Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 20 of 41

DL305 User Manual: Chapter 8: System Operation, pages 150 to 159

Pages 150 to 159 of 357, from DL305 User Manual

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA

Page 150

System Operation

18

In This Chapter. . . ., Introduction, CPU Operating System, Initial Mode Setting and Memory Initialization, Program Mode Operation, Run Mode Operation, I/O Response Time, CPU Scan Time Considerations, Memory Map, I/O Point Bit Map, Control Relay Bit Map, Special Relays, Timer / Counter Registers and Contacts, Data Registers, Stage Control / Status Bit Map, Shift Register Bit Map, Special Registers

Page 151

8--2

System Operation

System Operation

Introduction Achieving the proper control for your equipment or process requires a good understanding of how the DL305 CPUs control all aspects of the system operation. This includes many things, such as I/O updates, program execution, etc. Take a few minutes to understand how the CPU stores and processes information. For more complex applications, this knowledge will make it easier to program and debug your application program to meet your system performance requirements. There are four primary things you need to understand before you create your application program S CPU Operating System, the CPU is the heart of the system. It manages all aspects of system control. A quick overview of all the steps is provided in the next section. S CPU Operating Modes, the CPU has different operating modes that allow different types of operations. There are two primary modes of operation, Program Mode and Run Mode. S CPU Timing, it is important you understand how the CPU timing can affect the system operation. The two most important areas are the I/O response time and the CPU scan time. S CPU Memory Map, The DL305 CPUs offer a wide variety of memory types, such as timers, counters, inputs, etc. It is important to understand what memory types are available and how the memory areas are organized. The remainder of this chapter discusses these items in detail.

DL305 User Manual, Rev. D

Page 152

System Operation

8--3

CPU Operating System After the initial power-up sequence, the DL305 CPUs process data cyclically. There are several tasks the CPU must perform during each cycle, such as updating the I/O status, servicing external communications, executing the application program, etc. There are many different segments of execution, but the overwhelming majority of your concerns will be with the portion of the execution cycle that occurs during Run Mode. These operations will be discussed throughout the remainder of this chapter. DL305 CPU Operational Flow Chart

Power up #1 Initial Mode Setting

Initialize memory

Is program memory OK?

NO

YES

YES What mode is the programmer in? RUN

System Operation

Is programmer connected?

Display error code NO User changes programmer to program mode

PGM/ Cassette What is the last mode?

PGM/ Cassette

RUN I/O update Service peripherals Service peripherals Service for force operation or monitoring

Operation of program or cassette mode PGM What is the mode?

Executes user program

RUN

DL305 User Manual, Rev. D

Page 153

8--4

System Operation

Initial Mode Setting and Memory Initialization Flow Chart for The previous flowchart contained a step called Initial Mode Setting. Once power has Initial Mode Setting been connected to the system, the CPU executes the following procedure to determine which mode of operation should be entered. (#1) NO

Is programmer or Data Communication Unit connected? YES What is connected?

Data Communication Unit

Programmer ONLINE or OFFLINE?

ONLINE

OFFLINE Is programmer connected?

NO

PROM

YES

System Operation

What is the current mode? RUN

Service peripherals

Initialize Memory

DL305 User Manual, Rev. D

PGM

PGM

Select PGM/ Cassette mode

What is the last mode? RUN

What is the program memory RAM

Page 154

System Operation Memory Initialization

8--5

Before the CPU can begin normal operation, all memory areas are initialized. The CPU completes the following operations to initialize the memory areas. Item

Procedure

I/O Points

Input Points: activated, CPU will monitor status. Output Points: turned off

Control Relays

Non-Retentive: turned off Retentive: retains the condition prior to the system power interruption.

Shift Registers

Retains the condition prior to the system power interruption.

Timer / Counter Current Values

Timers: reset to zero Counters: retains the current count prior to the system power interruption.

Stages

Non-Retentive: turned off Retentive: retains the condition prior to the system power interruption.

Data Registers

Retains the condition prior to the system power interruption.

DL305 User Manual, Rev. D

System Operation

NOTE: Not all memory areas are retentive by default. See Chapter 3 for details on how to set the CPU to have retentive memory. Also, the memory map section provided later in this chapter shows the exact ranges that can be selected as retentive.

Page 155

8--6

System Operation

Program Mode Operation

System Operation

In Program Mode, the CPU does not execute the application program or update the output modules. The primary use for Program Mode is to enter or change an application program. You can also use the program mode to set up CPU parameters, such as the network address for the communication port on the DL340, retentive memory areas, etc. You can use the Handheld Programmer key switch to select Program Mode operation, or you can use a DirectSOFT menu option to change the CPU mode.

