The text of a manual · part 9 of 11

DL305 Handheld Programmer, pages 81 to 90

Pages 81 to 90 of 107

The original document is the PDF (2.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Koyo D3-HP

Page 81

System Monitoring and Troubleshooting In This Chapter. . . ., Troubleshooting Suggestions, Monitoring Discrete Points, Forcing Discrete Points, Monitoring Register Locations, Changing Register Values, Monitoring Timer/Counter Values, Changing Timer/Counter Values, Monitoring Program Stages, Forcing Program Stages, Error Codes

16

Page 82

System Monitoring and Troubleshooting

6--2

System Monitoring and Troubleshooting

Troubleshooting Suggestions The Handheld is very useful in troubleshooting your machine. As with any problem, you have to find it before you can fix it. There are several operations and features that help you quickly find the exact cause of system problems. S Monitor Discrete I/O Points, to examine I/O power flow for individual I/O points. S Force Discrete I/O Points, to examine machine sequences or inconsistencies. S Monitor Register Locations, to examine word locations to determine if correct values are being used. S Change Register Values, to force word locations with different values. S Monitor Timer/Counter Values, to adjust machine timing elements. S Understand Error Codes, to know where to look first.

Page 83

6--3

System Monitoring and Troubleshooting

You can monitor up to 16 discrete points at one time. The points can be from the following data types. S Inputs S Output S Control relays The status display area is also used to show the status for the points being monitored. Here’s how the display is organized. Indicates I/O Status Display

Reference Number n050 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

16 LEDs Total show on/off status

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

50--57

60--67

Use the following keystrokes to monitor discrete points. To select a different data type, use the corresponding reference number instead of the one shown. The DL305 memory map is included in Appendix A. This will help you determine the appropriate ranges for the various data types. Select the reference number to monitor SHF

5

0

MON n050 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

Use PRV or NXT to scroll through the references (8 point increments) PRV n040 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

System Monitoring and Troubleshooting

Monitoring Discrete Points

Page 84

System Monitoring and Troubleshooting

6--4

System Monitoring and Troubleshooting

Forcing Discrete Points You can also force discrete points with the Handheld Programmer. It is important to note that the DL305 CPUs only retain the forced value for one scan if the output point is used in the logic program or if the input point used corresponds to module that is installed in the base. The following example shows how the forcing actually works. Force 050 ON

Force I/O Points 000

002

005

001

003

010

Force 010 ON

007

050

004 051

END

On due to 010 forced ON

Next Scan

010 is off”

CPU reads the I/O status from the modules. Sees that point 010 is off, overwrites force to turn off 010.

Read Inputs

000

002

005

001

003

010

Force is overwritten

007

050

004 051

Logic is solved. Point 010, even though previously forced on, is turned off. Points 050 and 051 are turned off since conditions are not met.

END

050 and 051 are off

Update Outputs

CPU updates the output status with the results obtained from the logic execution. Y0 and Y1 were turned off.

NOTE: If you use a CR as an input, you will not have the “one scan” problem.

Page 85

6--5

System Monitoring and Troubleshooting

WARNING: Depending on your application, forcing I/O points may cause unpredictable machine operation that can result in a risk of personal injury or equipment damage. To turn a point on CLR

SET

SHF

Display returns to address display 5

0

0000 .... ADDRESS/DATA

ENT

ON/OFF

RUN BATT PWR CPU

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

Monitor the point to verify the force (optional) CLR

SHF

5

0

MON n050 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

To turn a point off CLR ENT

RST

SHF

Display returns to address display 5

0

0000 .... ADDRESS/DATA

ON/OFF

RUN BATT PWR CPU

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

System Monitoring and Troubleshooting

The following example shows the keystrokes required to force an I/O point.

