown by the use of an appropriate arc suppression. This technique is discussed earlier in this chapter. Derating Chart for F3--08TRS--2

Typical Relay Life (Operations)

Points 8

Output Current 5A/point (40A/module)

6 4

RELAY OUTPUT F3--08TRS--2

0 1 2 3

Discrete Output Modules

2 0 0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F) L

0C

+

L

--

1C L

2C

--

+

L

3C L

L

4C 5C

L

6C

--

+

L

L L

7C 7NC

0 C

0 NC 0 NO 1 NO 2 NO 3 NO 4 NO 5 NO 6 NO 7 NO

DL305 User Manual, Rev. D

1 C 2 C 3 C 4 C 5 C 6 C 7 C 7 NC

4 5 6 7

Maximum Resistive Operating Voltage or Inductive Inrush Load Current 28VDC 120VAC 240VAC 5.0A 200K 100K 325K 125K 50K 3.0A .05A >50M Expected mechanical relay life is 100 million operations. 12--250VAC

0 NC

5A Common

0 NO 1 NO

NO

L

2 NO 3 NO

12--30VDC

--

Common

5 NO

7 NO

5A

+

4 NO

6 NO

9V

Outputs 1--6

L

L

NC

9V

NO

Outputs 0 & 7 *Maximum DC voltage rating is 120 VDC at .5 Amp, 30,000 cycles typical Motor starters up to and including a NEMA size 3 can be used with this module.

Page 21

Discrete Output Modules

7--21

D3--16TR, Relay Output Module Outputs per module Commons per module Operating voltage

Max leakage current Max inrush current

Minimum load Base power required

5 mA @ 5v 9V 30 mA/ON pt. (480 mA Max) 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight

12 ms 12 ms Removable Logic Side 8.5 oz. (248g)

Fuses

None

Discrete Output Modules

Output type Peak voltage AC frequency ON voltage drop Max current

16 2 (isolated) 5--265 VAC 5--30 VDC 16 Form A (SPST) 265 VAC / 30 VDC 47--63 Hz N/A 2A / point AC/DC (resistive) 8A / common AC/DC 0.1mA @ 220 VAC 2A

Typical Relay Life (Operations) Voltage Resistive Solenoid Closures 220VAC 220VAC 110VAC 110VAC 24VDC

2A

0.25A 0.03A 0.25A 0.05A 0.25A

2A 2A

100k 800k 100k 650k 100k

5--265VAC

CI 0

L L

2

L L

4

L

5--30VDC

6

L L

CII

L L

1

L

3

L

5

L

L

L L

7

I

I 1 3 5 7 0 2 4 6

Points 16

D3--16TR

0 2 4 6 C 1 3 5 7

0 1 2 3

4 5 6 7

0 1 2 3

4 5 6 7

II

12 8 4

C

0

1

0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

3 5

5--265 VAC

7 0 2

5--30VDC -- +

Common

9V

4 6

L

II Output

Relay

DL305 User Manual, Rev. D

Discrete Output Modules

L

Derating Chart for D3--16TR RELAY OUTPUT

Page 22

This page is a scan with no text; see it in the PDF.