DL305 User Manual, Rev. D

Download Program

Page 156

System Operation

8--7

Run Mode Operation In Run Mode, the CPU executes the application program and updates the I/O system. You can perform many operations during Run Mode. Some of these include: S Monitor and change I/O point status S Update timer/counter preset values S Update Register memory locations Even though there are many steps in the overall flowchart of operation, the Run Mode operation can be divided into a few key areas. It is very important you understand how each of these areas of execution can affect the results of your application program solutions.

Update I/O Points Service Peripherals Service Monitoring & Forcing Solve Application Program

System Operation

DL305 User Manual, Rev. D

Page 157

8--8

System Operation

Update I/O Points

The CPU reads the status of all input modules present in the local CPU base and local expansion bases. The status of each input is stored in the input image register area. The input image register data is used by the CPU when it solves the application program. You may be thinking, “What if an input changes after the CPU has read the inputs?” Good question! Generally, the CPU program execution time is measured in milliseconds, so in most cases this is not a problem. If you need to know more, I/O response timing is explained in more detail later in this chapter. The CPU also uses the output image register to update the output modules present in the local CPU base and local expansion bases.

8pt

8pt

8pt

16pt

4ch.

16pt

Relay

Output

Input

Input

Output

Input

050 -057

040 -047

030 -037

020 027 -120 127

010 017 -110 117

000 007 -100 107

System Operation

CPU Scan

Field Device OFF

030

OFF

031

ON

032

ON

033

OFF

034

ON

035

OFF

036

OFF

037

OFF

040

OFF

041

ON

042

ON

043

OFF

044

ON

045

OFF

046

OFF

047

DL305 User Manual, Rev. D

Update I/O Points

I/O Modules

... ... The CPU reads the inputs from the local and expansion bases and stores the status in an input image register.

032 031 030 ON OFF OFF Input Image Register

... ...

... 042 041 040 ... ON OFF OFF Output Image Register

... ...

Service Peripherals Service Monitoring & Forcing Solve Application Program

The CPU also writes the status of the output image register to the output modules.

Page 158

System Operation

8--9

Service Peripherals After the CPU updates the I/O points, it reads any attached peripheral devices. This is primarily a communications service for any attached devices. For example, if you were using an operator interface to read or write data, the CPU would service these requests during this portion of the scan. 8pt

8pt

8pt

16pt

4ch.

16pt

Relay

Output

Input

Input

Output

Input

050 -057

040 -047

030 -037

020 027 -120 127

010 017 -110 117

000 007 -100 107

CPU Scan Update I/O Points ... ...

... ...

... 042 041 040 ... ON OFF OFF Output Image Register

... ...

Service Peripherals Service Monitoring & Forcing Solve Application Program

DL305 User Manual, Rev. D

System Operation

CPU services peripherals through communication ports.

032 031 030 ON OFF OFF Input Image Register

Page 159

8--10

System Operation

Service for After the CPU updates any communications requests from peripheral devices, it determines if any forcing operations have been requested. The CPU also services Monitoring and Forcing Operations any monitoring requests during this portion. For example, if you are using the Handheld Programmer to monitor the current value of a timer or counter, the CPU will provide this information during this portion of the scan. Here’s an example of one of the more popular requests. For example, you may want to force an input on, even though it is really off. This allows you to change the point status that was stored in the image register. This value will be valid until the image register location is written to during the Update I/O Points segment of the next scan. 8pt

8pt

8pt

16pt

4ch.

16pt

Relay

Output

Input

Input

Output

Input

050 -057

040 -047

030 -037

020 027 -120 127

010 017 -110 117

000 007 -100 107

System Operation

CPU Scan

Field Device

Update I/O Points

I/O Modules

OFF

030

OFF

031

ON

032

ON

033

The CPU reads the inputs from the local and expansion bases and stores the status in an input image register.

... ...

... 042 041 040 ... ON OFF OFF Output Image Register

... ...

Service Peripherals

Force input 030 ON

The application program uses the forced value to solve the application program. In this example, output 040 will be turned on because the force changed the status of input 030 in the image register.

DL305 User Manual, Rev. D

032 031 030 ON OFF OFF Input Image Register

... ...

Service Monitoring & Forcing ... ...

032 031 030 ON OFF ON Input Image Register

... ...

Solve Application Program 030

040