Page 1 of Koyo D4-08TA and PLC Direct D4-08TA Spec Sheet

Spec sheet · Koyo

Koyo D4-08TA and PLC Direct D4-08TA Spec Sheet

Spec sheet3 pagesPDF 591 KB

All 3 pages are below, each with its text.

Download the PDF591 KB

Covers · 2 models

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Three catalog pages for DL405 AC output modules: a specification table for the D4-08TA and D4-16TA, a worked DL405 power budget example, and the DL405 power supplied and consumed tables. It helps check the module's ratings and whether a base has enough power for it.

Type
AC output module p. 1
Output type
SSR (triac) p. 1
Operating voltage
15-265VAC, 265VAC peak p. 1
AC frequency
47-63Hz p. 1
Commons
2 (isolated) p. 1
Minimum load
10mA p. 1
Response time
OFF to ON 1ms; ON to OFF 1ms + 1/2 cycle p. 1
Terminal type
Removable, included p. 1
Status indicators
Logic side p. 1
Fuses
1 per common, non-replaceable p. 1
PLC family
DL405, listed in the DL405 power requirements table p. 2, 3

What this sheet walks you through

  • Calculating the power budget for a DL405 base p. 2
  • Looking up power supplied by DL405 CPUs and units and consumed by modules p. 3

Good to know

  • With the ZIPLink wiring system, the sheet derates relay outputs to 2 Amps per point max. p. 1
  • Exceeding the base power budget may make the system operate unpredictably. p. 2

Questions this sheet answers

What voltage can the D4-08TA switch?

The sheet gives an operating voltage of 15-265VAC at 47-63Hz, with SSR (triac) outputs. p. 1

Are the fuses on the D4-08TA replaceable?

No. The sheet lists one fuse per common, non-replaceable. p. 1

Which PLC family is the D4-08TA for?

It appears among the AC output modules in the DL405 power requirements table. p. 2, 3

The file

Size and text

Pages3
PDF591 KB
TextText from the PDF itself.

Every page · 3

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Koyo D4-08TA and PLC Direct D4-08TA Spec Sheet

The text of page 1, from the PDF itself

AC Output Modules

Company Information Systems Overview

D4-08TA AC Output Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage AC Frequency ON Voltage Drop

<--->

8 2 (isolated) 15-265VAC SSR (triac) 265VAC 47-63Hz 1.5VAC @ 2A

D4-16TA AC Output Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage AC Frequency ON Voltage Drop

16265VAC 47-63HzDrives1.5VAC @ 0.5ASoft Starters

0.5A/point 3A/common @ 45° C 2A/common @ 60° C

Max Leakage Current5mA @ 265VACMax Leakage Current4mA @ 265VACMax Inrush Current

30A for 10ms 10A for 100ms

Max Inrush Current

Minimum Load Base Power Required 5V OFF to ON Response ON to OFF Response Terminal Type (included Status Indicators Weight Fuses

15A for 10ms 10A for 100ms

10mA

Minimum Load Base Power Required 5V OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight Fuses

10mA

Removable (D4-8IOCON) Logic side 11.6oz. (330g) 1 (8A) per common, non-replaceable

C-more & other HMISSR (triac)Max Current1ms + 1/2 cycleSoftware15-265VAC

2A/point 5A/common @ 30° C 2A/common @ 60° C

1msField I/O2 (isolated)Max Current250mA max

Programmable Controllers

<--->

Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors

450mA max 1ms

Photo Sensors

1ms + 1/2 cycle Removable (D4-16IOCON)

Limit Switches

Logic Side Encoders

12.2oz. (350g) 1 (5A) per common, non-replaceable

See page 6-57 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.

Current Sensors Pressure Sensors

Note: When used with the ZIPLink wiring system, relay outputs are derated not to exceed 2 Amps per point max.

Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index

Volume 13

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-71

Page 2 of Koyo D4-08TA and PLC Direct D4-08TA Spec Sheet

The text of page 2, from the PDF itself

Check the Power Budget Verify your power budget requirements

This logo is placed next to I/O modules that are supported by the ZIPLink connection systems. See the I/O module specifi-

Calculating your power usage

Your I/O configuration choice can be affected by the power requirements of the I/O modules you choose. When determining the types and quantity of I/O modules you will be using, it is important to remember there is a limited amount of power available from the power supply.

cations at the end of this section.

The following example shows how to calculate the power budget for the DL405 system. The example is constructed around a single 8-slot base using the devices shown. It is recommended you construct a similar table for each base in your system.

The chart on the opposite page indicates the power supplied and used by each DL405 device. The adjacent chart shows an example of how to calculate the power used by your particular system. These two charts should make it easy for you to determine if the devices you have chosen fit within the power budget of your system configuration.

A Base Number 0

B

Use ZIPLinks to reduce power requirements If your application requires a lot of relay outputs, consider using the ZipLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to page 6-57 for more information.

5 VDC (mA)

External 24 VDC Power (mA)

CURRENT SUPPLIED CPU/Expansion Unit /Remote Slave

D4-440 CPUC3700400

CURRENT REQUIRED SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7

D4-16ND2+150+0D4-16ND2+150+0F4-04DA+120+100D4-08ND3S+100+0D4-08ND3S+100+0D4-16TD2+100+0D4-16TD2+100+0D4-16TR+1000+0

BASE Handheld Programmer

D4-08B+80+0D4-HPP+320+0

E Maximum Current Required

2820

100

F Remaining Current Available

3700-2820=880

400-100=300

If the I/O you have chosen exceeds the maximum power available from the power supply, you can resolve the problem by shifting some of the modules to an expansion base or remote I/O base (if you are using remote I/O). Warning: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

Device TypeDOTHER

1. Using a chart similar to the 3one above, fill in column 2. 2. Using the tables on the opposite page, enter the current supplied and used by each device (columns 3 and 4). Pay special attention to the current supplied by the CPU, Expansion Unit, and Remote Slave since they differ. Devices which fall into the "Other" category (Row D) are devices such as the Base and the Handheld programmer, which also have power requirements, but do not plug directly into the base. 3. Add the current used by the system devices (columns 3 and 4) starting with Slot 0 and put the total in the row labeled "maximum current required" (Row E). 4. Subtract the row labeled "Maximum current required" (Row E), from the row labeled "Current Supplied" (Row B). Place the difference in the row labeled "Remaining Current Available" (Row F). 5. If "Maximum Current Required" is greater than "Current Supplied" in either column 3 or 4, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration. Note the auxiliary 24 VDC power supply does not need to supply all the external power. If you need more than the 400mA supplied, you can add an external 24VDC power supply. This will help keep you within your power budget for external power.

DL405 CPU power supply specifications and power requirements Specification Part Numbers

AC Powered Units D4-450, D4-440, D4-430, D4-EX (expansion base unit), D4-RS (remote slave unit)

Voltage Withstand (dielectric) Insulation Resistance

24 VDC Powered Units D4-450DC-1, D4-440DC-1, D4-EXDC (expansion base unit), D4-RSDC (remote slave unit)

125 VDC Powered Units D4-450DC-2 D4-440DC-2

1 minute @ 1,500 VAC between primary, secondary, field ground, and run relay > at 500VDC

