A one-page specification sheet for two AC output modules, the D4-08TA and D4-16TA, printed side by side. It gives their electrical ratings, derating charts and wiring diagrams. The facts below are those the two modules share.
- Operating voltage
- 15 to 265VAC, 265VAC peak p. 1
- Output type
- SSR (triac) p. 1
- AC frequency
- 47 to 63 Hz p. 1
- Commons
- 2 (isolated) p. 1
- Minimum load
- 10 mA p. 1
- Response time
- OFF to ON 1 ms; ON to OFF 1 ms + 1/2 cycle p. 1
- Current at 60 C
- 2A per common at 60 °C p. 1
- Inrush current
- 10A for 100 ms p. 1
- Terminal type
- Removable p. 1
- Status indicators
- Logic side p. 1
- Fuses
- 1 per common, non-replaceable p. 1
- Isolation
- Optical isolator in the output circuit p. 1
What this manual walks you through
Questions this manual answers
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
Outputs per module8Outputs per module16Commons per module2 (isolated)Commons per module2 (isolated)Operating voltage15–265VACOperating voltage15–265VACOutput typeSSR (triac)Output typeSSR (triac)Peak voltage265VACPeak voltage265VACAC frequency47–63 HzAC frequency47–63 HzON voltage drop1.5VAC @ 2AON voltage drop1.5 VAC @ 0.5AMax current
2A / point 5A / common @ 30 °C 2A / common @ 60 °C
Max current
0.5A / point 3A / common @ 45 °C 2A / common @ 60 °C
Max leakage current5mA @ 265VACMax leakage current4mA @ 265VACMax inrush current
15A for 10 ms 10A for 100 ms
Minimum load10 mABase power required 5v450 mA maxOFF to ON response1 msON to OFF response1 ms +1/2 cycleTerminal typeRemovableStatus indicatorsLogic SideWeight12.2 oz. (350 g)Fuses
1 (5A) per common Non-replaceable
Max inrush current
30A for 10 ms 10A for 100 ms
Minimum load10 mABase power required 5v250 mA maxOFF to ON response1 msON to OFF response1 ms +1/2 cycleTerminal typeRemovableStatus indicatorsLogic SideWeight11.6 oz. (330 g)Fuses
1 (8A) per common Non-replaceable Points Derating Chart
Points
18–220VAC
8 Output Current 1A/point 4
TB
Output Current 0.5A/point
Output Current 2A/point (5A/common)
2Derating Chart160 1 2 3
Output Current 0.35A/point
OUTPUT 12
FU
Output Current 0.5A/point
84 5 6 72A/common4
15–265VAC 10mA–2A 50/60Hz
CA L0L LL L12L L18–220 VACLL0L15CBLL7LL L2L4 0 57L47 CB6L6L35L L64L34L26 CB18–220 VACCB457L05 3L234 5 6 712L0 1 2 34 1L1L0L0B 4 5 6 7L18–220 VAC18–220 VACCAFU A0 1 2 3
15–265VAC 10mA–0.5A 50/60Hz CA
° Ambient Temperature (°C/°F)
CAOUTPUTTB31 652 Output76Optical IsolatorOutputL7 18–220 VAC CommonOptical Isolator3L18–220 VAC To LEDCommonTo LED0018–220VACD4–16TA3A/commonD4–08TA
° Ambient Temperature (°C/°F)
Output Current 0.25A/point