Page 232

RLL PLUS Programming Basics

10--31

Step 4: Some actions may only take place if certain conditions are met. Examine the Add Conditions for program carefully to determine any conditions that should be added. The following flowchart adds any conditions for the actions that take place during each part of the Actions program. Wait for Start

Press Start Switch

Check for Part

Part in place

No Part Jump to Move Conveyor

Lock the Clamp Clamp On Clamp Limit Switch

Press the Part Press Press Lower Limit Switch Unlock the Clamp Press Up

Clamp Off

Unclamp Limit Switch Move Conveyor

Condition Symbol Conveyor On

Conveyor Index Limit Switch Check Mode

Jump to Wait for Start

Check 1-cycle Switch OFF Jump to Check for Part

DL305 User Manual, Rev. D

RLLPLUS Programming Basics

Check 1-cycle Switch ON

Page 233

10--32

RLL PLUS Programming Basics

Step 5: Add Alarm or Monitoring Operations

Many people are tempted to add alarm or monitoring operations earlier in the flowchart design process. It is almost always easier to add them last because then you know how they should affect the main part of the program. The following flowchart adds an operation that monitors for the conditions that will stop the press. Wait for Start

Press Start Switch

Check for Part

Monitor for Stop

Stop Switch

Part in place

Reset all Operations

Jump to Wait for Start

No Part Jump to Move Conveyor

Lock the Clamp Clamp On

Clamp Limit Switch

Press the Part Press On Press Lower Limit Switch Unlock the Clamp Press Up

Clamp Off

Unclamp Limit Switch Move Conveyor Conveyor On Conveyor Index Limit Switch

RLLPLUS Programming Basics

Check Mode

Check 1-cycle Switch ON Jump to Wait for Start

DL305 User Manual, Rev. D

Check 1-cycle Switch OFF Jump to Check for Part

Page 234

RLL PLUS Programming Basics Step 6: Determine Stage Numbering

10--33

You can number the stages any way you would like, but it’s usually best to follow some type of sequence that matches the flow of the program. This makes it much easier to understand. There are a few guidelines we have used to determine the best numbering sequence. You don’t have to follow these guidelines, but they may help. You can typically find these types of operations in any program. S Sequential Operations, a certain sequence of events, one after the other. This is usually the main part of the program. It’s usually best to number these first. For example, you may want to always number these stages from 0 -- 127 (octal). S Independent Operations, these operations usually only perform one task, such as activating a motor or turning on a horn. For example, you may want to number all independent operations starting from 130 -- 147 (octal). S Alarm and Monitoring Operations, These operations usually monitor the main parts of the program. Since you may want to reset parts of the program during an alarm condition, it is usually best to number these last. This way you can use one Reset (RST) instruction to reset almost the entire program. Use stages 150 -- 177 for alarming and monitoring stages. These guidelines are especially helpful if you have many different programs. By using a standard numbering scheme, you always know where to look for the various types of operations. The example shows how we assigned numbers for the example press. Notice we’ve also made a separate stage for the clamp. This was not an absolute requirement because there are several ways you could have done this. We just did it to show you an example of an independent operation.

RLLPLUS Programming Basics

DL305 User Manual, Rev. D

Page 235

10--34

RLL PLUS Programming Basics

Initial Stage 0 Wait for Start

Press Start Switch Stage 1 Check for Part

Stage 150 Monitor for Stop

Stop Switch

Part in place

Reset all Operations

No Part Jump to Move Conveyor

Stage 2 Lock the Clamp Clamp On

Jump to Wait for Start

Clamp Limit Switch

Stage 140 Clamp

Stage 3 Press the Part Clamp

Press On Press Lower Limit Switch Stage 4 Unlock the Clamp Press Up

Clamp Off

Unclamp Limit Switch Stage 5 Move the Conveyor Conveyor On Conveyor Index Limit Switch Stage 6 Check Mode

RLLPLUS Programming Basics

Check 1-cycle Switch ON Jump to Wait for Start

DL305 User Manual, Rev. D

Check 1-cycle Switch OFF Jump to Check for Part

Page 236

RLL PLUS Programming Basics

10--35

The final step before you enter the program is to assign the I/O addresses and the destinations for any Jump, Set, or Reset instructions.

Step 7: Assign I/O Addresses

Initial Stage 0 Wait for Start

Press Start Switch

Stage 1 Check for Part

Stage 150 Monitor for Stop

Stop Switch

000

010

Part in place Reset All Operations RST S0 -- S140

Jump to Wait for Start

001

No Part Jump to Move Conveyor

Stage 2 Lock the Clamp

Clamp Limit Switch

Stage 140 Clamp

002

Clamp SET S140

Stage 3 Press the Part Clamp OUT 020

Press Lower Limit Switch

004

Press On OUT 021

Stage 4 Unlock the Clamp Press Up

Unclamp Limit Switch

005 003

Clamp RST S140

Stage 5 Move the Conveyor

006

Conveyor Index Limit Switch

Conveyor OUT 022

Stage 6 Check Mode Check 1-cycle Switch OFF

007 Closed Jump to Wait for Start

007 Open Jump to Check for Part

DL305 User Manual, Rev. D

RLLPLUS Programming Basics

Check 1-cycle Switch ON

Page 237

10--36

RLL PLUS Programming Basics

Step 8: Enter the Program

The following diagram shows how the program would look when viewed as a ladder program. ISG

Start

S1 JMP

000 SG

A

Wait forStart

S000

020 S2 JMP

001 S6 JMP

001

Clamp SET S140 S3 JMP

002

Press the part

S003

Press Down 021 Lower Limit

S4 JMP

004

Unclamp the part

S004 Top Limit

Clamp RST S140

005 Part Unlocked

S5 JMP

003 SG

Index the conveyor

S005

Move Conveyor 022 Conveyor Moved

S6 JMP

006 SG

RLLPLUS Programming Basics

A

One cycle or automatic?

S006 One Cycle

S0 JMP

007 One Cycle 007

DL305 User Manual, Rev. D

SG

Check for Stop

S150 Stop 010

Clamp the part

S002

Part Locked

SG

Clamp OUT

Check for a Part

S001

Part Present

SG

Clamp

S140

S150 JMP

Part Present

SG

SG

S1 JMP

S0 -- S140 RST S000 JMP

Page 238

RLL PLUS Programming Basics

10--37

This diagram shows how a portion of the program would look when viewed as a Stage Diagram in DirectSOFT. Wait forStart ISG S0

Check for a Part J

SG S1

Clamp the part J

SG S2

J

SG S6

Clamp S

Press the part J

Check for Stop J

SG S150

J

ISG S0

R

SG S140

SG S140

SG S3

RLLPLUS Programming Basics

DL305 User Manual, Rev. D

Page 239