Input Voltage Range

85-132 VAC (110 range) 170-264 VAC (220 range

20-28 VDC (24 VDC) with less than 10% ripple

90-146 VDC (125 VDC) with less than 10% ripple

Maximum Inrush Current Maximum Power

20 A20 A20 A50 VA38 W30 WVolume 13e6-24

Programmable Controllers

1 - 80 0 - 633 - 0405

Page 3 of Koyo D4-08TA and PLC Direct D4-08TA Spec Sheet

The text of page 3, from the PDF itself

Power Requirements

Company Information Systems Overview Programmable Controllers

Power Supplied CPUs/Remote Units/ Expansion Units

5 VDC Current Supplied in mA

24V Aux Power Supplied in mA

CPUs/Remote Units/Expansion Units

5V Current Supplied in mA

24VAux. Power Supplied in mA

D4-430 CPU D4-440 CPU D4-440DC-1 CPU D4-440DC-2 CPU D4-450 CPU D4-450DC-1 CPU D4-450DC-2 CPU

3700 3700 3700 3700 3100 3100 3100

400 400 NONE NONE 400 NONE NONE

D4-EX D4-EXDC D4-EXDC-2 D4-RS D4-RSDC H4-EBC H4-EBC-F

4000 4000 3700 3700 3700 3470 3300

400 NONE NONE 400 NONE 400 400

Field I/O Software C-more & other HMI Drives

Power Consumed Power-consuming Device I/O Bases

5V Current Consumed

D4-04B-1 D4-06B-1 D4-08B-1

80 80 80

External 24VD Current Required

NONE NONE NONE

DC Input Modules

D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2

100 150 150 150 150 300 max.

NONE NONE NONE NONE NONE NONE

Power-consuming 5V Current Device Consumed Analog Modules (continued)

External 24VDC Current Required

F4-16AD-1 F4-16AD-2 F4-04DA-1 F4-04DA-2 F4-04DAS-1 F4-04DAS-2 F4-08DA-1 F4-08DA-2 F4-16DA-1 F4-16DA-2 F4-08RTD F4-08THM-n F4-08THM

100 100 75+20per circuit 90 60 per circuit 60 per circuit 100+20 per circuit 150 100+20 per circuit 25 max. NONE 50 60

75 75 70 90 60 60 90 80 90 80 80 120 110

Motors & Gearbox

100 150

Photo Sensors Limit Switches

NONE NONEH4-ERM H4-ERM-F D4-RM320 450 300NONE NONE NONE

Pressure Sensors Temperature Sensors

150 90

D4-08TD1 F4-08TD1S D4-16TD1 D4-16TD2 D4-32TD1 D4-32TD1-1 D4-32TD2

150 295 200 400 250 250 350

D4-64TD1800NONE NONE

35 NONE 125 NONE 140 140 (15V) 120 (4A max including loads) NONE

Communications and Networking H4-ECOM100 H4-ECOM H4-ECOM-F D4-DCM F4-MAS-MB FA-UNICON

300 530 670 500 235 NONE

Pushbuttons/ Lights

NONE NONE NONE NONE NONE 65

Process Relays/ Timers Comm.

CoProcessors F4-CP128-1

Terminal Blocks & Wiring

305

NONE Power

AC Output Modules 250 450

NONE NONE

Relay Output Modules D4-08TR F4-08TRS-1 F4-08TRS D4-16TR

Proximity SensorsCurrent SensorsDC Output ModulesD4-08TA D4-16TAMotor ControlsEncoders

AC/DC Input Modules D4-16NE3 F4-08NE3S

Steppers/ Servos

Remote I/O

AC Input Modules D4-08NA D4-16NA

Soft Starters550 575 575 1000NONE NONE NONE NONE

Specialty Modules H4-CTRIO D4-INT D4-HSC F4-16PID F4-8MPI D4-16SIM F4-4LTC

Circuit Protection

400 100 300 160 225 150 280

NONE NONE NONE NONE 170 NONE 75

Enclosures Tools Pneumatics Appendix

Analog ModulesProgramming 320NONEProduct IndexDV-1000150NONEPart # IndexC-more Micro-Graphic210NONE

D4-HPP-1 (Handheld Prog.) F4-04AD F4-04ADS F4-08AD

85 270 75100 120 90Operator InterfaceVolume 13

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-25

More documents · 1

For the same models