Page 81
System Monitoring and Troubleshooting In This Chapter. . . ., Troubleshooting Suggestions, Monitoring Discrete Points, Forcing Discrete Points, Monitoring Register Locations, Changing Register Values, Monitoring Timer/Counter Values, Changing Timer/Counter Values, Monitoring Program Stages, Forcing Program Stages, Error Codes
16
Page 82
System Monitoring and Troubleshooting
6--2
System Monitoring and Troubleshooting
Troubleshooting Suggestions The Handheld is very useful in troubleshooting your machine. As with any problem, you have to find it before you can fix it. There are several operations and features that help you quickly find the exact cause of system problems. S Monitor Discrete I/O Points, to examine I/O power flow for individual I/O points. S Force Discrete I/O Points, to examine machine sequences or inconsistencies. S Monitor Register Locations, to examine word locations to determine if correct values are being used. S Change Register Values, to force word locations with different values. S Monitor Timer/Counter Values, to adjust machine timing elements. S Understand Error Codes, to know where to look first.
Page 83
6--3
System Monitoring and Troubleshooting
You can monitor up to 16 discrete points at one time. The points can be from the following data types. S Inputs S Output S Control relays The status display area is also used to show the status for the points being monitored. Here’s how the display is organized. Indicates I/O Status Display
Reference Number n050 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
16 LEDs Total show on/off status
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
50--57
60--67
Use the following keystrokes to monitor discrete points. To select a different data type, use the corresponding reference number instead of the one shown. The DL305 memory map is included in Appendix A. This will help you determine the appropriate ranges for the various data types. Select the reference number to monitor SHF
5
0
MON n050 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
Use PRV or NXT to scroll through the references (8 point increments) PRV n040 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
System Monitoring and Troubleshooting
Monitoring Discrete Points
Page 84
System Monitoring and Troubleshooting
6--4
System Monitoring and Troubleshooting
Forcing Discrete Points You can also force discrete points with the Handheld Programmer. It is important to note that the DL305 CPUs only retain the forced value for one scan if the output point is used in the logic program or if the input point used corresponds to module that is installed in the base. The following example shows how the forcing actually works. Force 050 ON
Force I/O Points 000
002
005
001
003
010
Force 010 ON
007
050
004 051
END
On due to 010 forced ON
Next Scan
010 is off”
CPU reads the I/O status from the modules. Sees that point 010 is off, overwrites force to turn off 010.
Read Inputs
000
002
005
001
003
010
Force is overwritten
007
050
004 051
Logic is solved. Point 010, even though previously forced on, is turned off. Points 050 and 051 are turned off since conditions are not met.
END
050 and 051 are off
Update Outputs
CPU updates the output status with the results obtained from the logic execution. Y0 and Y1 were turned off.
NOTE: If you use a CR as an input, you will not have the “one scan” problem.
Page 85
6--5
System Monitoring and Troubleshooting
WARNING: Depending on your application, forcing I/O points may cause unpredictable machine operation that can result in a risk of personal injury or equipment damage. To turn a point on CLR
SET
SHF
Display returns to address display 5
0
0000 .... ADDRESS/DATA
ENT
ON/OFF
RUN BATT PWR CPU
0 AND 1 OR 2 STR 3 NOT
4 OUT 5 TMR 6 CNT 7 SR
0 MCS 1 MCR 2 SET 3 RST
4 ADR 5 SHF 6 DATA 7 REG
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
Monitor the point to verify the force (optional) CLR
SHF
5
0
MON n050 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
To turn a point off CLR ENT
RST
SHF
Display returns to address display 5
0
0000 .... ADDRESS/DATA
ON/OFF
RUN BATT PWR CPU
0 AND 1 OR 2 STR 3 NOT
4 OUT 5 TMR 6 CNT 7 SR
0 MCS 1 MCR 2 SET 3 RST
4 ADR 5 SHF 6 DATA 7 REG
System Monitoring and Troubleshooting
The following example shows the keystrokes required to force an I/O point.
