A one-page catalog specification sheet for two input modules: the D4-16NA-1 AC input module and the D4-16NE3 AC/DC input module. It does not name the D4-16NA the site files it under. It lists input ratings, response times, terminal block and weight for each module.
- What it covers
- D4-16NA-1 AC input module and D4-16NE3 AC/DC input module p. 1
- D4-16NA-1 inputs
- 16 inputs, 2 isolated commons, 187-238 VAC, 47-63 Hz p. 1
- D4-16NA-1 levels
- ON above 150 V, OFF below 40 V, 22K input impedance p. 1
- D4-16NA-1 current
- 10.0 mA at 220 VAC p. 1
- D4-16NA-1 timing, power
- OFF to ON 5-30 ms, ON to OFF 10-50 ms, 150 mA max from the 5 V base p. 1
- D4-16NA-1 weight
- 9.2 oz (260 g) p. 1
- D4-16NE3 inputs
- 16 sink/source inputs, 2 isolated commons, 10.2-26.4 VAC/VDC p. 1
- D4-16NE3 current
- 3.8 mA at 12 V, 8.3 mA at 24 V p. 1
- D4-16NE3 weight
- 8.8 oz (250 g) p. 1
- Terminal block
- Removable D4-16IOCON, included p. 1
- Wiring accessories
- ZIPLink cables and terminal blocks, listed elsewhere in the catalog p. 1
What this manual walks you through
- Comparing the input specifications of the D4-16NA-1 and D4-16NE3 p. 1
Questions this manual answers
What voltage does the D4-16NA-1 accept?
187-238 VAC at 47-63 Hz, with a 265 VAC peak. p. 1
What terminal block does the D4-16NA-1 use?
A removable D4-16IOCON terminal block, which the sheet lists as included. p. 1
Is the D4-16NE3 sinking or sourcing?
Its 16 inputs are sink/source, rated 10.2-26.4 VAC/VDC. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
AC and AC/DC Input Modules D4-16NA-1 AC Input Inputs per Module Commons per Module Input Voltage Range Peak Voltage AC Frequency ON Voltage Level OFF Voltage Level Input Impedance Input Current Minimum ON Current Maximum OFF Current Base Power Required 5V OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight
16 2 (isolated) 187-238VAC 265VAC 47-63Hz >150V <40V
PLC Products
Inputs per Module Commons per Module Input Voltage Range Peak Voltage AC Frequency ON Voltage Level OFF Voltage Level
7mA 2mA 150mA max 5-30ms 10-50ms Removable (D4-16IOCON) Logic side 9.2oz. (260g)
<--->
16 (sink/source) 2 (isolated) 10.2-26.4VAC/VDC 37.5VAC/VDC 47-63Hz >9.5V <3.0V
Input Impedance3.2 @ 12V 2.9 @ 24VInput Current
3.8mA @ 12V 8.3mA @ 24V
Minimum ON Current Maximum OFF Current Base Power Required 5V OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight
4mA
10.0mA @ 220VAC
See the Terminal Blocks & Wiring Solutions section in this catalog for part numbers of ZIPLink cables and terminal blocks compatible with this module.
6–62D4-16NE3 AC/DC Input<--->
1.5mA 150mA max 5-40ms 10-50ms Removable (D4-16IOCON) Logic side 8.8oz. (250g)
See the Terminal Blocks & Wiring Solutions section in this catalog for part numbers of ZIPLink cables and terminal blocks compatible with this module.
1 - 80 0 - 633 - 0405