Page 86

System Monitoring and Troubleshooting

6--6

System Monitoring and Troubleshooting

Monitoring Register Locations You can use the Handheld to monitor and change register locations. When a register is monitored, the handheld programmer will display two register locations (eight bits each) this means that 4 digits of data will be shown. Since data register locations are 8-bit locations, two consecutive data registers will be displayed. When changing values in data register locations, you can also write two consecutive data register locations. Select the location to monitor CLR

R

4

0

0

R401

R400

1453 ADDRESS/DATA

MON

ON/OFF

RUN BATT PWR CPU

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

Changing Register Values Select the location to monitor CLR

R

4

0

0

R401

R400

1453 ADDRESS/DATA

MON

ON/OFF

RUN BATT PWR CPU

Enter the new value SHF ENT

1

3

5

R401

4

R400

1354 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Page 87

6--7

System Monitoring and Troubleshooting

You can also use the Handheld to monitor and/or change timer and counter current values. There are two ways to do this. You can use the register monitoring procedure discussed previously which will display the current value with the decimal point implied for timers. The second method uses slightly different keystrokes and will show timer current values with the decimal point. Using this method also uses the instructions LEDs to indicate the last two digits of the timer/counter memory reference. Select the location to monitor CLR

SHF

6

0

0

4569 . ADDRESS/DATA

MON

Shows accumulated time or count

ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

00--07 10--17 LEDs show last two digits of the register reference number

Changing Timer/Counter Current Values Select the timer location to monitor CLR

SHF

6

0

0

4569 . ADDRESS/DATA

MON

ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

Enter the new value SHF ENT

1

3

5

4

1354 . ADDRESS/DATA

ON/OFF

RUN BATT PWR CPU

System Monitoring and Troubleshooting

Monitoring Timer/Counter Current Values

Page 88

System Monitoring and Troubleshooting

6--8

System Monitoring and Troubleshooting

Monitoring Program Stages The RLL PLUS CPUs also have stages that can be monitored. This is especially useful since it can quickly show you exactly which parts of the program are being executed. The procedure is very similar to the one used for monitoring discrete I/O points. Here’s how the display is organized. Indicates Stage Status Display

Stage Number s010 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

16 LEDs Total Show on/off status

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

10--17

20--27

Page 89

6--9

System Monitoring and Troubleshooting

Select the stage number to monitor SG

SHF

1

0

MON s010 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

Use PRV or NXT to scroll through the references (8 stage increments) PRV n020 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0

4

0

4

1

5

1

5

2

6

2

6

3

7

3

7

System Monitoring and Troubleshooting

Use the following keystrokes to monitor the stages.

Page 90

System Monitoring and Troubleshooting

6--10

System Monitoring and Troubleshooting

Forcing Program Stages You can also force Program Stages with the Handheld Programmer. However, due to the self-contained nature of this style of programming, you can really cause some problems by forcing stages on and off. It is important to note that the DL305 CPUs only retain the forced value for one scan if the logic within the stage (or another stage) causes the status to be discarded. The following example shows how the forcing actually works. Assume that the saw takes approximately 10 seconds to reach the bottom limit. (Which is many, many, CPU scans.)

Force a Stage ON Stage 10

Stop 005

RST all stages Jump to Stage 0

Stage 5 forced ON

Current Stage ISG 0

Start 000

Stage 1

Pipe limit 001

Stage 2

Clamped 002

Bottom 003

Stage 3

Stage 4

Top 004

Stage 5

020

021

022

023

024

022

021

Converyor

SET Clamp

SET Saw Saw Down On

Saw Up

RST Saw Off

RST Clamp

Next Scan Stage 10

Stop 005

RST all stages

Clamp is reset, which may cause a saw jam.

Jump to Stage 0

ISG 0

Start 000

Stage 1

Pipe limit 001

Stage 2

Clamped 002

Bottom 003

Stage 3

Stage 4

Top 004

Stage 5

020

021

022

023

024

022

021

Converyor

SET Clamp

SET Saw Saw Down On

Saw Up

RST Saw Off

RST Clamp