Page 86
System Monitoring and Troubleshooting
6--6
System Monitoring and Troubleshooting
Monitoring Register Locations You can use the Handheld to monitor and change register locations. When a register is monitored, the handheld programmer will display two register locations (eight bits each) this means that 4 digits of data will be shown. Since data register locations are 8-bit locations, two consecutive data registers will be displayed. When changing values in data register locations, you can also write two consecutive data register locations. Select the location to monitor CLR
R
4
0
0
R401
R400
1453 ADDRESS/DATA
MON
ON/OFF
RUN BATT PWR CPU
0 AND 1 OR 2 STR 3 NOT
4 OUT 5 TMR 6 CNT 7 SR
0 MCS 1 MCR 2 SET 3 RST
4 ADR 5 SHF 6 DATA 7 REG
0 AND 1 OR 2 STR 3 NOT
4 OUT 5 TMR 6 CNT 7 SR
0 MCS 1 MCR 2 SET 3 RST
4 ADR 5 SHF 6 DATA 7 REG
0 AND 1 OR 2 STR 3 NOT
4 OUT 5 TMR 6 CNT 7 SR
0 MCS 1 MCR 2 SET 3 RST
4 ADR 5 SHF 6 DATA 7 REG
Changing Register Values Select the location to monitor CLR
R
4
0
0
R401
R400
1453 ADDRESS/DATA
MON
ON/OFF
RUN BATT PWR CPU
Enter the new value SHF ENT
1
3
5
R401
4
R400
1354 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
Page 87
6--7
System Monitoring and Troubleshooting
You can also use the Handheld to monitor and/or change timer and counter current values. There are two ways to do this. You can use the register monitoring procedure discussed previously which will display the current value with the decimal point implied for timers. The second method uses slightly different keystrokes and will show timer current values with the decimal point. Using this method also uses the instructions LEDs to indicate the last two digits of the timer/counter memory reference. Select the location to monitor CLR
SHF
6
0
0
4569 . ADDRESS/DATA
MON
Shows accumulated time or count
ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
00--07 10--17 LEDs show last two digits of the register reference number
Changing Timer/Counter Current Values Select the timer location to monitor CLR
SHF
6
0
0
4569 . ADDRESS/DATA
MON
ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
Enter the new value SHF ENT
1
3
5
4
1354 . ADDRESS/DATA
ON/OFF
RUN BATT PWR CPU
System Monitoring and Troubleshooting
Monitoring Timer/Counter Current Values
Page 88
System Monitoring and Troubleshooting
6--8
System Monitoring and Troubleshooting
Monitoring Program Stages The RLL PLUS CPUs also have stages that can be monitored. This is especially useful since it can quickly show you exactly which parts of the program are being executed. The procedure is very similar to the one used for monitoring discrete I/O points. Here’s how the display is organized. Indicates Stage Status Display
Stage Number s010 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
16 LEDs Total Show on/off status
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
10--17
20--27
Page 89
6--9
System Monitoring and Troubleshooting
Select the stage number to monitor SG
SHF
1
0
MON s010 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
Use PRV or NXT to scroll through the references (8 stage increments) PRV n020 ADDRESS/DATA ON/OFF
RUN BATT PWR CPU
0
4
0
4
1
5
1
5
2
6
2
6
3
7
3
7
System Monitoring and Troubleshooting
Use the following keystrokes to monitor the stages.
Page 90
System Monitoring and Troubleshooting
6--10
System Monitoring and Troubleshooting
Forcing Program Stages You can also force Program Stages with the Handheld Programmer. However, due to the self-contained nature of this style of programming, you can really cause some problems by forcing stages on and off. It is important to note that the DL305 CPUs only retain the forced value for one scan if the logic within the stage (or another stage) causes the status to be discarded. The following example shows how the forcing actually works. Assume that the saw takes approximately 10 seconds to reach the bottom limit. (Which is many, many, CPU scans.)
Force a Stage ON Stage 10
Stop 005
RST all stages Jump to Stage 0
Stage 5 forced ON
Current Stage ISG 0
Start 000
Stage 1
Pipe limit 001
Stage 2
Clamped 002
Bottom 003
Stage 3
Stage 4
Top 004
Stage 5
020
021
022
023
024
022
021
Converyor
SET Clamp
SET Saw Saw Down On
Saw Up
RST Saw Off
RST Clamp
Next Scan Stage 10
Stop 005
RST all stages
Clamp is reset, which may cause a saw jam.
Jump to Stage 0
ISG 0
Start 000
Stage 1
Pipe limit 001
Stage 2
Clamped 002
Bottom 003
Stage 3
Stage 4
Top 004
Stage 5
020
021
022
023
024
022
021
Converyor
SET Clamp
SET Saw Saw Down On
Saw Up
RST Saw Off
RST Clamp